• Gemo TT104A

Gemo TT104A is a compact 48 × 48 mm temperature controller with a built-in timer. It supports J, K, T, S and R type thermocouples as well as Pt100, with selectable P, PI, PD, PID or ON/OFF control. OtomasyonAVM has been supplying Gemo products since 2013.

Panel dimensions: 48 × 48 mm.
Standard supply: 220 VAC.
If a 24 V supply version is required, this must be specified when ordering.
Output: Dry-contact relay output as standard. If an SSR output version is required, please specify this when ordering.

Selectable sensor inputs: J, K, T, S and R type thermocouples and Pt100.

The controller can be used with a J type thermocouple or Pt100, depending on the selected input setting.

The TT104A combines temperature control and timing in one compact panel unit. The built-in timer can start automatically when the process temperature reaches the selected trigger level.

ON/OFF and PID operation

If H.Hys is set to a value other than zero, the controller operates in ON/OFF mode.

If H.Hys = 0, PID control is enabled for the heating function.

Pb.C – Proportional band: Defines how many degrees before H.SET the time-proportional control begins. The proportional band ends at H.SET.

Ct – Control period: The control cycle period. A setting of 4–10 seconds is recommended in the source documentation.

Ti – Integral time: Used to reduce the remaining difference between the process value and SET value. Lower Ti settings give a faster response, but excessively low values may cause temperature oscillation.

If Ti = 0, the integral part is disabled and the controller operates as P or PD.

Td – Derivative time: Used to respond to sudden changes between the process value and SET value. Increasing Td makes the controller more sensitive to rapid changes.

If Td = 0, the derivative part is disabled and the controller operates as P or PI.

PID parameter ranges

Integral time: 0–30.0 minutes; 0 = OFF.
Derivative time: 0–10.0 minutes; 0 = OFF.
Proportional band: 1–130 °C, Pb.C.
Heat hysteresis: 0–50 or 0.0–5.0 °C, H.Hys; setting H.Hys to zero selects PID control.

The PID mode also includes anti-windup and overshoot-reduction functions.

Built-in timer operation

The timer start point is determined by the Process Value PV, temperature setting H.SET and trigger threshold t.HYS.

When PV ≥ (H.SET − t.HYS), the built-in timer starts and the countdown begins.

Once the timer has started, the countdown continues until RESET is applied. At the end of the programmed time, the ALARM output switches ON.

Example: If H.SET = 180 °C and t.HYS = 2 °C, the timer starts when the measured temperature reaches 178 °C or higher.

For the Pt.0 sensor setting, t.HYS can be adjusted from 1.5 to 5.0 °C. For the other sensor types, the available range is 1–50 °C.

Timer reset

Hold the RESET button on the front panel for approximately three seconds to reset the built-in timer and switch the ALARM output OFF.

Timer settings

Time setting: 00:00–99:59 hours, t.SET.
Adjustment step: 1 minute increments / decrements.
Trigger setting: 1–1250 / 1.5–125.0 °C, t.HYS.
ALARM ON duration: Adjustable up to 99:59 minutes.
OUT automatic OFF: OUT can be configured to switch OFF automatically when the T.SET period has finished.

Temperature control features

Heat SET: Lo.L to UP.L, H.SET.
Control modes: P, PI, PD, PID or ON/OFF.
Thermocouple compensation: Ambient temperature compensation.
Pt100 line compensation: Maximum 10 Ω with 3-wire Pt100.

Sensor fault protection: If the sensor or sensor wiring is open, the measurement goes outside the selected range, or the input cannot be read correctly, OUT operates according to the P.Err and Ct settings. If P.Err = 0, OUT remains OFF. The ALARM output remains OFF during an input fault.

Measurement ranges

J type T/C: -100 ... 600 °C, Inpt = J.
K type T/C: -100 ... 1300 °C, Inpt = K.
T type T/C: -100 ... 400 °C, Inpt = T.
S type T/C: 0 ... 1750 °C, Inpt = S.
R type T/C: 0 ... 1750 °C, Inpt = R.
Pt100: -100 ... 600 °C, Inpt = Pt.
Pt100 with decimal display: -99.9 ... 600.0 °C, Inpt = Pt.0.

Output and general features

ALARM output: On TT104A, relay NO contact only, 250 VAC / 2 A resistive load.
OUT output: Relay as standard; SSR version optional.
Parameter protection: Password-protected settings.
Memory: Program and control parameters remain stored when power is removed.

Control panel use

The TT104A can be installed in panels containing AC drives and speed controllers. Sensor and power wiring should be separated where possible, especially when thermocouple or Pt100 signals are used.

Keeping temperature-sensor cables away from motor and inverter output wiring helps reduce electrical interference and improves measurement stability.

Other compatible sensing products can be found in our industrial sensors section.

Gemo TT104A User Manual (PDF)

Gemo price list
Gemo contact information
Gemo main page
Industrial control devices

Installation: Sensor, supply and output wiring should be carried out by qualified technical personnel.

Before applying power, check the selected sensor type, supply voltage, terminal connections and output configuration against the product documentation.

Write a review

Note: HTML is not translated!
Bad Good

Gemo TT104A

  • 52.00USD

  • Ex Tax: 52.00USD

Related Products

Ntc ısı sensörü _v1

Ntc ısı sensörü _v1

DERELL NTC-V1 is a temperature sensor / probe. It provides temperature measurement to a compatible i..

128.00USD Ex Tax: 128.00USD

Ntc ısı sensörü _v2

Ntc ısı sensörü _v2

DERELL NTC-V2 is a temperature sensor / probe. It provides temperature measurement to a compatible i..

129.00USD Ex Tax: 129.00USD

Ptc ısı sensörü _v1

Ptc ısı sensörü _v1

Silicon PTC thermistor temperature sensor features:There is a nearly constant TK (temperature coeffi..

130.00USD Ex Tax: 130.00USD

Ptc ısı sensörü _v2

Ptc ısı sensörü _v2

DERELL PTC-V2 is a temperature sensor / probe. It provides temperature measurement to a compatible i..

131.00USD Ex Tax: 131.00USD