GD300-16
INVT GD300-16 HVAC Pump and Fan Drive
The INVT Goodrive300-16 is a variable-frequency drive for heating, ventilation and air conditioning (HVAC) and water supply. In a booster system, it increases pump speed when pipe pressure falls below the setpoint. In ventilation systems, a similar arrangement can regulate duct pressure.
Constant pressure and multi-pump operation
A pressure transmitter sends the measured pressure to the drive. In closed-loop operation, the PID controller compares the reading with the setpoint and adjusts the frequency reference. The drive has two PID loops. With sleep and wake configured, the pump can stop at low demand and restart when pressure falls again.
The manual covers two arrangements. One pairs a dedicated variable-speed pump with fixed-speed auxiliary pumps. The other rotates variable-speed duty among pumps. Check the lead and standby roles, contactor arrangement and each motor nameplate when selecting a drive.
Nameplate, control modes and communications
GD300-16-011G/015P-4 is one example in the three-phase 380–440 V class. For this frame, the manual lists 11 kW / 25 A for G duty and 15 kW / 32 A for P duty. When selecting a drive, check the load duty, motor nameplate current and rated frequency. The series supports V/F and sensorless vector control.
Modbus RTU over RS-485 is available. For BACnet, check the communications option fitted to the drive. When connecting an INVT PLC or INVT HMI, check the port and use the drive's register map. The INVT VFD Software page covers INVT Studio. Confirm support for the full GD300-16 model code and firmware revision before connecting a PC.
Editor's Note
Before replacing a drive, photograph the nameplate and back up the settings if you can still access them.
If the gauge and display disagree, check the transmitter and input scaling before adjusting the PID loop.
If pressure will not settle, check the acceleration and deceleration ramps. Watch what happens as each pump starts.
Check how the pressure responds when an auxiliary pump starts, and make sure the standby pump takes its turn.
If a fault recurs, record the code, running frequency and which pump was running. That gives the next technician a much better starting point.
Related topics
Commissioning and operation: Motor auto-tuning · Skip frequency · Flying start · Carrier frequency · Drive losses
Fault diagnosis: VFD fault codes · DC bus · Overvoltage · Undervoltage · Phase loss. See section 3.7 of the manual for the GD300-16 fault table.
Other INVT drives: Goodrive300 · CHV160 · CHV160A.