6ES5 247-5AA11
Siemens 6ES5 247-5AA11 SIMATIC S5 COM 247 configuration package
+ OtomasyonAVM SIMATIC S5 PDF archive
The 6ES5 247-5AA11 is the German-language configuration package for the SIMATIC S5 IP 247 positioning module. Siemens ST 50 lists COM 247 software, standard function blocks and the manual as package contents. The software prepares, backs up and tests machine data and traverse programs for stepper positioning cards such as the IP 247 4UA31.
Package versions and STEP 5 blocks
5AA11 is German, 5AA21 English and 5AA31 French. The 5AA11 product record lists diskette media, printed documentation and a single-installation licence. The IP 246 family uses COM 246. Identify the S5 function module and CPU by their labels before matching blocks in the STEP 5 project. FB 164 operates and monitors the axis. FB 165 handles data operations such as transferring machine data and traverse programs.
The Siemens manual documents 4UA31 and 4UA41 modules and CPU-specific FB selection for the S5-115U, S5-135U, S5-150U and S5-155U. ST 50 lists MS-DOS for COM 247. The older A02.0 manual describes a S5-DOS and PCP/M-86 environment. Match the diskette release to the programmer environment before installation.
Programmer connection and backup
On the 4UA31 and 4UA41 covered by the manual, the programmer connects to X8. For the 4UA31 with a PG 720/740, Siemens APPnote 249 specifies the 6ES5 734-2BF00 cable. It lists the 6ES5 731-1…0 cable family for older programmers. Choose the cable type by programmer model. If online access fails, check that the module is seated in the rack and verify the S5 power supply.
In the COM 247 Transfer screen, select IP 247 as the source and the FD drive as the destination for a backup. Transfer machine data and traverse programs separately to a .247 file. Before replacing the card, check that both types of data can be opened from the file.
Axis data and troubleshooting
Check axis scaling against the stepper motor’s step count and the mechanical transmission ratio. If the drive setup has changed, verify the step and direction signals and speed and travel scaling. If the position drifts during acceleration, check motor torque and mechanical load. The IP 247 calculates its displayed coordinate from the pulses it sends. Measure actual travel independently.
During online troubleshooting, use the schematic to identify whether the reference and limit switch signals reach the IP 247 or the PLC’s digital inputs. Monitor the drive enable control output separately. If a command is present and the axis does not move, check for drive and mechanical faults before editing the traverse program.
Editor’s note
1. For a used package, ask for photos of the 247-5AA11 label, diskette release, printed manual and licence. Ask the seller to demonstrate COM 247 starting up.
2. Write-protect the original diskette. Make a readable working copy and test installation from that copy. Keep the machine’s existing .247 files separately.
3. Before reading data from the old card, double-check the source and destination in the Transfer screen. Save machine data first and then traverse programs. Include the machine and axis in the archive filename.
4. If the programmer cannot see the module, verify X8 and the cable order number before reinstalling software. Starting the program and establishing an online connection are separate checks.
5. If the PLC can read axis status but data transfer fails, inspect the CPU-specific FB 165 and its addressing. Test transfer separately even if monitoring through FB 164 works.
6. Secure the movement area before restoring data. For the first test, move one axis over a short distance at low speed. Verify direction, reference position and actual travel before switching to automatic operation.
Related topics
Used Siemens equipment
To sell a 6ES5 247-5AA11, send the quantity, diskette condition, a photo of the package label and the asking price to otomasyonavm@gmail.com.
External sources
+ Siemens ST 50, COM 247 and order numbers (EN)
+ Siemens IP 247 manual, COM 247 chapter (DE)
+ Siemens IP 247 manual, Transfer screen (EN)