6ES5 788-7LB11

Siemens 6ES5 788-7LB11 — Analog Input/Output Simulation Module

Siemens 6ES5 788-7LB11 is a SIMATIC S5 simulation module for one analog input signal and one analog output signal. Listed in the S5-135U/S5-155U section of Siemens ST 50, this auxiliary module provides a ten-turn setting potentiometer, separate input and output range selectors, and two measuring instruments with 0–100 % scales.

It supports commissioning, training and fault-finding by applying a controlled value to an analog input and displaying the resulting analog output. The catalogue identifies the associated S5 analog modules as the 460 analog input and 470-7LB analog output families, allowing the input and output paths to be checked separately.

Ten-turn adjustment and percentage displays

The input rotary selector chooses the test range. A ten-turn potentiometer sets the applied value, which is shown on the input measuring instrument. Changing the analog signal progressively helps assess the input module together with the scaling used in the program.

Both instruments use 0–100 % scales. Interpret the percentage against the selected electrical range; it is not a direct voltage or current reading. When checking low, middle and high points in an analog input/output path, record the selector setting, module range and programmed engineering units together.

Signal type and output monitoring

Before testing, establish whether the circuit uses a voltage signal or a current signal. Match the simulator selector to the input or output module setting. This Siemens catalogue page describes the selectors and percentage scales; exact electrical range selection must follow the relevant module and connection instructions.

Field analog sensors include devices with 4–20 mA outputs and 0–10 V outputs, which require different connection and measurement methods. Before substituting a test signal for a field device, disconnect the existing signal path and verify that the selected simulation range suits the input being tested.

The output side has its own range selector and measuring instrument. It displays the physical signal delivered by the 470-7LB output module in response to the PLC command. This helps compare the programmed numerical value with the output module’s digital-to-analog conversion path.

768-7LB cable and two-slot installation

The catalogue specifies a 768-7LB connecting cable, 0.3 m long, to be ordered separately. When buying a used module, check whether the required S5 cable and connector are included. Treat 768-7LA and 768-7LB as distinct connecting parts.

Siemens lists installation in ZG 135U/155U and ZG 135U central controllers, and the EG 185U expansion unit. Each simulation module requires two slots. Allow for this width in the S5 rack and check the available space, connector arrangement and mechanical fit within the existing SIMATIC S5 system.

STEP 5 testing and other 788 variants

The address and data format observed in the PLC program depend on the 460 or 470-7LB analog module under test. As the potentiometer setting changes, compare the raw input value with the scaled result. During fault-finding, checking input wiring, programmed conversion and physical output response as separate steps helps narrow down the fault.

6ES5 788-7LA11 is another simulation model for 16 binary input and 16 binary output signals; 788-7LB11 handles analog signals. The distinction between analog and digital inputs matters when selecting a simulator. The 788-7LC variant handles the entry and display of numerical values such as timer or counter values. The shared 788 designation alone does not identify a suitable replacement.

Editor’s note

Start by checking the potentiometer and both measuring instruments. A rotating knob alone proves little: the signal should change smoothly, the pointers should move freely, and returning to the same setting should give a repeatable result.

Confirm the cable early. Without the 768-7LB connecting cable, even a working module may be difficult to test on the bench. A similar-looking connector is not enough to establish a compatible connection.

Do not read the percentage scale as a voltmeter. Record the selected range first, then compare low, middle and high points with a suitable reference instrument. A shifted mechanical zero should not be mistaken for an analog module fault.

When checking used analog modules, test the input and output paths separately. A good result in one direction does not establish the condition of the other. Operate the range selector several times and return to the same test point; investigate contacts and connections if readings become unstable.

Before a test on an installed machine, establish which valve, drive or other load the output can affect. Set up controlled test conditions and change values in small steps. Keep the Siemens S5 system project backup and original wiring photographs available for restoring the previous arrangement.

OtomasyonAVM resources and PDFs

See S5 analog modules and About Siemens S5 PLC for system and signal background. General documents are collected in the shared Siemens S5 PDF archive. Links to the ST 50 model page are provided below. The catalogue also lists manual 6ES5 998-0EA11 in German and 6ES5 998-0EA21 in English.

Related topics

+ 6ES5 788-7LA11 — simulation module for binary signals.

+ Analog inputs compared with digital inputs.

+ S5 cables and connectors.

+ PLC fault-finding and signal tracing.

Browse SIMATIC S5

S5 auxiliary and expansion modules · S5 analog modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

Siemens ST 50, 1998 — English — Manufacturer catalogue, printed p. 4/104, PDF p. 268. Exact 6ES5 788-7LB11 part number, 460/470-7LB connection, controls, instruments and installation scope.

Siemens ST 50, 1998 — Deutsch — German manufacturer catalogue copy, printed p. 4/104, p. 176 in this PDF; ALL4SPS archive.