6ES5 935-8ME11
Siemens 6ES5 935-8ME11 – PS 935 Auxiliary Supply for Ex Analog Modules
Siemens 6ES5 935-8ME11 is the PS 935 auxiliary power supply for increased internal power demand from Ex analog modules in SIMATIC S5 systems. This S5 supply module converts 24 V DC to 9 V DC at 2.5 A for the I/O bus. It serves installations using Ex analog modules in S5-95U, S5-100U and ET 100U/ET 200U systems.
The 9 V output supplies the internal I/O bus. Its role differs from PS 930 and PS 931 units that convert mains power to 24 V. Assess the field supply and signal terminals of 4–20 mA sensor circuits separately from the module’s internal supply.
Input, output and current ratings
The rated input is 24 V DC, with a static range of 20.4–28.8 V DC and a dynamic range of 18.5–30.2 V DC. Rated input current at 24 V is 1.25 A. Output voltage is 8.55–9.45 V DC, with a rated output current of 2.5 A. During analog signal measurement or 4–20 mA loop checks, distinguish the 9 V supply from the measurement signal.
System compatibility and load budget
It cannot be used with S5-100U CPU 100; the supported CPUs in that family are CPU 102/103. Check the installed S5 CPU number. Siemens specifies up to seven Ex analog modules, subject to the current budget. Ex modules require the correct base hardware, such as the 6ES5 700-8EA11 Ex bus unit. Include every connected module in the load calculation.
Installation and connections
In the S5 mounting arrangement, fit PS 935 immediately to the right of the CPU or ET interface; it occupies two slots. Inspect the ribbon cable and connectors. For stations with an interface module, follow the diagram for the installed unit, such as IM 318-C. The ET 200U manual shows an L+ connection; PS 935 has no separate M terminal.
Addressing and ET 200U operating mode
With fixed S5-95U/S5-100U addressing, PS 935 reserves input bytes 0 and 1; the first digital module on its right starts at byte 2, or byte 80 for an analog module/CP/IP. Record the PLC program addresses before replacement. Match the ET station’s COM configuration to its mode: ET 200U DP Siemens uses 008/008; DP Standard uses 016/016. Check the addresses of additional modules accordingly.
DC 9 V and FAULT indicators
The green DC 9 V indicator shows normal supply operation; red FAULT indicates a fault. Red FAULT together with a flashing green indicator signifies an overloaded 9 V I/O bus. During S5 maintenance, check input voltage, load and connections before condemning the supply from its LEDs alone.
Isolation, dimensions and ambient conditions
There is no galvanic isolation. Assess grounding and reference connections against the system diagram. Dimensions are 45.4 × 135 × 120 mm. Permitted ambient temperature is 0…+60 °C horizontally or 0…+40 °C vertically.
Editor’s Note
When buying a used Siemens PS 935, verify 935-8ME11 on the label. A similar front cover does not establish equivalence: the required output here is the 9 V I/O bus supply.
Do more than a no-load check. Monitor input and output together with a suitable test load; a supply that looks healthy unloaded may drop under load. Record the load and test duration.
A FAULT indication is not a reason to replace capacitors immediately. Inspect for trapped ribbon cables, oxidized connectors and excessive consumption from added modules. Establish whether the supply or its load causes the problem.
Photograph the module sequence and record addresses before removal. Overlooking the two reserved slots can leave the program reading incorrect inputs after power is restored. Record the operating mode of an ET station as well.
Check the bases, coding parts and partitions in the Ex arrangement. A functioning PS 935 alone does not validate the complete Ex circuit. Do not describe a board as tested without a recorded test result.
OtomasyonAVM resources and PDFs
+ S5 power supply models · S5 analog modules · Shared SIMATIC S5 PDF archive – S5-115 PDF files
Related topics
+ 6ES5 930-8MD11 · 6ES5 931-8MD11 · 6ES5 700-8EA11 Ex bus unit · 6ES5 318-8MC12 IM 318-C
Browse SIMATIC S5
+ Siemens SIMATIC S5 · S5 power supplies · S5 interface modules · Used Siemens equipment
Siemens and external references
+ Siemens Ex I/O: S5-100U – 6ES5 998-0EX22, Release 02 (English). Section 11.4: application, addressing and diagnostics; Appendix F, F-2/F-3: PS 935 specifications.
+ Siemens S5-100U System Manual – EWA 4NEB 812 6120-02b, Edition 04 (English). Printed page 14-6: 6ES5 935-8ME11 technical data.
+ Siemens ET 200U Manual – EWA 4NEB 812 6087-02b, Edition 03 (English). Installation and connection: 3-4/3-15; PS 935 data and DP mode identifiers: 8-10.