6ES5 247-4UA11
Siemens 6ES5 247-4UA11 SIMATIC S5 IP 247 stepper motor positioning module
The 6ES5 247-4UA11 is a forced-air-cooled IP 247 module for positioning stepper-driven axes in a SIMATIC S5 system. It converts PLC motion commands into pulse and direction signals for the external drive. The external drive supplies motor current.
Motion commands and fault diagnosis
Siemens’ IP 247 family manual describes open-loop positioning for three independent drives. The module calculates position from axis data and the pulses it has sent. If the motor misses steps, the displayed coordinate can differ from the actual travel. See how a stepper motor works, what the stepper drive does, pulse and direction signals, and how speed and position are controlled.
If the axis stays still, check the motion enable, reference sensor and limit switch status first. Use the machine drawings to identify which signals terminate on the card and which go to the PLC’s digital input and digital output modules. Check for drive alarms and mechanical binding as separate stepper system faults. If the motor loses steps under load, review available stepper torque alongside the acceleration settings.
Installation, software and hardware revisions
Table 15-1 of the Siemens S5-115U manual lists 0.8 A on the internal 5 V rail for the 4UA11. An adapter casing and a fan are required. For the CR 700-2LB rack, Figure 3-6 shows the 491-0LB11 adapter casing and excludes the 3 A power supply when an IP 247 is installed.
The CSA certificate hosted by Siemens lists the IP 247 family under S5-135U, S5-150U and S5-155U systems. Before fitting the module, identify the existing S5 rack, power supply, any expansion interface, and the axis cables and connectors. The S5 fan unit is an installation example. Identify the correct fan from the rack model and verify airflow at the card slot.
The family manual describes using COM 247 configuration software to create machine data and traversing programs. Check the function module address and the blocks used in the existing STEP 5 project. The manual describes FB164 for operation and monitoring, and FB165 for parameter assignment.
The IP 247 4UA21, IP 247 4UA31 and IP 247 4UA41 have separate order numbers. The IP 246 and IP 267 are separate positioning families. Siemens’ wiring and jumper tables cover 4UA31 and 4UA41. For the 4UA11 pinout and jumper settings, use the machine drawings and documentation for the installed card.
Editor’s note
1. When buying used, ask for photos of the 247-4UA11 label and the axis connectors. Ask which axes were tested with an external drive in a fan-cooled rack.
2. Before removing the card, back up the STEP 5 project and any COM 247 archive. Record axis scaling, reference settings and traversing programs.
3. Isolate cabinet and field supplies and verify that power is off. Document the card slot, connectors and jumper positions. Check airflow at the slot before restarting.
4. If a command is present and the motor stays still, check whether the drive is ready and enabled. Check pulse and direction only at the test points identified in the machine drawings.
5. If the displayed coordinate advances and the axis falls short, check for binding, a loose coupling or missed steps during acceleration. Measure the actual travel before adjusting settings.
6. After replacement, test each axis separately at low speed under controlled conditions. Check direction, reference return and limit response. Compare actual motion with the displayed position.
To offer a 6ES5 247-4UA11 for sale, send the quantity, working condition, label photo and asking price to otomasyonavm@gmail.com.
Manual and supporting documents
+ Siemens S5-115U manual, 4UA11 current, fan and adapter table (EN)
+ Siemens IP 247 manual, 4UA31 and 4UA41 family reference (EN)
+ Siemens IP 247 manual, 4UA31 and 4UA41 family reference (DE)
+ CSA certificate 1232105, 4UA11 forced-air cooling entry (EN)
+ 6ES5 247-4UA11 exact part record (EN)