6ES5 095-8MB02

Siemens 6ES5 095-8MB02 SIMATIC S5-95U SINEC L2 Compact PLC

The Siemens 6ES5 095-8MB02 is a 24 V DC S5-95U compact PLC in the SIMATIC S5 family with a built-in SINEC L2 (PROFIBUS) port. It has 16 KB of user memory, 16 digital inputs, 16 digital outputs, 8 analog inputs, 1 analog output, 4 interrupt inputs and 2 counter inputs. The PG/OP serial port and the SINEC L2 network port use separate connectors.

The CPU reads machine sensors and drives local outputs while exchanging data with other controllers on SINEC L2. The S5-95U 8MA03 is the base model, the 8MC01 adds a second AS511 serial port, and the 8ME01 is a separate PROFIBUS-DP master version. The 8MB02 uses DB1 to set its role as an active or passive station on SINEC L2.

How is the SINEC L2 network connected and configured?

The bus plugs into a 9-pin female D-sub port. Siemens lists six baud rates from 9.6 kbaud to 1.5 Mbaud. When selecting S5 cables and connectors, check the shielded bus cable, permitted segment length and termination at both ends for the chosen baud rate. The 734-2 PG cable connects to the programming port.

The SL2 parameter block in DB1 defines the local station address, active or passive role, baud rate and bus timing. The L2-SEND and L2-RECEIVE blocks can handle PLC-to-PLC transfers. In the hardware list, distinguish the built-in L2 port from any separate S5 communications modules installed in the system.

What signals does the onboard I/O handle?

The 24 V DC digital inputs use addresses I 32.0–I 33.7. The outputs use Q 32.0–Q 33.7. Siemens lists the 490-8MA12 crimp connector and 490-8MB11 screw-terminal connector for the 40-pin front connection. In expanded systems, check onboard addresses separately from the addresses of external digital input and digital output modules.

The eight 0–10 V analog inputs are read at IW 40–IW 54. The single analog output at QW 40 provides 0–10 V or 0–20 mA, depending on the wiring. The range of an external analog module depends on its own order number.

The four interrupt inputs use I 34.0–I 34.3. Siemens specifies an upper limit of 5 kHz for counter A (IW 36) and 2 kHz for counter B (IW 38). The user program and communications load can affect the usable counting rate in service.

Power supply, expansion and program memory

Use S5-100U expansion modules to add local I/O. Siemens specifies expansion for up to 32 modules on the S5-95U. Check the bus units and total current budget together. Siemens lists the PS 931 6ES5 931-8MD11 among the accessories. Size the 24 V DC supply for the connected loads.

An EPROM or EEPROM submodule can store the control program. Check the backup battery for the program and data held in RAM and record the full order number of any fitted memory submodule. Include the live DB1 and machine data blocks in the STEP 5 project backup.

Editor’s note

Read the full CPU label. The 8MB01, 8MB02 and 8MB03 are in the same port family. Compare the order number, hardware revision and existing project settings when selecting a spare.

Save DB1 before removal. Read the SL2 settings, station address and baud rate from the CPU. Keep a record of the running project and any fitted memory submodule.

Check SL2 when the BF light is on. Siemens states that starting with the default DB1 leaves the L2 processor inactive and lights BF. Then check for a duplicate address, a baud rate mismatch and incorrect termination.

Label the front connectors. Photograph the digital I/O, analog I/O, interrupt/counter and network connections. Record whether the machine uses the analog output for current or voltage.

Test the replacement in two stages. Verify RUN and local I/O first, then confirm that data actually passes over SINEC L2. Record the CPU order number and the network settings used for the test.

OtomasyonAVM resources and PDFs

S5-90U to S5-115U CPU pages · Siemens S5 hardware and STEP 5 guide

OtomasyonAVM SIMATIC S5 PDF archive

Related topics

S5-95U 6ES5 095-8MB01 SINEC L2 · S5-95U 6ES5 095-8MB03 · S5-95U 6ES5 095-8MC01 AS511 · S5-95U 6ES5 095-8ME01 DP master

S5 navigation

Siemens S5 PLC · SIMATIC S5 · S5 CPU models · S5 90/110 modules

External references

Siemens S5-95U SINEC L2 interface manual, 6ES5 998-8MB22 (English PDF)

Siemens S5-95U SINEC L2 start-up diagnostics and BF LED, section 3.3.3 (English PDF)

Siemens SIMATIC S5-90U/S5-95U system manual, CPU connections (English PDF)