6ES5 243-1AB11
Siemens 6ES5 243-1AB11 – IP 243 High-Speed Analog Input Module
6ES5 243-1AB11 is the input-focused, partially equipped IP 243 module in the Siemens SIMATIC S5 family. It provides 8 analog voltage inputs, a 12-bit A/D converter and four analog signal conditioning circuits. Its analog input ranges are ±5 V, ±10 V and 0–10 V, with a maximum single-conversion time of 35 µs.
The module transfers measurement signals from suitable analog sensors to the PLC. The 1AB version has no D/A converters, digital inputs or outputs, comparators or interrupt hardware. Check the complete order number when assessing analog input and output functions.
Input range and channel selection
The voltage input range is selected using unipolar/bipolar jumpers on the board. For a 0–10 V sensor, the hardware range and software range setting must agree. Check the 0–10 V or 4–20 mA interface carefully: this module's specified input ranges are voltage ranges.
An eight-channel multiplexer feeds a shared analog-to-digital converter. 35 µs applies to one selected channel conversion. Updating all eight channels also depends on the channel selection and reading sequence in the user program.
What do the four conditioning circuits do?
The module includes AV1–AV4 analog conditioning circuits. Front-panel adjustments change the operating point and gain. Their connection to ADC channels is established through the internal analog signal jumper block. Treat analog signal conditioning and ADC channel selection as separate parts of the signal path.
These four circuits do not add four independent digitized channels to the eight ADC channels. For a pressure transmitter or used analog sensor, trace the wiring to establish whether its signal reaches the converter directly or through a conditioning circuit.
Wiring, power and system compatibility
The analog signals are not galvanically isolated, so reference connections and shielding matter. The external supply is 24 V DC, with a permitted range of 20–30 V DC. When checking S5 cables and connectors, follow the wiring diagram for the analog reference and supply return.
The IP 243 manual covers S5-115U/H, S5-135U, S5-150U/S and S5-155U/H systems. S5-115U requires an adapter casing. Verify any connection adapter against the rack and slot arrangement, and supplement the S5 system information with the installed CPU's documentation.
Reading values and diagnosing faults
For direct access, write the channel selection to base address +7, start conversion by writing to base address +6, and read the result from the peripheral word beginning at that address. Check the module address and channel number together in the PLC program.
Siemens FB 160 – PER:ANL can return the analog value as a raw pattern or a normalized value. During troubleshooting, verify the range and normalization settings. Keep the analog and digital input functions distinct: the fully equipped module's digital functions are absent from AB11.
Related IP 243 versions and used-module checks
6ES5 243-1AA11 is the fully equipped version. 6ES5 243-1AC11 is the other partial version, without an A/D converter. When considering 6ES5 243-1AB12, assess the revision, jumper configuration and program requirements separately.
For a used analog module, request photographs of the label, both sides of the board and the jumper blocks. Within the S5 analog module range, a similar front panel does not guarantee identical internal routing or hardware functions.
Editor’s note
Start with the 1AB11 order number on the label. Establish which functions this partial version actually contains before testing. It saves time searching for an output that this card was never equipped to provide.
Before removing the old module, photograph the soldered links, plug-in jumpers and front-panel settings. An IP 243 may contain signal routing configured for the machine. Keep a clear record of that arrangement.
If a reading is offset, leave the front-panel trimmers alone initially. Measure the direct input and conditioned signal separately. Preserving the original adjustment makes the actual fault much easier to identify.
The yellow LEDs are not fault indicators; they show the selected ADC channel as a binary code. Check which channel the program requests, then trace the signal that actually reaches it.
In a bipolar range, do not assume 0 V must produce a zero raw word. The IP 243's raw coding and a normalized value are different representations. Confirm which one you are viewing before judging the card.
A green LED alone is not a complete used-module test. Have all eight channels and the four conditioning paths used by the application checked on a suitable test setup. Record the tested range and jumper configuration with the results.
OtomasyonAVM resources and PDFs
Start with About Siemens S5 PLC and the S5 analog module directory for system and module information.
The OtomasyonAVM Siemens S5 PDF archive collects our available S5 documents. For this model's hardware table, analog routing and FB 160 operation, use the English IP 243 manual linked below.
Related topics
+ 6ES5 243-1AA11: the fully equipped IP 243 version.
+ 6ES5 243-1AB12: revision comparison within the input-focused group.
+ 6ES5 243-1AC11: the partial version without an A/D converter.
+ Analog-to-analog conversion: the role of conditioning in the measurement chain.
Browse SIMATIC S5
S5 analog modules · SIMATIC S5 systems · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens IP 243 Analog Module with FB 160/FB 161 – Equipment Manual, 6ES5 998-0KF21, English: revision 02/1992; pp. 2-2 and 2-4 for hardware variants, pp. 3-3–3-6 for analog input and raw coding, pp. 3-11–3-13 for conditioning, pp. 6-2 and 6-5 for specifications, and §7.2 for FB 160.