6ES5 415-7AB11
Siemens 6ES5 415-7AB11 — 8-Channel 115 V AC / 2 A Triac Output Module
6ES5 415-7AB11 is an 8-channel, galvanically isolated digital output module for the S5-110A in the Siemens SIMATIC S5 family. Its triac digital outputs switch 115 V AC loads. The permissible supply range is 88–132 V AC, with a maximum output current of 2 A per channel.
It switches AC coils and control loads in SIMATIC S5 installations. Assess the S5-110A arrangement using the appropriate rack, such as the 710-0AA11 mounting rack. 7AB11 is the 115 V AC version; do not transfer the voltage ratings of the 220 V AC version or the wiring of another S5 family to this module.
Channel current and temperature-dependent total load
2 A is the limit for one output. Siemens specifies a total loading factor of 100% at 20 °C and 50% at 55 °C for static outputs. The curve for the combined current of all eight outputs shows 16 A and 8 A respectively. Operating every channel at 2 A simultaneously is unsuitable at higher cabinet temperatures.
When selecting relays, contactors and interposing relay coils, check release behaviour as well as continuous current. Maximum switching frequencies are 20 Hz for resistive loads, 11 Hz for lamps and 2 Hz for inductive loads. The AC circuit is interrupted at current zero.
Off-state residual current and RC elements
Maximum residual current with the output at logic 0 is 8 mA AC. RC elements in the module produce capacitive residual current; the connected load must recognize that current as the off state. Particularly with small coils, an unloaded voltage reading alone should not determine whether the module is faulty.
Siemens states that contactors driven by these outputs must not have additional RC elements. The reason is parallel resonance that may be excited by the residual current. Inspect existing coil suppression components and the load specifications before changing the wiring.
Fuse, supplies and field wiring
The manual specifies an FF 6.3 A very fast fuse for short-circuit protection, giving Wickmann No. 19230 as an example. This fuse rating does not increase the 2 A channel load limit. Check the affected load and field cable before replacing an open fuse.
Assess the S5 power supply separately from the AC load supply. When inspecting S5 cables and connections, compare the upper and lower double-row screw terminals, channel markings and installed jumpers with the manufacturer’s diagram. In an expansion arrangement, also check the interface connections and rack compatibility.
Addressing and checks under load
Verify the output address in the PLC program against the installed rack and input/output assignment. The order code alone does not determine a fixed output byte address. During fault diagnosis, compare the program command, load supply and actual load behaviour. Establish safe machine test conditions before taking measurements.
For AC feedback circuits, an input card such as the 405-7AB11 115 V input module performs a separate function. Matching input and output voltage ratings do not make the two types interchangeable.
Differences between related codes
415-7AA31 is the 24–48 V AC version and 415-7AB21 is the 220 V AC version. 410-7AA11 has 24 V DC transistor outputs, while 417-7AA21 has relay outputs. Compare the complete order code, load voltage, switching technology and wiring when choosing a replacement.
Editor’s note
Start with the 7AB11 label and the 115 V AC load supply. A similar-looking 7AB21 is not a reason to connect this card to a 220 V circuit. That small suffix makes a substantial difference here.
If the meter shows voltage with an output off, give the card a fair check before setting it aside. There can be 8 mA of residual current; measure with a suitable load and check whether the coil actually releases. An unloaded reading can be misleading.
Do not assume another RC component across the coil will solve the problem. Siemens does not permit additional RC elements on contactors driven by these outputs. First establish what is already fitted to the coil and which load is connected.
If a fuse has opened, find the cause before replacing it and moving on. The specified type is FF 6.3 A, very fast; a higher fuse rating does not increase the card’s load capacity. Checking the cable and load can prevent a repeat failure.
For a used card, check all eight channels individually with suitable loads. Allow for total current in a warm cabinet too: the limit at 55 °C is 8 A. Photograph the label and connections before removal; those records will help at the next maintenance visit.
OtomasyonAVM resources and PDF files
+ S5 PDF files and user manuals · About Siemens S5 PLCs. The main reference is the S5-110A Operating Instructions, GWA 4NEB 807 0690-02 / 6ES5 998-0AA22, in English. Operating principles: printed 1.7 / PDF 11; specifications and total-load curve: 1.13 / PDF 17; connection notes: 2.6 / PDF 25.
Related topics
+ 415-7AA31 low-voltage AC output · 415-7AB21 220 V AC output · 410-7AA11 DC output · 417-7AA21 relay output · PLC fault diagnosis.
Browse SIMATIC S5
+ S5 digital output modules · S5 racks · S5 interface modules · Siemens S5 PLC · Siemens second-hand equipment.