6ES5 942-7UA12

Siemens 6ES5 942-7UA12 — S5-115U CPU 942, 10 Kbytes RAM

Siemens 6ES5 942-7UA12 is a CPU 942 central processing unit for SIMATIC S5-115U, with 10 Kbytes of internal RAM and a receptacle for a 375-series memory submodule. This CPU in the Siemens S5 family executes the machine program and manages the system’s I/O modules.

Sensor and control signals are handled through separate digital input and digital output modules. Spare selection should consider the complete 7UA12 order number, fitted memory and operating-system version, rather than the CPU 942 name alone.

10 Kbytes of internal RAM and 42 Kbytes total memory

The CPU 942’s 10 Kbyte internal RAM can be extended with a suitable memory submodule. The A-CPU manual specifies up to 32 Kbytes in an external submodule and 42 Kbytes total memory capacity. A receptacle accepting a 32 Kbyte submodule does not mean that the CPU has 32 Kbytes of internal RAM.

Siemens’ memory table lists the 6ES5 375-0LD11 — 8 Kbytes, 6ES5 375-0LD21 — 16 Kbytes and 6ES5 375-0LD31 — 32 Kbytes RAM submodules for CPU 942. A 32 Kbyte RAM submodule provides the 10 + 32 = 42 Kbyte arrangement. Check the installed submodule and actual program memory use separately.

Choosing RAM, EPROM or EEPROM

RAM expansion and non-volatile program storage serve different purposes. The manual lists 6ES5 375-0LC31 — 8 Kbytes and 6ES5 375-0LC41 — 16 Kbytes EEPROM options; these should not be treated in the same way as RAM expansion. Match the memory type, capacity and program layout together.

Retaining a program and data stored in RAM during a power failure depends on the system’s battery and backup arrangement. When taking a backup, record the fitted submodule’s type and contents as well as the CPU program.

TTY programmer connection

The programmer connection uses a TTY current loop. Select the correct interface and S5 cable for a PG, OP or suitable SINEC L1 connection. A connector that physically fits does not establish electrical compatibility.

Programming and maintenance use STEP 5. When selecting an S5-115U CPU, preserve the program backup, PG connection details and communications arrangement together. A replacement communicating with the PG has not yet passed a complete application test.

Why the operating-system version matters

Section 11.1.3 of Siemens’ A-CPU manual identifies a revision distinction for the exact 6ES5 942-7UA12 code. From hardware version A02 with operating-system level Z04, RECEIVE-ALL and SEND-ALL no longer occupy flag words MW 252 and MW 254. This matters when reviewing working areas reserved in older programs.

The manual states that firmware levels can be displayed using the PG’s SYSPAR function. During S5 maintenance, record software versions even when two CPUs share the same order number. The front label alone does not establish identical program behaviour.

Rack installation, supply and diagnostics

The CPU operates in a suitable S5-115U central rack. CR 700-3 / 6ES5 700-3LA12 is one central-rack option for the system. Power is provided through the PS 951 supply and system connections; check CPU connections against the system diagram.

During fault-finding, assess the power-supply battery warning, CPU indicators, fitted memory and program state together. Before carrying out an overall reset, have a working program backup and a defined reloading method available.

Differences from 7UA11 and 7UA13

6ES5 942-7UA11 and 6ES5 942-7UA13 are different order versions within the CPU 942 family. Compare hardware, operating system and memory arrangement before treating them as direct substitutes. In particular, do not automatically transfer another suffix’s current, weight or instruction-time figures to 7UA12.

Editor’s note

When buying used Siemens equipment, inspect the 7UA12 label and fitted 375 submodule together. A CPU supplied without its original memory submodule may not offer the capacity used in the machine.

Keep the internal 10 Kbytes distinct from the 42 Kbyte total. Use the PG to establish where the program resides and which memory submodule it requires. A RUN indication alone does not confirm sufficient memory.

Back up the program, data blocks and memory-submodule details before removing power. If a battery warning is present, do not assume that RAM-submodule data will be retained.

Check the replacement’s operating-system level with SYSPAR. In older applications using SEND-ALL/RECEIVE-ALL, review the MW 252 and MW 254 distinction.

Under suitable conditions, verify PG access, I/O behaviour and startup after a controlled power cycle. Record the memory submodule and software version alongside the CPU part number.

OtomasyonAVM resources and PDFs

Browse the 6ES5 942-7UA12 model page, SIMATIC S5 CPU family and used Siemens equipment. General documents are collected in the shared Siemens S5 PDF archive. The Siemens manual used for this A-CPU is linked below and is in German.

Related topics

+ 6ES5 942-7UA11 — another CPU 942 order version.

+ 6ES5 942-7UA13 — CPU 942 option requiring revision comparison.

+ 6ES5 375-0LD31 — 32 Kbyte RAM expansion submodule.

+ 6ES5 375-0LD21 — 16 Kbyte RAM submodule.

+ 6ES5 375-0LC31 — 8 Kbyte EEPROM submodule.

Browse SIMATIC S5

S5-115U CPU group · S5 racks · S5 memory submodules · S5 interfaces · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

Siemens S5-115U A-CPU Handbuch — GWA 4NEB 811 6000-01b, Ausgabe 03 — German, 1989. PDF p. 51: CPU 942 internal 10 Kbyte memory and 8–32 Kbyte external submodules. PDF p. 55 / printed 2-22: 375-series memory table. PDF p. 311 / printed 11-5: exact 942-7UA12 A02/Z04 note concerning MW 252/MW 254, and firmware display using SYSPAR.