6ES7 153-2AA02-0XB0

6ES7 153-2AA02-0XB0 – Siemens ET 200M IM153-2

Series: Siemens SIMATIC DP / ET 200M
Category: PROFIBUS DP interface module

Description and system role

6ES7 153-2AA02-0XB0 is an IM153-2 interface module that connects a Siemens ET 200M station to PROFIBUS DP. It allows suitable S7-300 modules to operate as remote I/O near the machine. The control program runs in the upstream PLC CPU; the IM153-2 handles communication between that controller and the remote station within the SIMATIC S7 system.

The station may contain suitable digital input, digital output, analog input and function modules. These links describe module groups across the ET 200 family. Each selected component must also be approved for ET 200M and the particular IM153 version.

Technical specifications

Network: PROFIBUS DP over an electrical RS-485 interface with a 9-pin Sub-D connector. Maximum transmission rate: 12 Mbit/s. Station address: 1–125. Module capacity: up to 8 suitable SM/FM/CP modules to the right of the interface. This order number has neither a PROFINET port nor an integrated fiber-optic interface.

Supply: 24 V DC, permissible range 20.4–28.8 V DC. Current consumption at 24 V: maximum 550 mA. Typical power dissipation: 5 W. Dimensions: 40 × 125 × 117 mm (width × height × depth). Weight: approximately 360 g. When selecting an external power supply, account separately for station electronics and field loads.

Installation and configuration

Check the mounting rail, backplane arrangement and connection components against the existing station. The configured module order must match the physical installation. Select the correct IM153-2 version in STEP 7 hardware configuration, or check the appropriate GSD definition when using another DP master. The ET 200 system overview and PROFIBUS/PROFINET interface guide help distinguish the different station architectures.

For communication problems, start with the supply, station address, bus connector, cable shield and termination. Replacing the interface alone will not resolve a wiring or configuration error. Follow the applicable Siemens removal and installation procedure when servicing the station.

Product versions and feature limits

The E version matters even when the order number is unchanged. Siemens lists 96-byte enhanced diagnostics from E07 and DPV1 operation from E09. This model does not support SYNC/FREEZE, isochronous mode, firmware updates over PROFIBUS or updates using an MMC. Features of later IM153-2 generations must not be assumed for the 2AA02.

Redundancy and fail-safe modules

Two IM153-2 modules can provide redundant communication in a supported system. Siemens' software redundancy manual lists 6ES7153-2AA02-0XB0 from product version 02. For this older interface, the redundant backplane arrangement uses BM IM/IM 6ES7195-7HD00-0XA0. Check both masters, both interface versions and the project configuration together. Installing a second interface is only one part of a redundant system. I/O module replacement during operation requires suitable active bus modules and the correct parameters; this capability must not be assumed for a standard backplane connection.

When using fail-safe modules, check the individual F-module's hardware and firmware requirements. Siemens identifies support for specified S7-300 F-modules starting at E05 with firmware V1.1.0 for this interface. This is not approval for every F-module: SM336 F-AI 6 × 0/4–20 mA HART, for example, requires a later 2BA0./2BB0. interface. PROFIsafe operation also requires the appropriate fail-safe controller and safety program.

Diagnostics and replacement checks

The ON LED indicates supply status, BF a bus fault, SF a group fault and ACT the active interface. Read the master's diagnostics and module information alongside the LED indications. A communication alarm on an HMI or SCADA screen is a starting point for investigation, not proof that the interface itself has failed.

Before ordering a replacement, compare the complete order number, E version, firmware and bus module code with the installed equipment. Keep a copy of the STEP 7 project and record the module sequence. If changing to another IM153-2 order number, establish compatibility from the manufacturer's tables before treating it as a direct replacement.

Editor's Note

The IM153-2 name on the front cover is not enough to identify a suitable replacement. Ask for a clear label photograph showing the E version, and record the bus module code in a redundant station. A used unit that powers up has not necessarily passed a PROFIBUS communication test. Where possible, test it in a configuration representative of the intended installation.

PDF manuals and technical references

Use the ET 200M operating instructions, particularly section 10.3 for specifications and appendix A.2 for version compatibility, together with Software redundancy for SIMATIC S7 and the applicable S7-300 fail-safe module documentation. Visit Siemens ET 200 PDF and user manuals for the documentation page.

Related topics

About ET 200 · ET 200 communication interfaces · ET 200 additional modules · ET 200 terminal blocks · PROFIsafe