6ES5 470-7LA12
Siemens 6ES5 470-7LA12 SIMATIC S5 Eight-Channel ±10 V and 0–20 mA Analog Output Module
The Siemens 6ES5 470-7LA12 is an eight-channel AO 470 analog output module for SIMATIC S5-115U/H/F. Each channel has a ±10 V voltage terminal and a 0–20 mA current terminal. The module uses a 24 V DC field supply and has a 1 ms conversion time. The outputs are galvanically isolated from the system and share a common MANA reference.
The module converts a PLC command into an analog signal for a drive, valve positioner or indicator. Use QV for a voltage command or QI for a current command. A zero command gives 0 V or 0 mA. If the receiving device expects 4–20 mA, check the range table for the 470-7LC series.
What supply voltage and load does the module require?
Siemens specifies 20–30 V DC for the field supply, including ripple. Voltage outputs require a load resistance of at least 3.3 kΩ. Current outputs allow a total load of up to 300 Ω. Include the receiver input, wiring and series components in the current loop load. When troubleshooting, the open-circuit voltage at a current output can be around 18 V. Measure current with the load connected.
How are the front connector and jumpers wired?
The module uses a 46-contact front connector. Siemens lists the 490-7LB21 screw-terminal and 490-7LA11 crimp-contact connectors for the 470 family. In the pin table for this order number, 1 = L+, 47 = L− and 13 and 37 = MANA. For example, channel 0 uses 3 = QV0, 4 = S+0, 5 = S−0 and 6 = QI0.
Connect a current load between QI and MANA. For voltage wiring, S+ and S− sense the voltage at the load. Fit QV–S+ and S−–MANA jumpers at unused voltage outputs, including channels wired for current only. Leave unused current outputs open.
How do you check the STEP 5 value and address?
In the STEP 5 program, each channel value occupies one two-byte output word. Siemens’ table maps 512 units to +5 V or 10 mA and 1024 units to +10 V or 20 mA. On the voltage output, −1024 units gives −10 V. On the 7LA12 current output, a negative command gives 0 mA. Check the channel address and word format against the module layout in the S5-115U project.
In a CPU 944 or CPU 945 system with feedback through a 460-7LA12 or 460-7LA13, record the input and output addresses separately. On a CPU 942H system, use the system diagram for any redundant output wiring. On a CPU 942F system, Siemens classifies this module as a nonsafety-related Type 18 analog output.
What differs across the related 470 models?
The 470-7LA11 and 470-7LA13 have the same nominal ranges in different versions. The 470-7LB11, 470-7LB12 and 470-7LB13 have ±10 V voltage outputs. The 470-7LC12 and 470-7LC13 use 1–5 V and 4–20 mA ranges. The 470-8MA11 and 470-8MB11 are two-channel output modules for the S5-100U family.
Editor’s note
Record the label and slot. Before removal, photograph the 7LA12 suffix, rack slot and channel addresses.
Identify the output terminal. Check whether the channel uses QV or QI. Confirm the receiver’s input range from its label or settings.
Account for the jumpers. Record the QV–S+ and S−–MANA jumper positions for each unused voltage output.
Measure the load. If output current is low, check the total resistance of the series components and the module’s 24 V field supply.
Compare the scaling. Before placing the field output in service, measure zero, midscale and full-scale commands with a suitable test load.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 analog input and output modules · SIMATIC S5 CPU and system pages
+ OtomasyonAVM SIMATIC S5-115 PDF archive
+ SIMATIC S5-115H system manual, Figure 7-13, analog output wiring
Related topics
+ 6ES5 470-7LA13 ±10 V and 0–20 mA · 6ES5 470-7LB12 ±10 V · 6ES5 470-7LC12 1–5 V and 4–20 mA
If you have a 6ES5 470-7LA12 to sell, send the label photo, quantity and channel test status to otomasyonavm@gmail.com.
Browse the S5 range
SIMATIC S5 analog modules · Siemens SIMATIC S5
Siemens and external references
+ Siemens S5-115U manual, 6ES5 470-7LA12 pinout and specifications, pp. 15-52–15-53
+ Siemens S5-115U manual, wiring jumpers and output scaling table, pp. 10-57–10-59
+ Siemens S5-115F manual, Type 18 analog output use, §10.12.1
+ Siemens S5-115F/H declaration of conformity, 470-7LA12 module listing