6ES5 523-3UA11

Siemens 6ES5 523-3UA11 CP 523 Serial I/O Communications Processor

The Siemens 6ES5 523-3UA11 is a CP 523 serial I/O module for SIMATIC S5 controllers including the S5-115U, S5-135U, S5-150U and S5-155U. Its single 25-pin D-sub supports either RS-232-C (V.24) or 20 mA TTY. The module supports 110–9,600 baud, 10- or 11-bit character frames, and 3964 / 3964R. Check the rack documentation for H and F configurations.

The S5 communications module provides a point-to-point link between the PLC CPU and a serial device. In print mode, it can send machine events and fault messages to a serial printer. The 6ES5 521-8MA21 CP 521 SI is a separate serial module listed for the S5-90U, S5-95U, S5-100U and ET 200U.

Serial port and cable selection

V.24 and TTY use different pins on the same connector. Check the partner device’s interface and pinout before selecting an S5 cable. Siemens gives cable lengths of 15 m for V.24, 10 m for active TTY and 1,000 m for passive TTY. Use the wiring diagram to determine which device supplies current to the TTY loop.

The S5-115U manual shows a TTY link between the CP 523 and a dual-interface CPU 944. Siemens documents a separate RS-422/RS-485 interface arrangement for the 6ES5 524-3UA15 CP 524.

Communications mode and 375 memory

In transparent mode, message length or the inter-character delay determines the end of a frame. Interpretive mode processes end-of-text and control characters. For 3964 / 3964R, match the baud rate, character format and protocol at both ends.

Communications parameters can come from DB 1 on the 375 memory submodule or from the CPU program. Serial print mode requires a memory submodule containing the message texts. Siemens lists several suitable S5 memory modules, including the 375-0LA15 8 KB EPROM, 375-0LA21 16 KB EPROM and 375-0LC31 8 KB EEPROM.

Rack mounting and STEP 5 addressing

The CP draws typically 130 mA from the 5 V rail. In an S5-115U, check the slot diagram for the installed S5 rack, such as the CR 700-0LB11 or CR 700-2LB11. The CP 523 manual specifies the 6ES5 491-0LB11 adapter casing for the S5-115U and S5-115F. For F racks such as the CR 700-2F, check slot and wiring requirements against the system manual.

The CP 523 occupies eight bytes of I/O space. The S1 DIP switches set the start address. The factory setting is 128 in the P area. The S5-115U uses the P area. When replacing the module, compare its S1 settings with the start address in the STEP 5 program.

Editor’s note

Read the full order number on the label. For the 6ES5 523-3UA11, record CP 523 and the serial interface in use in the service notes.

Record the settings before removal. Photograph the S1 switches, the 375 module label and the serial plug. Switch off rack power before removing the CP or its memory submodule.

Start with the SEN and RCV indicators. If the CP transmits but receives no reply, check the partner settings, the pinout and which device supplies the TTY loop current.

Check power and addressing separately. If the board shows no activity, check the rack power supply. If the CP runs but the CPU cannot access it, check for an address conflict. The Siemens S5 system page provides rack documentation links.

Test the spare in the mode it will run. When buying a used Siemens board, ask for a serial data exchange or printer test. To offer a board for sale, send the order number, quantity, condition, label photo and asking price to otomasyonavm@gmail.com.

OtomasyonAVM resources and PDFs

SIMATIC S5 communications modules and Siemens S5 system information

OtomasyonAVM SIMATIC S5-115 PDF archive

SIMATIC S5-115H system manual, outputting operating system error messages via the CP 523

Related topics

6ES5 524-3UA15 CP 524 serial communications processor

6ES5 525-3UA21 CP 525 communications processor

6ES5 375-0LC31 8 KB EEPROM submodule

Browse the S5 range

Siemens SIMATIC S5 PLCs › S5 communications modules · S5-115U range

External references

Siemens CP 523 serial I/O manual, technical specifications · 25-pin connector pinout · 3964 and 3964R · Mounting and S1 address settings

Siemens S5 migration guide, 6ES5 523-3UA11 compatibility table

Siemens ST 50 catalog, CP 523 order number, operating modes and memory modules (DE)