6ES5 945-7UA11
Siemens 6ES5 945-7UA11 — S5-115U CPU 945 with 256 KB RAM
Siemens 6ES5 945-7UA11 is the S5-115U CPU 945 central processing unit in the Siemens S5 family. It has 256 KB of internal user memory. In a SIMATIC S5 installation, it executes the machine program, evaluates inputs and generates output commands. It has one serial interface and a receptacle for a second interface submodule.
The 6ES5 945-7UA21 is the 384 KB version. When comparing with related numbers such as 6ES5 945-7UA13 and 6ES5 945-7UA23, record the complete order number and hardware/software version together. Do not overlook the final suffix when planning a replacement.
RAM, Flash EPROM and program backup
The CPU copies the program from the memory card into internal RAM for execution. When selecting S5 memory products, compare card capacity with actual program size. Retaining RAM contents through a power failure requires battery backup. Verify separately that the memory card contains the current machine program.
For cards such as 6ES5 374-1KG11 and 6ES5 374-1KH21, the manufacturer’s table requires PG software V6.6 or later. Having a card does not establish that the correct backup is available. Keep the STEP 5 project, machine parameters and installed card number in the same maintenance record.
Program resources and execution time
The CPU 945 family provides 256 timers, 256 counters, 2048 flag bits and 32768 S flags. The specified 0.1 µs bit-operation time is an instruction time, not the complete program scan time. When assessing a program in Ladder or function block representation, measure the scan under actual operating load.
SI1 and the replaceable SI2 interface
SI1 is a 15-pin, 20 mA current-loop interface for PG, operator-panel or suitable SINEC L1 connections. Select the programming cable against the port’s own pin assignment. A matching connector shape does not make an ordinary serial cable suitable.
The electrical interface of SI2 depends on the installed submodule. Examples include the 6ES5 752-0LA52 PG submodule, 6ES5 752-0LA12 TTY submodule and 6ES5 752-0LA62 SINEC L1 submodule. Identify the interface hardware by its complete number. For communication settings, also check the partner device’s protocol and the existing project parameters.
Addressing, DB1 and maintenance preparation
Record the rack arrangement, power supply and installed modules before removal. Compare digital input, digital output and analog module addresses with the existing project and each module’s addressing information. Replacing the CPU is not a reason to change addresses by guesswork.
COM DB1 is Siemens software for editing the CPU’s DB1 parameters. Save the existing DB1 before considering a sample parameter block. Compare communication, restart and retentive-area settings with the machine’s established operation.
During PLC troubleshooting, record LED indications and information obtained through the PG first. OVERALL RESET erases RAM contents. Do not use it as a trial step without a verified program backup and recovery method. Include the installed memory card’s contents in the maintenance plan.
Editor’s note
When buying a used Siemens CPU 945, make sure the label clearly reads 7UA11. A general “CPU 945 available” description is insufficient. Establish whether the memory card and second-interface submodule are included.
Seeing the CPU online does not establish that every function works. Check PG connection, program loading, memory and the required serial interface separately. Record the supporting equipment used for the test as well.
Back up the existing machine CPU’s program and DB1 first. Check that the files open, and retain machine-specific comments and parameter files where available. Do not start the replacement relying solely on the Flash card fitted to the board.
Do not overlook the small module in the SI2 receptacle. Record its complete number and compare it with the replacement. Do not interchange TTY, PG and SINEC L1 hardware merely because the modules look similar.
If the program disappears after a power interruption, inspect the battery, battery connection and backup arrangement before condemning the CPU. Carry out power-interruption checks after verifying the program backup and preparing the recovery method.
For S5 maintenance, the record matters alongside the program. Keep the CPU number, version, memory card, SI2 submodule and completed tests on one form. Distinguish completed checks from functions that have not been tested.
OtomasyonAVM resources and PDFs
+ Siemens S5 PDF archive: system and module documentation. The CPU 945 manufacturer manual is linked below.
+ 6ES5 945-7UA11 model page and second-hand Siemens S5 models: the CPU and related system parts.
Related topics
+ 6ES5 945-7UA13 · 6ES5 945-7UA21 · 6ES5 945-7UA23: different order numbers in the same family.
+ S5 memory products · S5 interface modules · PLC debugging: memory, connections and maintenance.
Browse SIMATIC S5
Product page · Siemens S5 · SIMATIC S5 · Used Siemens equipment
Siemens and external references
+ Siemens S5-115U CPU 945-7UA1./-7UA2. Manual — 6ES5 998-3UF21, Edition 06: memory, interfaces, DB1, diagnostics and technical information.
+ Siemens COM DB1 Parameterization Software Manual: page 1-4 identifies 7UA11 as 256 KB and 7UA21 as 384 KB.
+ Siemens ST 50 — 1998 catalogue; manufacturer document hosted by Acomee: pages 3/24–3/26 cover the CPU 945 family and accessories. The ordering table lists the later 7UA13/7UA23 versions.