6ES7 193-0CA20-0XA0

Siemens 6ES7 193-0CA20-0XA0 ET 200B TB1-4/DC Terminal Block

Siemens 6ES7 193-0CA20-0XA0 is the TB1-4/DC terminal block for the ET 200B series within the SIMATIC ET 200 family. It accommodates digital electronics blocks and features four-tier screw terminals in a 160 mm-wide base. For an existing installation, identify both the terminal block and the electronics block before selecting a replacement.

Its role in the ET 200B station

The terminal block holds the field wiring, while the fitted electronics block provides the input and output functions. This arrangement allows the field cables to remain connected when the electronics block is replaced. Both the mechanical design and the wiring layout matter when comparing ET 200 terminal blocks.

During fault investigation, consider the PLC, field cable, terminal connection and electronics block separately. A missing sensor signal calls for checking the relevant digital input characteristics. A load that fails to operate requires a review of the digital output rating and its field circuit.

Four terminal tiers and the PE connection

Four tiers describe the terminal rows, rather than four I/O channels. The TB1-4/DC belongs to the 16-channel terminal-block group; the actual input and output arrangement depends on the electronics block. The fourth row provides PE terminals.

The PE terminals are linked internally to one another but are not internally connected to the base's PE screw. Verify the connection to protective earth and its continuity against the wiring diagram. Keep the roles of the M reference and protective earth distinct when documenting or transferring the wiring.

Compatible electronics blocks

The listed electronics blocks are ET 200B-16DI, ET 200B-16DO, ET 200B-8DI/8DO, ET 200B-8DI/8DO HWA and ET 200B-8RO. The base can therefore serve several I/O arrangements within its supported group.

Distinguish the ET 200B-16DO from the ET 200B-16DO/2A, which uses the wider terminal-block group. Their similar names do not establish base compatibility. Include the full electronics-block order number in a replacement enquiry to avoid matching parts by channel count alone.

Supply and operating conditions

Siemens specifies a 24 V DC nominal supply, an allowable range of 18.5–30 V DC including ripple, and IP20 protection. The stated 100–170 mA internal logic consumption must not be interpreted as a field-load allowance or an output-channel rating.

ET 200B catalogue conditions specify 0 to +60 °C for horizontal mounting on a vertical surface and 0 to +40 °C for other orientations. Allow practical access to connectors, cable routes and the removable electronics block when planning the cabinet layout.

Review power supply modules and power distribution modules according to their respective functions. Calculate the requirements of the electronics, sensors and output loads separately when assessing the supply arrangement.

Screw terminals and conductor sizes

For TB1-4 supply and signal connections, the Siemens manual specifies 0.14–2.5 mm² without ferrules and a maximum of 1.5 mm² with ferrules. These limits concern supply and signal terminals; protective-earth connections have their own requirements.

When inspecting a base removed from an older cabinet, examine the screw heads, conductor-clamping parts and plastic housing. Damaged ferrules, broken strands or worn terminals can remain a source of trouble after an electronics block has been replaced. Prepare and secure conductors according to the applicable connection instructions.

PROFIBUS connection and station addressing

The base carries the PROFIBUS-DP connection, station address selector, STOP/RUN switch and fuse. A newly selected address becomes effective following a STOP-to-RUN transition. Plan address changes as part of a controlled shutdown and recommissioning procedure.

The explanations of PROFIBUS communication and the available connection components provide related background. An upgrade to PROFINET requires a separate assessment of the controller, network and field wiring.

STOP does not establish that every load terminal is de-energized. Isolate the relevant energy sources and verify absence of voltage before wiring work or component replacement.

Checking sensor connections

Compare a sensor's output type and supply requirements with the characteristics of the fitted input electronics. The guides to sink and source wiring and two-wire sensors can help with this review.

For metal detection applications, explore how inductive sensors work before comparing inductive sensor models. Matching the housing or number of wires is only part of the selection; electrical compatibility also needs checking.

Distinguishing similar terminal blocks

6ES7 193-0CA10-0XA0 identifies the three-tier screw-terminal TB1/DC. 6ES7 193-0CA20-0XA0 identifies the four-tier screw-terminal TB1-4/DC described here. 6ES7 193-0CA40-0XA0 is the four-tier spring-terminal TB3-4/DC.

When considering a change between screw and spring connections, review the existing conductor ends, cable lengths and access to each terminal. Support for the same electronics-block group does not eliminate the need to check the field wiring before transferring it.

PDF manuals and wiring documentation

Visit the Siemens ET 200 manuals page for documentation. Section 7.2.2 of the ET 200B Distributed I/O Station manual covers the TB1-4/DC base. Use the installed electronics block's diagram for terminal assignments. The Siemens ET 200 overview introduces the wider system family.

Related topics

For the controller side, explore Siemens S7 PLCs and SIMATIC S7-300. Keeping the base number, electronics-block number, station address and wiring diagram together makes later maintenance enquiries easier to resolve.

Editor's note: Two details deserve particular attention on this model: the 160 mm base group and the fourth-row PE connections. Compare the complete order number and electronics-block label instead of selecting a replacement from “ET 200B” or “16 channels” alone.

Explore more: Siemens products | SIMATIC S7 | SIMATIC ET 200