6ES5 951-7ND21

The Siemens 6ES5 951-7ND21 is a PS 951F power supply for the SIMATIC S5-115F. It takes a 24 V DC input and supplies the internal rack rail with 5 V DC at up to 7 A. This order number is listed without a backup battery. The input and output are non-isolated, so Siemens requires external monitoring of the 5 V output.

In a SIMATIC S5 115F system, the module powers the CPU 942F, the I/O bus and the module control circuits in the CR 700-2F central rack. When tracing a fault, follow the internal 5 V rail and the sensor and actuator field circuits separately.

5 V monitoring and overvoltage shutdown

For the 7ND21, Siemens requires external monitoring of the secondary 5 V DC rail. If an overvoltage is detected, the protection circuit must disconnect the module’s 24 V DC input automatically. That monitoring and shutdown arrangement is a requirement for using this order number in the S5-115F.

When power drops out, use the cabinet drawings to trace the 24 V DC supply and the feed to the PS 951F. The event sequence can help distinguish a drop in the incoming voltage from a shutdown initiated by the external monitor.

The 7 A limit and rack load

7 A is the limit for the internal 5 V output. Siemens specifies fanless operation for the S5-115F and limits the total current drawn by the modules on this supply to 7 A. When adding a card to an S5 rack, include the existing modules in the 5 V load calculation.

If only a few digital inputs, digital outputs or analog channels are affected, trace the field supply they share. If the fault is confined to one expansion unit, include that unit’s supply, interface module and inter-rack cable in the investigation.

Comparing the 7ND21, 7ND31 and 7ND41

Siemens lists the 6ES5 951-7ND31 and 6ES5 951-7ND41 with galvanic isolation and a 7 A maximum in the S5-115F. In the same table, the 7ND21 is listed with the external voltage-monitoring requirement. Check the installed protection circuit as well as the rack when selecting a spare.

The 6ES5 951-7ND12 is a separate order number catalogued for the S5-115U/H. For a 115F installation, match the full order number against the power supply table in the 115F manual.

Editor’s note

Record all three nameplates. Put the supply, rack and CPU order numbers on the work order. That makes it easier to pick the correct unit from a shelf of similar-looking PS 951 modules.

Locate the external monitor on the drawings. Mark the circuit that monitors the 5 V rail and the circuit that disconnects the 24 V input. On older cabinets, check the drawings against the equipment actually installed.

Capture the first event. Establish whether the CPU stopped, the incoming 24 V disappeared or the voltage monitor tripped first. The sequence points to the part of the circuit worth checking first.

Update the load calculation after adding a card. Add the new module’s 5 V current draw to the existing total. Keep the calculation with the rack records so later changes can be traced.

Keep bench and site tests separate. When buying a used PLC power supply, ask what load was applied when the 5 V output was checked. Verify the cabinet’s monitoring and automatic shutdown functions under the site’s safety test procedure during commissioning.

OtomasyonAVM references and PDF archive

Browse our Siemens S5 PLC section for series and model pages. The OtomasyonAVM S5 PDF page hosts the S5-115H and S5-100U manuals. The S5-115F manual containing the 7ND21 table is linked under External references below.

Related topics

The S5 CPU 90U–115U index covers processors and central units from the same generation. For the power supply position in a 115F installation, see the CR 700-2F rack page.

Site navigation

Siemens Automation › Siemens S5 PLC › S5 power supplies

External references

Siemens SIMATIC S5-115F system manual, Volume 1 (PDF, English) · Section 3.4.1, Table 3-3, printed page 3-32. See this section for listed power supplies and the external monitoring requirement for the 7ND21.