6ES5 382-0AA32

Siemens 6ES5 382-0AA32 · Type I adapter for the 381 timer/counter

The 6ES5 382-0AA32 is the Type I adapter set for the 6ES5 381-7AA11 timer/counter module in the SIMATIC S5 S5-110A. It belongs to the special modules in the S5 90/110 range. Each channel uses one adapter and one three-digit thumbwheel. Siemens lists the 0AA32 with an LED thumbwheel. The Type II set with the seven-segment display is 6ES5 382-0AB32.

Time ranges and down-counting

The time setting is the thumbwheel number multiplied by the selected time base. For example, 125 gives 1.25 s on the 0.01 s setting, 12.5 s on the 0.1 s setting and 125 s on the 1 s setting. The range limits are 9.99 s, 99.9 s and 999 s respectively. The Type I LED stays on until the time or count is complete. When tracing timer and relay functions, check the LED and the machine output separately.

In down-counting mode, the channel counts from the preset to zero. The highest preset is 999. The K1 terminal receives external 24 V DC counting pulses. In timer mode, the adapter’s quartz oscillator supplies the time base. Siemens specifies a 100 Hz maximum for the 381 hardware counter with RE = 2.4 kΩ. Use the 381’s own limit when comparing it with high-speed counters.

715 cable and panel connections

The Bu 2 socket connects to the appropriate 381 front channel through a 715 cable. Siemens specifies a maximum length of 10 m. The adapter clips onto a 35 mm rail. The panel-mounted thumbwheel connects to it through a ribbon cable of about 200 mm. Check the 24 V DC supply of the rack-mounted 381 separately from the pulse at K1. Keep the 715 link out of cables carrying digital inputs or digital outputs.

Complete set and spare parts

In the Siemens S5-110A parts list, 382-0AA32 is the complete Type I set, 773-7AC11 is the Type I adapter alone and 773-0AE21 is the LED thumbwheel. When reviewing the S5 system, match the 381 channel to the adapter label first. Record any S5-110A test module as a separate part.

The 380-8MA11 and 390-5AA22 are separate timing products. The 385A, 385B, IP 242 and IP 240 have their own counting connections and order numbers. Identify this set by its connection to the 381-7AA11 through a 715 cable.

Editor’s note

+ Ask for photos showing the 0AA32 label, three-digit LED thumbwheel, short ribbon cable and rail clip. Confirm separately whether the long 715 cable is included.

+ Before removal, record the 381 channel, thumbwheel value and range selector position. If the elapsed time is off by a factor of ten, check the 0.01 s, 0.1 s and 1 s selector first.

+ After safely isolating the equipment, inspect the Bu 2 socket and the 715 plug. Check the short ribbon cable for a sharp fold or loose contact before replacing the adapter.

+ If the channel runs in timer mode but fails to count, check the selector and the 24 V pulses at K1 against the machine drawing. These checks separate the adapter setting from the field signal.

+ If the timing is correct but the LED stays dark, inspect the LED thumbwheel and short ribbon cable. Observe the 381 channel’s completion state to distinguish an indicator fault from a channel fault.

+ After replacement, follow the site test procedure and try 003 on the 1 s range. In counter mode, use three controlled pulses and check for completion and the LED going out.

For a used set, ask whether timing and counting have both been tested. To sell a set, email the full order number, quantity, operating condition, photos and asking price to otomasyonavm@gmail.com.

PDFs and Siemens references

+ S5-110A manual, 381/382 operation, p. 1.8 (EN)

+ S5-110A manual, exact order number and specifications, p. 1.14 (EN)

+ S5-110A manual, K1 and Bu 2, Fig. 35, p. 3.2 (EN)

+ S5-110A manual, complete set and spare part numbers, p. 6.1 (EN)

+ Siemens S5 PDF archive

Related topics

+ About Siemens S5 PLCs

+ Down-counting function

+ Siemens 380-8MA11 timer module

Second-hand Siemens

+ S5 special modules

+ S5 90/110 modules

+ Siemens S5

+ Second-hand Siemens main page