6ES7 193-1FL30-0XA0
Siemens 6ES7 193-1FL30-0XA0 — ET 200L two-row screw-type supplementary terminal
6ES7 193-1FL30-0XA0 is a Siemens two-row supplementary terminal with screw connections for the 32-channel ET 200L arrangement. It provides additional field-wiring connections beside the station within the SIMATIC ET 200 family. The Siemens product data sheet gives an approximate weight of 266 g.
This is a wiring accessory. It does not run a PLC program, evaluate an input signal or switch an output load. Check it together with the main terminal block; the supplementary terminal on its own is not a complete ET 200L station.
Where it fits and how the rows are connected
The accessory belongs to the TB 32L arrangement. Siemens describes the supplementary-terminal range as a way to extend two-wire station connections to three- or four-wire connections. The terminals within each row are internally linked. They must therefore not be treated as separate, electrically isolated signal terminals.
For maintenance, that distinction matters more than the number of visible screws. Conductors intended to share a common potential can be brought together in an orderly way; independent sensor outputs cannot simply be grouped on a linked row. Keep the functions of M / 0 V and protective earth PE distinct. Follow the station diagram and the markings on the assembly when assigning connections. The grounding arrangement cannot be established from wire colour or appearance alone.
The 32-channel description does not mean that fitting this accessory creates 32 additional electronic I/O channels. Signal acquisition belongs to the digital input electronics, and load switching belongs to the digital output electronics. The ET 200 system overview explains how wiring components, electronics and communication fit together.
Check the circuit before choosing the wiring accessory
An inductive sensor or photoelectric sensor must match the supply and electrical input requirements of the installed electronics. This terminal does not convert PNP/NPN or sinking/sourcing signals. A wire fitting into a terminal is only a mechanical observation; it does not establish electrical compatibility.
When using sensor cables and connectors, trace the connector pin assignment through to the numbered cabinet terminal. Label both ends before removing existing wiring, especially where earlier repairs may have changed the original colour convention. A clear record of the old installation makes the replacement easier to verify.
The power supply must suit the circuit voltage and total load. On an output circuit, also check the electronic channel rating, protection and the load itself. An interposing relay or contactor coil may need suitable suppression according to the component instructions. Additional termination points do not increase an output channel’s current rating.
Installing and checking screw connections
Place the machine in a safe condition, isolate the relevant supplies and verify that the circuit is de-energized before rewiring. Compare the complete part number, mounting arrangement, number of rows and existing wire routing. For a screw-terminal connection, conductor construction, cross-section, end preparation and tightening torque all matter. Use the applicable ET 200L wiring instructions; a torque value for a different Siemens terminal is not a substitute.
Make sure the clamp captures the conductor rather than its insulation. Do not leave excessive bare wire exposed, and keep stray strands away from adjacent connections. If ferrules are used, their size, length and crimp must match the terminal’s approved conductor preparation. A screw that binds or turns without clamping needs inspection, not additional force.
Before recommissioning, check the DIN-rail power supply, circuit fuses, common return paths and field connections as a complete circuit. Electrical measurements and functional checks should be carried out by qualified personnel with suitable equipment while preserving the machine’s safe state. Support the wiring so that cable tension is not carried by the terminal connection.
Separating a connection fault from an electronics fault
For an intermittent sensor signal, identify where the signal is lost before replacing the electronic block. Compare the sensor indication, its local supply, the cable termination and the input status. Several devices failing together can point towards a common supply or return problem, but that pattern alone is not a diagnosis.
If the controller does not receive a changing input, investigate the local electrical path separately from PROFIBUS communication and address mapping. Treating every lost signal as a network failure can lead to unnecessary replacements. Discolouration, damaged threads, corrosion or melted insulation at a terminal deserve closer examination. Tightening a screw does not resolve the cause of heat damage.
Similar order numbers describe different versions
6ES7193-1FL20-0XA0 is listed as a single-row, 32-channel screw version; 6ES7193-1FL60-0XA0 as a two-row, 32-channel spring-terminal version; and 6ES7193-1FH30-0XA0 as a two-row, 16-channel screw version. These references identify differences in the range. They are not a list of approved drop-in replacements.
ET 200L, ET 200S and ET 200SP use different component arrangements. Select connection components and additional accessories by the full part number and the installed system. A power distribution component from another range should not be substituted on the basis of a similar appearance or description.
What to check when buying a used part
Confirm the scope of the listing. A supplementary terminal, main terminal block and electronic block may be offered separately. Photographs should show the screws, connection openings, housing and mounting features. A statement that an item was working when removed is different from a documented inspection or test. Refer to the individual seller’s description for the condition and components included.
Editor’s advice
Start with the 6ES7193-1FL30-0XA0 marking and the existing connection arrangement. Photograph the assembly before removal, label the wires and compare the common connections with the drawing. Where the replacement follows a poor contact or overheated terminal, investigate the cause as well as the damaged part. Cable strain, unsuitable conductor preparation or excessive loading can damage the replacement too.
Technical references and user manuals
The identification and weight were checked against the Siemens product data sheet. The supplementary-terminal arrangement and related order numbers were checked in sections 7.3 and A.1 of the ET 200L Distributed I/O Device manual. Use the Siemens ET 200 PDF and user manuals page to locate documentation for the installed ET 200L assembly. A general ET 200 family brochure does not replace its terminal and wiring drawings.
Related topics
ET 200 terminal blocks / ET 200 connection components / Screw and spring terminal connections / Sinking and sourcing / Grounding