6ES5 944-7UA11
Siemens 6ES5 944-7UA11 – S5-115U CPU 944, 96 KB RAM and one PG port
Siemens 6ES5 944-7UA11 is a CPU 944 central processing unit for SIMATIC S5-115U, with 96 KB of internal RAM and one programmer port. It belongs to the A series within the Siemens S5 PLC family. This CPU executes the user program, evaluates input states and sends output commands to separate I/O modules.
Typical duties include machine sequencing, interlocks and process control. Retain the complete 7UA11 suffix: memory arrangements, operating systems and interface counts differ across the 944 family and matter when selecting a spare.
96 KB RAM and two memory banks
The A-CPU manual divides CPU 944 RAM into BANK 1 and BANK 2, each holding 48 KB. BANK 1 holds data blocks and BANK 2 holds program blocks. Support for storing program blocks in BANK 1 is separately described for 7UA12/22 with suitable operating-system versions. Consequently, the 7UA11's total 96 KB RAM must not be interpreted as a single unrestricted instruction-program area.
Check this bank distinction when comparing it with 6ES5 944-7UA12. A STEP 5 programming backup should preserve program blocks, data blocks and the contents of any installed EPROM/EEPROM memory submodule.
Program storage and battery backup
During the appropriate restart procedure, CPU 944 copies blocks from the installed memory submodule into internal RAM. Retaining RAM contents during a power interruption requires battery backup. An installed memory submodule does not establish that it contains the latest program and data changes.
The operating-system module and user-program memory submodule serve different purposes. When assessing auxiliary modules, check the CPU's operating-system label, user memory and current project version separately.
One serial interface and communication
This model has one serial PG connection. In the A-CPU system, this connection supports PG/OP access and, with suitable configuration, SINEC L1 slave operation. Select an S5 programming cable suitable for the TTY current-loop interface; connector shape does not establish direct RS-232 or Ethernet compatibility.
Assess interface modules and communication processors against the installation's requirements. Do not automatically assign the two-interface CPU 944 variants' second interface, ASCII/3964R options or hardware clock associated with that interface's processor to the single-port 7UA11.
Timers, counters and I/O
The A-series CPU 944 provides 128 timers and 128 software counters. These counters are not physical high-speed counter inputs. Digital inputs, digital outputs and analog I/O use separate modules; field voltage, measurement range and output current depend on the selected board.
The manual's 500 ms scan-monitoring setting is not the actual program cycle time. Assess application response together with program length, the operations used, interrupts and communication load.
Rack, supply and version comparison
The CPU operates with a suitable S5-115U rack and PLC power supply. During maintenance, check rack power, battery condition, module locks and grounding connections together.
6ES5 944-7UA22 is a different, two-port version. 6ES5 944-7UB11 and 6ES5 944-7UB21 belong to the B series. 6ES5 943-7UA11 is another CPU with a different memory capacity. These order numbers must not be treated as automatically interchangeable. See About Siemens S5 PLC for family context.
Editor's note
Start by photographing the complete 7UA11 label and the operating-system module number. “CPU 944” alone is insufficient: distinguish A from B series and single-port from dual-port versions.
Do not assume that the 96 KB marking means the entire area can hold program blocks without restriction. Bank allocation matters on this early version; record the working program and data arrangement before changing it.
A weak battery can allow the latest RAM changes to disappear after power is removed. Obtain a current backup before checking the battery and memory, and verify separately that any installed EPROM is up to date.
If the PG cannot connect, check the TTY converter, correct S5 cable and software settings before condemning the CPU. This single-port device does not provide a second programmer socket or Ethernet connection.
During fault finding, record STOP and other fault indications, ISTACK and the circumstances of the stop together. Do not begin with an overall reset and lose the working program or diagnostic evidence.
When buying used Siemens equipment, request program reading through the PG port, data-block access and a memory-retention test after power cycling with suitable battery backup. Running an empty program does not demonstrate compatibility with the machine's existing application.
OtomasyonAVM resources and PDFs
Browse the 6ES5 944-7UA11 model page, S5 CPU family and used Siemens equipment. Check document titles and system coverage in the S5-115 PDF archive. The German manual used for this page's A-series memory explanation is linked separately under external references.
Related topics and models
+ 6ES5 944-7UA12: a later single-port A-series version; check memory-bank use separately.
+ 6ES5 944-7UA22: A-series CPU 944 with two serial interfaces.
+ 6ES5 944-7UB11: B-series CPU 944 with one interface.
+ 6ES5 944-7UB21: B-series CPU 944 with two interfaces.
Other S5 equipment
Siemens S5 PLC · CPUs · Memory · Cables · Interfaces · Racks · Used Siemens equipment
Manufacturer documents and external references
+ Siemens S5-115U A-CPU Gerätehandbuch – 6ES5 998-0UF12, 03/1989, German: sections 2.2.2 and 5.4 cover memory banks; PDF pages 37–38 cover RAM and copying, 49 compares A-series CPUs, and 53 describes CPU 944 construction. The detailed specification on PDF page 468 is for 7UA12 and must not be presented as a 7UA11-specific data sheet.
+ Siemens Migration from S5 to S7-1500 – English: lists 6ES5 944-7UA11 as CPU 944. The migration table does not establish a direct plug-in replacement.