6ES5 255-3AC11
Siemens 6ES5 255-3AC11 SIMATIC S5 IP 255 MONA-C display module
The 6ES5 255-3AC11 is the IP 255 MONA-C display board for Siemens SIMATIC S5. It provides the video path for process screens and status information on the existing operator display. The full order number in the S5 special module family ends in 3AC11.
Monitor connection and video timing
When replacing the monitor, record its model, video input, connector type and the cable markings at both ends. The IHSE converter manual lists a MONA-C profile of 560 × 413, with 25.8 kHz horizontal and 58.2 Hz vertical timing. Use these figures as a starting point for converter selection. Confirm the signal and sync type against the installed monitor documentation or have a qualified technician measure them.
Rack, CPU and process data
A spare-parts record for the exact order number lists the 3AC11 for S5-135U and S5-155U systems. When selecting a spare, record the rack label and existing slot number. If the system uses a CPU 928A or CPU 948, record its full order number too. Trace the rack power supply and the external display supply separately on the cabinet drawing.
For a cabinet with an expansion rack, record where the board is installed and which interface modules are fitted. If the screen comes up but one value stops updating, trace the source in the PLC program. It could be a digital input, a digital output or an analog measurement. Compare the displayed value with the live PLC value in STEP 5.
Display hardware identification
The parts list records 6ES5 255-3AA11, 6ES5 255-3AC11 and 6ES5 255-3AC12 under separate order numbers. In a cabinet with several visualization components, record the AS 256, OP 393-II and CP 526 labels against their respective circuits. Match the S5 communications module codes to the cabinet drawing as well.
1. Document the working setup before removal. Photograph the 3AC11 label, E-Stand revision, rack slot and both ends of the display cable. Back up the STEP 5 project and any available visualization files and settings.
2. If the screen is black, test the monitor and cable separately. Check the monitor supply and selected video input. Have a qualified technician swap one component at a time using a known-good monitor and cable for the same video signal.
3. If the picture rolls, check sync. When changing from CRT to LCD, check the converter's MONA-C profile and sync setting. If the color or geometry is wrong, compare the settings with a working installation.
4. If the picture is present but values are frozen, check the PLC data. Check in STEP 5 whether the process value changes. Then verify the address or tag mapping on the screen and have the data path to the board's rack checked.
5. When buying used, ask for a start-up and live-value test. Request photos of the full 3AC11 label, E-Stand and connector. Ask for a test record identifying the monitor or converter and showing a stable picture and at least one changing process value.
To offer a 3AC11 for sale, send the full order number, E-Stand, quantity, condition, label photo and asking price. Contact otomasyonavm@gmail.com.
PDFs and technical references
+ Exact 6ES5 255-3AC11 listing, ADEGIS parts list, p. 5 (PL/EN)
+ IHSE converter manual, MONA-C video profile, p. 44 (EN)
+ Siemens S5-135U/155U system manual, rack reference (EN)
Related topics
+ SIMATIC S5 communications modules