6ES5 308-3UB11

Siemens 6ES5 308-3UB11 — IM 308-B PROFIBUS-DP Master Interface

The Siemens 6ES5 308-3UB11 is an IM 308-B PROFIBUS-DP master interface module for SIMATIC S5 systems. It provides cyclic data exchange between S5-115U, S5-135U and S5-155U controllers and the ET 200 distributed I/O system. This S5 interface module supports a maximum transmission rate of 1.5 Mbit/s.

The module is fitted in the SIMATIC S5 central controller. The appropriate slot and any adapter arrangement depend on the rack model. When reviewing S5 communication hardware, assess the IM 308-B as the link between remote I/O data and the CPU.

Master and remote-station roles

The IM 308-B operates on the master side. ET 200U interfaces such as the 6ES5 318-8MB11 and 6ES5 318-8MB12 operate at the station. Their related 308/318 designations do not make them interchangeable modules.

The stations' digital input, digital output and analog input modules must match their configured positions. If module types, order or I/O allocation change, review the master project against the installed hardware.

COM ET 200 and configuration memory

The IM 308-B is parameterized using COM ET 200. When selecting PLC software, consider the module version and existing project file together. Its E(E)PROM configuration requires separate attention when handling S5 memory modules and EPROMs.

COM PROFIBUS cannot directly read an E(E)PROM programmed for the IM 308-B. Siemens specifies the COM ET 200 version that generated it, or a higher version, for reading its contents. Converting an old project file and reading the memory module are different operations.

DP Siemens and DP Standard requirements

The 318-8MB11 operates with DP Siemens. To operate the 318-8MB12 as a DP Standard slave, the manual requires COM ET 200 V4.0 or later and an IM 308-B from revision level 5 or software version 4.0 onward. The 3UB11 order number alone does not establish identical protocol support across all revisions.

Bus connection and field checks

Check the PROFIBUS cable, connectors and termination against the complete installation. Review grounding, cable shielding and connector-housing contact together. Preserve cable routing and mechanical support to maintain noise immunity.

Differences from the IM 308-A and IM 308-C

The 6ES5 308-3UA12 belongs to the IM 308-A connection arrangement and should not be confused with the IM 308-B's PROFIBUS-DP role. The 6ES5 308-3UC11 and 6ES5 308-3UC21 are IM 308-C models. An upgrade from B to C requires separate consideration of configuration, memory media and diagnostic software.

Siemens describes converting the old COM ET 200 project and exporting it to a memory card for the IM 308-C. Consequently, do not treat the IM 308-C as a replacement that runs simply by fitting the old E(E)PROM.

Installation and fault finding

Change the module or memory with system power switched off. During PLC debugging, first establish which stations are affected, then inspect the master configuration, station addresses, bus and field supplies together. Loss of all stations and failure of a single station may call for different checks.

Editor's note

Start with the complete 308-3UB11 label and the module's revision. Two similar-looking IM 308-B boards can have different revisions. A photograph of the old label is a useful starting point.

Before replacing the card, safeguard the project file and configuration memory. Finding a sound spare matters; keeping the machine's correct settings matters just as much.

If communication stops, give the rest of the network a fair check before condemning the master. A bus plug, termination or station supply can produce the same symptom. Find where the working connection ends.

Take care with the idea of simply fitting a C in place of a B. Without project conversion and memory preparation, even a sound card may not establish communication. Keep a record of the old working arrangement.

Where possible, test a used module with a known configuration and a working remote station. A test result kept with the ET 200 system information tells you more than illuminated LEDs alone.

OtomasyonAVM resources and PDFs

+ Start with the OtomasyonAVM ET 200 manuals and the S5 PDF archive.

+ For the exact order number, see S5-135U/155U System Manual, 2-5. Speed and migration information appear in ET 200 Distributed I/O System, 1-8 and 14-5–14-8; protocol/revision conditions appear in the ET 200U manual, preface iv–v. The documents below are in English.

Related topics

+ IM 318-B — 318-8MB11 · IM 318-B — 318-8MB12 · IM 308-C — 308-3UC11 · IM 308-C — 308-3UC21.

+ IM 308-A — 308-3UA12 · S5 memory modules · ET 200 manuals.

Browse SIMATIC S5

+ S5 interface modules · S5 communication modules · Siemens ET 200.

+ Siemens S5 main page · Used Siemens automation equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual — C79000-G8576-C199-07: page 2-5 lists 6ES5 308-3UB11 with the IM 318-B.

+ Siemens ET 200 Distributed I/O System — 2806161–0002: IM 308-B operation up to 1.5 Mbaud, software/memory compatibility and migration to the IM 308-C.

+ Siemens ET 200U Manual — EWA 4NEB 812 6087-02b: DP Siemens, DP Standard and master revision requirements.