6ES7 193-4CE00-0AA0

Siemens main menu › SIMATIC S7 family › ET 200 › Terminal blocks

6ES7 193-4CE00-0AA0 — ET 200S TM-P15S22-01 Power Module Terminal Base

6ES7 193-4CE00-0AA0 is the TM-P15S22-01 screw-terminal base for PM-E power modules in ET 200S, part of the Siemens ET 200 family. Within the ET 200 terminal block range, it supports the power module and provides the external supply connections. It is not a standalone power supply.

Technical details and AUX1 arrangement

Width: 15 mm. Connection: Four screw terminals in a 2×2 arrangement. Dimensions: 15 × 119.5 × 43 mm (width × height × depth).

Together with a compatible ET 200 power module, the base provides the infeed for a new potential group extending to the next TM-P terminal. Plan the ET 200 power distribution arrangement around these group boundaries.

The AUX1 bus remains continuous and electrically connected to AUX1 in the adjacent group on the left. However, this base provides no terminal access to AUX1. Starting a new supply group therefore does not also separate AUX1.

Power module combinations

Siemens documents show its use with 6ES7138-4CA00-0AA0 PM-E DC24V. The manual for 6ES7138-4CA50-0AB0 PM-E DC24..48V also lists this base as compatible. Select ET 200 connection components against the complete power module number; operating voltage and load limits cannot be determined from the terminal designation alone.

Five checks before selection or replacement

1. Terminal class: Do not confuse this TM-P power-module base with a TM-E electronic-module base of the same width.

2. Connection method: 6ES7193-4CE00-0AA0 / TM-P15S22-01 uses screw terminals; 6ES7193-4CE10-0AA0 / TM-P15C22-01 uses spring terminals. Check the full order number and existing conductor ends.

3. AUX1 requirements: If a wire connection to the auxiliary potential is needed at this position, account for the absence of AUX1 terminals. Compare wiring diagrams before selecting a different terminal type.

4. Supply and load: Check the PM-E module’s permitted voltage, the group’s total load and the protection specified for the installation. Four terminal points do not mean four independent power outputs.

5. Physical condition: Inspect screws, contacts and latches for distortion or heat damage. Alongside the ET 200 additional modules and accessories, check that adjacent terminal bases engage fully.

Role within the station

The base does not measure or switch field signals. These functions belong to the appropriate digital input modules, digital output modules and analog input modules. Communication is handled by the PROFIBUS and PROFINET interface modules; the terminal base has no separate network address.

Editor’s note

The 15 mm width is only one part of the selection. A continuous AUX1 bus and terminal access to AUX1 are different features. Read the potential distribution diagram before replacing the base; matching its physical size is not enough.

PDF documentation and user manuals

On the Siemens ET 200 PDF and user manual page, consult the TM-P15x22-01 section of ET 200S Terminal Modules and the wiring table for the intended PM-E module. Check the data sheet against the complete order number 6ES7193-4CE00-0AA0.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive