6ES5 430-8MB11

Siemens 6ES5 430-8MB11 – 4-Channel 24–60 V DC Digital Input Module

6ES5 430-8MB11 is a Siemens SIMATIC S5 module with 4 digital inputs and a nominal input voltage of 24–60 V DC. This member of the S5 digital input range provides optocoupler isolation. Its four inputs share one isolation group and a common M reference.

The card reads field contacts and suitable DC sensors in the S5-90U, S5-95U and S5-100U family. Check CPU expansion requirements, bus unit and address allocation together in the SIMATIC S5 system. Follow the relevant system manual when connecting an S5-90U CPU or another station.

Input thresholds and sensor current

Logic 0 is −33 to +8 V; logic 1 is 13–72 V. The region between 8 and 13 V should not be used as a defined logic state. Assess these signal thresholds alongside the 24–60 V DC nominal supply specification.

Typical input current is 4.5 mA at 24 V and 7.5 mA at 60 V. Two-wire BERO connection is supported; sensor off-state residual current must not exceed 1.5 mA. Include sensor leakage current when investigating an input that fails to turn off.

L+, M and input connections

The Siemens drawing assigns terminal 1 to L+ and terminal 2 to M. Check the DC power supply voltage and M return together. Maintain the specified M return separately from protective grounding.

The four inputs use terminals 4, 6, 8 and 10, respectively. Terminals 3, 5, 7 and 9 distribute L+ in the drawing. Match field cable labels to that order. The circuit operates by applying positive voltage to an input; when selecting PNP sensors, check their output ratings and their own supply-voltage limits.

Red F LED and response time

The red fault LED indicates missing L+ input supply. Check L+–M voltage and connections first when it illuminates. Delay in either switching direction is typically 3 ms, with a 1.4–5 ms range; include CPU scan time when assessing short pulses.

Bus unit and mechanical installation

The module plugs into a suitable bus unit. The family includes bus modules such as the 6ES5 700-8MA11 and 6ES5 700-8MA21. Compare mechanical coding, terminal condition and included parts with the existing unit before replacement.

S5-100U addressing and the .4–.7 markings

On the S5-100U, a digital module’s byte address is its slot number. The input/output address plan uses only .0–.3 for this four-channel card. In slot 3, for example, English STEP 5 notation reads I 3.0, I 3.1, I 3.2 and I 3.3.

Front-panel markings .4–.7 do not identify four additional physical inputs. The S5-100U manual states that these numbers apply to ET 100U addressing. Do not assume that two four-channel cards share one byte on the S5-100U.

ET 100U and ET 200U operation

The card also appears in the ET 100U and ET 200U module lists. For distributed I/O stations, check address allocation and configuration against the fitted station interface. Establish the address arrangement from that station’s documentation.

Supply consumption and operating conditions

Specified consumption is 5 mA from the CPU’s internal 9 V bus supply and at most 35 mA from L+. Maximum module power loss is 2 W. Permitted ambient temperature is 0–60 °C for horizontal installation and 0–40 °C for vertical installation. Maximum unshielded cable length is 100 m.

Differences from similar codes

The 6ES5 420-8MA11 is a four-input, 24 V DC, non-isolated model. The 6ES5 421-8MA12 has eight 24 V DC inputs, while the 6ES5 431-8MA11 provides eight isolated 24 V DC inputs.

The 6ES5 430-8MC11 belongs to the 115 V input class, and the 6ES5 430-8MD11 to the 230 V class. Check the full order number and voltage rating when replacing a card with a similar housing or 430 designation.

Used-module checks and replacement preparation

Back up the program and memory unit, and photograph the bus position, M common and channel labels. Test each of the four channels in both states with a suitable source.

During S5 maintenance, assess the LED, program input bit and terminal voltage together. For used Siemens modules, state label details, included bus unit, physical condition and completed tests for the individual item.

Editor’s note

Start with the supply when the red F LED comes on. Check L+ and the M return. A loose terminal can make a healthy card appear faulty.

Keep the shared group in mind. All four inputs use the same isolation group and M common. Check that shared connection when several channels misbehave together.

Read the .4–.7 markings in their system context. On the S5-100U, this card uses .0–.3. Confirm the system before tracing a program address.

Check the sensor label before raising the supply. A card that accepts 60 V does not make a connected sensor suitable for 60 V. Assess the two ratings separately.

Check that the input turns off as well. This is particularly useful with two-wire sensors. Record the off-state voltage and program bit, and keep a result for all four channels.

OtomasyonAVM resources and PDFs

+ Shared SIMATIC S5 manuals and PDF archive

+ S5 digital input modules and model pages

Related topics

+ 6ES5 420-8MA11 – 4-channel 24 V DC input

+ 6ES5 421-8MA12 – 8-channel 24 V DC input

+ 6ES5 431-8MA11 – 8-channel isolated input

+ 6ES5 430-8MC11 – 115 V input

+ 6ES5 430-8MD11 – 230 V input

+ 6ES5 700-8MA11 bus module

Browse SIMATIC S5

+ Back to S5 digital input modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and models

Siemens and external references

+ Siemens S5-100U – 430-8MB11 specifications and wiring, 14-19 (English)

+ Siemens S5-100U – four-channel module addressing, 6-4 (English)

+ Siemens ST 50 – thresholds and two-wire BERO limit, 2/27 (English)

+ Siemens ET 100U manual – module list and station addressing (English)

+ Siemens ET 200U manual – module list and configuration (English)