6ES7 193-0CB40-0XA0
Siemens 6ES7 193-0CB40-0XA0 ET 200B TB4-4/DC Terminal Block
Siemens 6ES7 193-0CB40-0XA0 is the TB4-4/DC terminal block for the ET 200B series within the SIMATIC ET 200 family. Designed for digital electronics blocks, it features four-tier spring terminals and a width of 235 mm. When selecting a replacement, compare the complete terminal block number, the fitted electronics block and the existing wiring diagram.
The terminal block's role in an ET 200B station
The terminal block carries the permanent field wiring, while the electronics block fitted above it provides the input and output functions. This arrangement allows field cables to remain connected when the electronics block is replaced. Selecting the correct terminal block therefore requires more than matching the appearance of the housing.
For background on the control system, see how a PLC works, digital input modules and digital output modules. Channel count and output current should not be inferred from the terminal block number alone.
Four-tier wiring and protective earth
Four tiers describe the terminal arrangement, rather than four I/O channels. The tiers accommodate signals, supply connections, reference potential and protective earth, with the fourth row providing channel-by-channel PE connections. Use the wiring diagram for the installed electronics block to identify each terminal.
A PE terminal row does not mean the protective-earth connection is already complete. The TB2-4/DC pin assignments, which also apply to this model, identify the internally linked PE terminals as separate from the base's PE screw. Verify the required PE connection and continuity against the applicable wiring diagram.
Compatible electronics blocks
Siemens lists ET 200B-16DO/2A, ET 200B-32DI, ET 200B-32DI 0.2 ms, ET 200B-32DO, ET 200B-16DI/16DO, ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms as compatible electronics blocks. The main manual's TB2-4/DC pin assignments are used for the TB4-4/DC.
Record both component labels when identifying an existing station. Compatibility with the base does not mean that different electronics blocks can be exchanged while keeping every field connection unchanged. Pay particular attention to stations combining inputs and outputs, and compare the wiring diagram before selecting a replacement.
PROFIBUS connection and station address
The base includes the PROFIBUS-DP connection, station address selector, STOP/RUN switch and fuse. The active PROFIBUS interface electronics are located in the electronics block. A changed station address is accepted during a STOP-to-RUN transition.
When reviewing communications, distinguish between PROFIBUS and PROFINET. This ET 200B arrangement uses PROFIBUS-DP. A migration to PROFINET requires a separate system assessment. The ET 200 connection components category provides a starting point for exploring related connection hardware.
Plan address changes within a controlled machine shutdown. The STOP position does not confirm that all field and load terminals are de-energized. Isolate the relevant supplies and verify absence of voltage before wiring work or component replacement.
Supply and operating conditions
The Siemens data sheet specifies a 24 V DC nominal supply, an allowable range of 18.5–30 V DC including ripple, and IP20 protection. Its 100–200 mA internal logic consumption figure must not be treated as a field-load rating or a per-channel output capacity.
The ET 200B catalogue specifies 0 to +60 °C for horizontal installation on a vertical mounting surface and 0 to +40 °C for other mounting positions. Include orientation when assessing the cabinet layout.
Evaluate electronics, sensor and output-load requirements separately when reviewing the supply arrangement. Related power supply modules and power distribution modules can be explored through their categories; suitability for the actual station must be checked separately.
Checking field sensor connections
A sensor's physical connection is only one part of the selection process. Compare its output type and supply requirements with the input characteristics of the fitted electronics block. The explanations of sink and source wiring and two-wire sensors provide useful background.
For proximity detection applications, review how inductive sensors work before comparing inductive sensor options against the application's electrical and mechanical requirements.
Similar part numbers and replacement checks
6ES7 193-0CB30-0XA0 identifies the TB4/DC with three-tier spring terminals. 6ES7 193-0CB40-0XA0 identifies the four-tier TB4-4/DC. The four-tier screw-terminal version is designated TB2-4/DC. These distinctions matter when comparing PE provision and the existing cable arrangement.
Clear photographs of both product labels, the recorded station address and the wiring diagram make a replacement enquiry easier to assess. Include inspection of the terminal housing, spring connections, electronics-block contacts and retaining features in the maintenance work.
PDF manuals and technical documentation
Visit the Siemens ET 200 manuals page to explore the documentation. For this model, consult the ET 200B Distributed I/O Station manual together with the TB4-4/DC product information supplement. The Siemens ET 200 overview introduces the wider product family.
Related topics
For the controller side of the installation, explore Siemens S7 PLCs and SIMATIC S7-300. Record the exact CPU or communications-module number when assessing the existing system.
Editor's note: Keep the base label, electronics-block label and wiring diagram together when identifying this assembly. Recording the PE arrangement and station address alongside those details makes subsequent maintenance easier to plan and verify.