6ES7 193-1FL60-0XA0

Siemens 6ES7 193-1FL60-0XA0 — two-tier spring terminal accessory for ET 200L

The 6ES7 193-1FL60-0XA0 is a two-tier supplementary terminal with spring connections, intended for the 32-channel Siemens SIMATIC ET 200L arrangement. It adds wiring points to the terminal block, helping keep field connections together at the station. When identifying a replacement, first establish whether you need the main base carrying the electronics or the additional terminal assembly fitted to it.

The 32-channel designation describes the wiring arrangement this accessory serves. It does not mean that the part supplies 32 new inputs or outputs. There is no PLC program running in this terminal assembly, and it does not process field signals. The electronic block installed in the station determines the actual I/O function.

What the extra terminal rows provide

Supplementary terminals allow the ET 200L two-wire arrangement to be completed for three- or four-wire connections with the appropriate hardware. They provide additional termination points close to the station for sensors and other field equipment. Adding these wiring points does not expand the station’s electronic I/O capacity.

An essential detail is that the terminals within each tier are internally interconnected. A row must therefore not be treated as a collection of isolated signal terminals. Connecting different potentials to an interconnected row can create a short circuit. Assign each row according to the circuit drawing, terminal markings and installed base. Internal bridging within each row must not be confused with a connection between the two rows.

Editor’s note: If several sensors disappear together, replacing the digital input module immediately may miss a fault in their shared supply or return connection. Similarly, an active command on a digital output module does not prove that voltage reaches the field load. A useful diagnosis separates the electronics, shared wiring and individual field circuits before deciding which component needs attention.

Identification and replacement selection

Manufacturer: Siemens. Order number: 6ES7193-1FL60-0XA0. Product group: SIMATIC DP / ET 200L supplementary terminal. Arrangement: 32 channels, two tiers. Connection method: spring terminals. The Siemens product data sheet revised on 16 March 2017 gives an approximate weight of 213 g; this is not a packed shipping weight.

Do not confuse this accessory with the 6ES7 193-1CL10-0XA0 TB 32L base. The base carries the electronic block, whereas 1FL60 identifies the supplementary terminal assembly. When reviewing connection components, compare the complete order number, mounting interface and terminal arrangement. An ET 200 family name alone does not establish interchangeability with ET 200S or ET 200SP hardware.

The nearby order numbers describe different arrangements. 6ES7 193-1FL50-0XA0 is a single-tier spring version for 32 channels. 6ES7 193-1FL30-0XA0 is a two-tier screw version, while 6ES7 193-1FL20-0XA0 is a single-tier screw version, also for 32 channels. 6ES7 193-1FH60-0XA0 has two tiers and spring connections but serves the 16-channel arrangement. These references help identify differences; they are not a list of drop-in replacements.

Installation and wiring checks

Before disconnecting wiring, place the machine in a safe condition, isolate the relevant supplies and verify the absence of voltage. Record the terminal labels and existing connections so that each conductor can be returned to its intended point. For shared potential rows, use the circuit drawing and terminal markings rather than relying on wire colour alone.

Spring termination requires the correct conductor preparation and release method. Follow the Siemens instructions for wire type, cross-section, stripping length and any ferrule requirements. A damaged spring mechanism, a conductor that is only partly inserted or loose strands outside the terminal can compromise the connection. Route cables and connectors and arrange the surrounding panel components so that the cable does not pull continuously on the terminal.

This accessory does not replace a power supply or generate a voltage. Check the distribution and protection of circuits fed from the DIN rail power supply separately. The current drawn by connected relays and sockets cannot be assessed from the channel count alone. Applicable limits for the terminal assembly, base, electronic block and load must all be respected.

Software and commissioning

There is no separate user program, network address or firmware download for 6ES7193-1FL60-0XA0. Its role is electrical termination. PROFIBUS communication and station configuration belong to the relevant ET 200L electronics. The functions described under ET 200 communication interfaces should not be attributed to this wiring accessory.

After replacement, check connection matching and conductor retention before carrying out appropriate electrical checks. Continuity measurements require an isolated circuit; connected electronics can affect the readings. Once the supply is restored, check voltage distribution and field states under controlled conditions. Compare the channel state shown in the engineering software with the actual machine condition, and prevent unexpected movement during output testing.

Interpreting faults without replacing the wrong part

An intermittent fault at one connection calls for inspection of the conductor, spring contact, cable end and any local damage. If several devices in the same group fail together, investigate their common supply and return path as well. When the whole station is missing from the network, broaden the investigation to station power and communication. None of these symptoms, on its own, identifies the supplementary terminal as the failed component.

Discolouration, melting, cracks or poor conductor retention require more than simply reinserting the wire. Find the cause of the damage before fitting a replacement, otherwise the new part may suffer the same fault. For used equipment, examine the complete order number, terminal openings, retaining features and the condition stated in the listing. Availability, testing and supplied components must be checked against the particular sales item.

Manuals, catalogue and related information

Use the Siemens ET 200 user manuals page to locate documentation. The existing Siemens IK PI 2007 ET 200 catalogue lists this accessory on page 5/214; the link targets PDF page 214. It is a general catalogue, not a dedicated manual for this part. For the terminal arrangement, consult section 7.6, pages 7-18 and 7-19, of the ET 200L system manual.

For wider context, see About ET 200, browse the ET 200 product range or visit the Siemens automation section. Send product enquiries through OtomasyonAVM’s Siemens contact page. Field observations can be shared in accordance with the community rules; information about the site is available under About OtomasyonAVM.

Navigation

ET 200 terminal blocks · ET 200 products · ET 200 manuals · About ET 200 · Siemens automation · Siemens product enquiries

Technical sources