Siemens 6ES5 930-7AA31 SIMATIC S5-110A Power Supply
The Siemens 6ES5 930-7AA31 is a 930-series power supply for the internal 5 V rail of a SIMATIC S5-110A rack. It takes a nominal 24 V DC input and supplies 5.2 V DC at 0.7 A. Siemens specifies a −15% / +25% input tolerance, equivalent to 20.4–30 V DC.
The module powers the internal SIMATIC S5 circuits. The 6ES5 900-7AD11 CPU and its fitted 910 EPROM memory submodule use this internal rail. For fault finding, trace the 7AA31’s 24 V input, the rack’s 5 V rail and the field supply separately on the machine drawing.
Input current, fuse and front-panel indication
The Siemens technical table specifies a 400 mA rated input current and a T 0.5 A time-delay primary fuse. At rated load the manual permits voltage dips shorter than 2 ms. The front-panel power LED indicates that the internal 5 V rail is available.
The spare parts list in the same manual prints 24 V AC against the 7AA31. Both the technical table and the serial-interface section specify 24 V DC. Use the exact model’s technical table and the unit label to verify the supply.
Rack and interface arrangements
Siemens lists legacy S5 racks such as the 6ES5 710-0AA11 and 6ES5 710-0AA41 under separate order numbers. Record the rack code and the supply’s mounting position before replacement. In a 311 serial-interface configuration, the manual specifies two 930-7AA31 units when the supply is 24 V DC.
The programming-device interface belongs to the 500 family. Siemens shows the 6ES5 500-7AA12 in Figure 32, its recommended online arrangement for the 7AA31. If a 6ES5 500-7AA11 is fitted, check the interface code and wiring diagram separately. For interference suppression, Siemens specifies hardware version C or later for the 7AA31.
Field supplies and related 930 models
Field signals for digital input modules such as the 400-7AA13 and 401-7AA13 use a separate circuit from the rack supply. On digital output modules, if the control LED lights but the load stays off, check the output’s field supply and its fuse.
The 930-7AA12 and 930-7AA11 take 220 V AC, while the 930-7AA21 takes 115 V AC. The 930-8MD11 and 931-8MD11 provide 24 V output for other S5 systems. The 932-3SA11 is a powered enclosure for the S5-110S.
Editor’s note
Record the order number and hardware version. When choosing a spare, check the 7AA31 suffix and version marking separately.
Check the 24 V input when the fault occurs. A steady-state measurement alone may miss a brief supply dip.
Start with the power circuit if the 5 V LED is off. After safe isolation, check the S5 cables and connectors and the primary fuse against the machine drawing.
Consider the other causes of a CPU STOP indication. The manual lists low 5 V supply as one possible cause. If a 330 test module is installed, record the test configuration as well.
Verify the program backup before removal. Record the EPROM order number and the condition of the 900 CPU battery used for retentive flags separately.
OtomasyonAVM resources and PDFs
About Siemens S5 PLCs · S5 90/110 modules · Siemens S5 PDF archive. The exact 7AA31 specification is in the S5-110A manual linked at the bottom of this page.
Related topics
930-7AA12 power supply · S5-110A 900 CPU · S5-110A 330 test module
S5 navigation
Siemens S5 PLCs · S5 90/110 modules · S5 power supplies
Siemens and other external references
Siemens SIMATIC S5-110A operating instructions, page 1.12 (Exact 7AA31 specifications)
Siemens S5-110A connections and interference suppression (Figure 32 and hardware version C requirement)
CoSysS 6ES5930-7AA31 product record (Exact order number and DC input)