6ES5150-3SB61

Siemens 6ES5 150-3SB61 SIMATIC S5-150U Central Unit

The Siemens 6ES5 150-3SB61 is the AC-powered central unit for SIMATIC S5-150U. The CPU board set, power supply and expansion interfaces share one chassis. See the Siemens S5 PLC guide for the system architecture and the S5 rack section for other chassis types.

Power supply and fans

Siemens lists the 6ES5 955-3LF11 and 6ES5 955-3LF12 supplies for the AC version. The manual specifies 110 or 220 V AC at 50 Hz input and a main output of 5.1 V DC at 40 A. The 3SB81 order number identifies the 24 V DC version. When sourcing a used PLC power supply, verify the chassis label, the fitted supply order number and the voltage setting separately.

CPU boards and slot assignments

The 924 S, 925 S, 926 S and 927 S CPU boards occupy fixed slots 35, 43, 51 and 59, respectively. The manual shows 16 additional module positions. Backplane jumper settings determine the function of some of these slots. When sourcing a used PLC CPU or an S5 function module, record both the full board order number and its installed slot.

Program memory and PG connection

For STEP 5 programming, Siemens specifies the AS 511 (6ES5 511-5AA12) interface in slot 69 or 79 for connecting a programming device. The manual also calls for a 340 or 350 memory module before commissioning. When comparing S5 memory cards, distinguish RAM from EPROM. A power cycle with the Batt. Low indicator lit can cause loss of RAM contents. Back up the program before replacing boards to reduce the risk of memory data loss.

Expansion and used equipment checks

The Siemens manual gives the EG 185 expansion rack as an option for adding modules. This arrangement uses an IM 304 in the central unit and an IM 314 in the expansion rack. Record the full order numbers of the fitted interface modules and connecting cables. Also record the slots used by digital input, digital output and analog I/O modules.

As with other used electronic boards, check for corrosion, damaged rear connectors and signs of solder rework. Ask the seller for photos of the labels on the CPU boards, memory and power supply.

Editor’s note
Siemens states that the 5 V rail comes on once both fans reach sufficient speed. When buying a used 150U, ask for a startup test record that shows both fans running, the Fan Fault indicator status and the 5 V rail coming on.

If you have this central unit for sale, send photos of its labels and boards to otomasyonavm@gmail.com.

Siemens S5 PDF archive

The Siemens 150U manual appears in the references below. See the shared Siemens S5 PDF archive for other S5 documentation.

Related topics

6ES5 183-3UA12 expansion rack · 6ES5 188-3UA11 S5-135U/155U central rack · 6ES5 955-3LF41 S5-135U/155U power supply

References

Siemens AG 150 U operating instructions, C79000-B8500-C346-04 (German) · Power supply specifications, pp. 13–14 · Commissioning, p. 28