6ES5 470-7LC11

Siemens 6ES5 470-7LC11 | SIMATIC S5 470 Analog Output Module, 8 Channels, 1–5 V and 4–20 mA

The Siemens 6ES5 470-7LC11 is an eight-channel analog output module for SIMATIC S5-115U and S5-115H systems. It converts PLC command values into field signals. Each channel has separate terminals for 1–5 V voltage and 4–20 mA current. The output circuitry is galvanically isolated, with a common MANA reference for all eight channels. The nominal field supply is 24 V DC and the module conversion time is 1 ms.

Typical applications include sending a 4–20 mA current command to a valve positioner or a 1–5 V voltage command to an analog signal controller. A channel’s QV and QI terminals follow the same command value in the PLC. The receiving device’s input type determines which output terminal to use.

Output ranges and load resistance

For voltage output, the receiving device must have an input resistance of at least 3.3 kΩ. For current output, the combined load of the receiving device, wiring and any series components must stay within 300 Ω. Siemens specifies an operating error limit of ±0.6% over 0–55 °C and a module weight of approximately 0.4 kg.

The Siemens S5-115H manual identifies the 6ES5 470-7LC12 as a compatible version. The 6ES5 470-7LC13 has the same nominal output ranges. The 6ES5 470-7LA11 provides ±10 V and 0–20 mA, while the 6ES5 470-7LB11 provides ±10 V. Check the full order number, rack and front connector diagram when selecting a replacement.

Front connector and field wiring

Field wiring lands on a 46-contact S5 front connector. Siemens lists the 6ES5 490-7LB21 screw-terminal connector, the 6ES5 490-7LA11 connector supplied with crimp contacts and the 6ES5 490-7LA21 connector supplied without crimp contacts.

Connect the field supply to contact 1 (L+) and contact 47 (L−). The permissible supply range is 20–30 V DC, including ripple. The MANA contacts are 13 and 37. Channel 0, for example, uses 3 (QV), 4 (S+), 5 (S−) and 6 (QI).

For voltage output, connect the load between QV and MANA and run the S+ and S− sense wires to the load terminals. For current output, connect the load between QI and MANA. When a channel’s voltage output is unused, jumper QV to S+ and S− to MANA at the front connector. Leave unused QI terminals open.

STEP 5 scaling and addressing

Each channel uses one 16-bit output word. The output value is encoded as 11 bits plus sign. Within the nominal range, 0, 512 and 1024 scaling units give 1, 3 and 5 V or 4, 12 and 20 mA, respectively. With the lowest four bits set to zero, the corresponding words are 0000h, 2000h and 4000h.

In an S5-115U panel with a CPU 943, CPU 944 or CPU 945, match the module start address to the documented rack layout, for example in a CR 700-3 central rack. In the STEP 5 program, trace the FB 251 call or T PW instruction that writes the output value.

Editor’s note

Record the channel wiring. Photograph the front connector before removing the module. Mark which channels use QV or QI and record the S+/S− jumpers.

Check both supplies separately. If all channels are affected, check the PS 951 rack supply and verify the separate 24 V DC field supply across contacts 1 and 47.

Measure full scale with the load connected. During a controlled test, if the current is correct near 4 mA but falls short of 20 mA, compare the total loop resistance with the 300 Ω limit.

Trace the command and feedback separately. If position feedback goes through a 6ES5 460-7LA13 to a separate analog input, measure the 470 output first and then check the feedback channel.

Check the S5-115H redundancy circuit. Siemens specifies additional hardware circuitry for redundant operation of the 470 analog output module. Before replacement, compare the field wiring of both subunits with the existing panel diagram.

OtomasyonAVM resources and PDFs

Siemens SIMATIC S5 systems and module overview

OtomasyonAVM S5-115 manuals and PDF archive

SIMATIC S5-115H system manual — 6ES5 470-7LC11 pin assignment and specifications

Related topics

The 6ES5 470-7LC12 and 6ES5 470-7LC13 are 470-7LC versions with the same signal ranges. The 6ES5 470-7LA13 is a 470-7LA version with ±10 V and 0–20 mA outputs.

Category navigation

SIMATIC S5-115U CPU and system family · SIMATIC S5 analog modules

Siemens external references

Siemens SIMATIC S5-115U system manual — 470-7LC series load wiring

Siemens SIMATIC S5-115H system manual — analog output redundancy requirements