6ES5 958-4UA11

Siemens 6ES5 958-4UA11 – 24 V Enable Supply Module

Siemens 6ES5 958-4UA11 provides a 24 V supply for I/O-module enable inputs in SIMATIC S5 systems. The Siemens technical description specifies use with up to 80 compatible compact modules from the 6ES5 4..-4U.11 family. This auxiliary supply module supports the I/O enable supply during operation and switching of the S5 system.

Check enable wiring against the requirements of the installed analog modules, digital inputs, digital outputs and combined I/O modules. The 80-module figure applies to the specified compatible family and current limits. Verify each module’s enable connections in its own documentation.

Output rating and source supply

The module receives its 24 V auxiliary supply through the lower bus connector. Its front output is rated 24 V, maximum 400 mA, with electronic short-circuit protection. Check the S5 power supply auxiliary capacity and other loads together with the rack arrangement.

The technical description lists source supplies including 6ES5 955-3LC13, 6ES5 955-3LF11, 6ES5 955-3NA11 and 6ES5 955-3NF11. Assess the source supply capacity alongside the 958’s 400 mA output limit.

42-pin front connector

The front connector has 42 pins. Siemens assigns pins 1–21 to positive and pins 22–42 to negative. Compare pin numbers with existing wire labels when connecting cables and connectors. When purchasing S5 supplementary equipment, establish whether the front connector is included.

Central-controller and expansion-unit installation

Siemens specifies installation in a central controller or expansion unit with an integrated power supply. Enable inputs in expansion units without their own power supply, such as EG 184U and EG 187U, are supplied through a 958 installed in a unit that has a power supply. Trace the expansion interface and enable wiring separately.

During S5 maintenance, record the origins of the load and enable supplies. Verify the effect of losing enable voltage for the actual modules, CPU and PLC program. Include voltage measurements at the affected module’s enable input during fault diagnosis.

Editor’s Note

When buying a used Siemens module, check the complete label and front connector. Establish which I/O enable inputs the 958 supplies in the existing installation. Trace the circuit before selecting a replacement.

Start measurements from a verified reference point. Check the incoming auxiliary supply, the module output and then the enable input at the connected card. Compare unloaded and loaded measurements when investigating voltage loss or an intermittent connection.

Read the numbers on the 42-pin connector carefully. Confirm polarity against the wiring diagram, and inspect for bent pins, loose contacts and heat damage. Investigate connections if moving a cable changes the fault.

Preserve the intended enable circuit. Check the project before adding links or combining it with the load supply. Establish how the connected modules behave during power-up and power-down.

Finish with a controlled check of module startup and actual machine functions. Record the connected modules, measured voltage and corrective work in the maintenance notes. Leave a clear wiring reference for the next repair.

OtomasyonAVM resources

+ 6ES5 958-4UA11 model page · Siemens S5 second-hand models · S5 power supplies · S5 cables and connectors.

Related topics

+ 6ES5 955-3LC13 · 6ES5 955-3LF11 · 6ES5 955-3NA11 · 6ES5 955-3NF11. These links concern source-supply selection; they are not direct replacements for the 958.

Browse SIMATIC S5

+ S5 function and supplementary hardware · S5 racks · S5 analog modules · SIMATIC S5 · Siemens second-hand main page.

Siemens and external references

+ Siemens U Periphery manual, 6ES5 998-0PC22, English. Technical description C79000-T8576-C395-01: 6ES5 958-4UA11, 24 V / 400 mA output and pin assignment. U-Series Installation Guide, section 2.8.2: enable supply from central controllers and expansion units.

+ Siemens S5-150U manual, German. Installation section B85452/2, printed pages 15–16: 958 installation conditions and supply of expansion units without an integrated power supply.