6ES7 193-7AB00-0AA0
Siemens main menu › SIMATIC S7 › SIMATIC ET 200
Siemens 6ES7 193-7AB00-0AA0 — ET 200iSP TM-IM/IM Terminal Module
6ES7 193-7AB00-0AA0 is the TM-IM/IM terminal base for two redundant interface modules in the ET 200iSP series of the Siemens ET 200 distributed I/O family. It holds two IM modules side by side and provides the station connection infrastructure. The interface modules are separate components; this order number identifies their terminal base.
Series: SIMATIC / ET 200iSP
Type: TM-IM/IM
Order number: 6ES7193-7AB00-0AA0
Module arrangement: Two interface modules, left and right slots
Dimensions (W × H × D): 60 × 190 × 52 mm
Approximate weight: 195 g
Manufacturer's delivery description: Includes power bus termination module
Distinguishing PROFIBUS and PROFINET applications
When reviewing the ET 200 system architecture, identify the fitted interface modules as well as the terminal base. Siemens’ March 2025 manual specifies this base for redundant IM 152-1DP — 6ES7152-1AA00-0AB0 and IM 152-1PN — 6ES7152-1BA00-0AB0 interfaces. This does not mean that one DP module and one PN module can form a mixed redundant pair.
ET 200 PROFIBUS and PROFINET interfaces use different network connections. In a PROFIBUS DP installation, the base provides two 9-pin D-sub sockets for PROFIBUS RS 485-IS. With IM 152-1PN, these D-sub connections are not connected inside the interface module; the sockets on the base are not used for PROFINET communication.
How it differs from TM-IM/EM and TM-EM/EM
Similar names within the ET 200 terminal block range describe different slot arrangements. TM-IM/IM holds two interface modules. TM-IM/EM holds one interface and one electronic module, while TM-EM/EM holds two electronic modules. When selecting ET 200 connection modules, matching the width or appearance is therefore insufficient.
Station position and the termination module
TM-IM/IM follows the station’s power supply section. The arrangement of ET 200 power supply modules must be considered separately from interface redundancy: two IM modules do not imply redundant power supplies. Field-side ET 200 digital input modules, ET 200 analog input modules and ET 200 digital output modules continue on their own appropriate terminal bases.
Siemens lists a power bus termination module as included. This component is installed at the right-hand end of the station; it is not the terminating resistor in a PROFIBUS connector. For used equipment, compare the manufacturer's standard package with the components actually included in the seller's offer.
Five checks before ordering or maintenance
1. Full order number: Verify 6ES7 193-7AB00-0AA0 on the label. Do not substitute a TM-IM/EM or TM-EM/EM base based on appearance.
2. Interface pair: Record both IM order numbers, hardware revisions and firmware versions. Redundant operation also requires a suitable controller, network arrangement and project configuration.
3. Network connection: For DP, inspect both D-sub sockets, securing points and RS 485-IS connection components. For PN, do not mistake the base’s D-sub sockets for network ports.
4. Supply and physical condition: Check the side contacts for bending, corrosion or heat damage, and inspect the housing and rail latch. Assess the ET 200 power distribution arrangement separately from interface redundancy.
5. Scope of supply: Confirm the termination module, whether the interfaces are included, and any necessary ET 200 additional modules and accessories before ordering.
Editor's note
Avoid two purchasing assumptions: that the two-slot base alone provides redundancy, and that both IM modules automatically come with it. Redundancy depends on a suitable interface pair and correct system configuration. Listing the base, interfaces and termination component separately in the quotation makes the delivery scope clear.
Manuals and PDF documentation
Visit our Siemens ET 200 PDF and user manuals page for documentation. Section 12.4 — TM-IM/IM of the ET 200iSP manual, 03/2025, A5E00247483-AL covers both DP and PN interfaces. Do not decide PN compatibility solely from an older edition describing only DP installations.
For hazardous-area installations, assess the product markings, hardware revision, enclosure and installation conditions together. Approval of the base does not make every complete station arrangement suitable; installation and replacement must follow the manufacturer's instructions and be performed by qualified personnel.
Related topics and Siemens navigation
Product family: Siemens automation | SIMATIC S7 | ET 200 family
Interfaces and connections: PROFIBUS and PROFINET | Terminal blocks | Connection modules
Power and technical resources: Power supply modules | ET 200 system architecture | ET 200 PDF manuals