6ES7 195-7HC00-0XA0

6ES7 195-7HC00-0XA0 Siemens ET 200M BM 1×80 Active Bus Module

6ES7 195-7HC00-0XA0 is a BM 1×80 active backplane bus module designed to accommodate one 80 mm wide S7-300 I/O module in a Siemens SIMATIC DP ET 200M distributed I/O station. It is not an analog or digital input/output module. Its purpose is to provide the mechanical mounting position and active backplane connection for a compatible signal, function or communication module.

When installed with the correct rail, interface module and hardware configuration, the active bus architecture forms part of the ET 200M “Module Change During Operation” system. This arrangement can permit a compatible I/O module to be removed and reinserted without unnecessarily shutting down the complete remote I/O station.

Product Description and Function

Product type: Active ET 200M backplane bus module
Siemens designation: BM 1×80
Article number: 6ES7 195-7HC00-0XA0
Compatible system family: SIMATIC DP ET 200M
Module capacity: One 80 mm wide S7-300 I/O module
Main function: Connecting the installed module to the active ET 200M backplane bus
Maintenance function: Supports module replacement during operation in a correctly designed station
Product status: Identified as a spare part in the Siemens technical data sheet

This component does not acquire field signals or generate output signals itself. It may instead form the mounting and backplane connection for a suitable ET 200 analog input module, ET 200 digital output module or ET 200 function module with the required 80 mm mechanical width.

Technical and Mechanical Data

Overall width: Approximately 97 mm
Installed width: 80 mm
Height: Approximately 92 mm
Depth: Approximately 30 mm
Approximate weight: 127 g
Supported module width: 1 × 80 mm
Mounting arrangement: On the dedicated rail for ET 200M active bus modules
Product class: PLC/distributed I/O mounting and backplane connection accessory

The specified 97 mm overall width and 80 mm installed width describe different mechanical values. Product selection should therefore be based on the Siemens width classification of the module being installed rather than a rough measurement of its external housing.

Selection and Compatibility Checks

The 6ES7 195-7HC00-0XA0 is intended for one 80 mm wide module. If the station uses one or two 40 mm modules, the appropriate BM 2×40 version should be evaluated instead. ET 200M bus modules may look similar while having different slot arrangements and functions, so ordering only by the description “ET 200M bus module” is not sufficient.

Before purchasing, compare the full article number of the IM 153 interface module, the MLFB number and mechanical width of the I/O module, the installed rail, the left-hand starting bus module, the redundant or non-redundant station architecture and the engineering configuration used for module replacement during operation.

For the station communication architecture, review ET 200 PROFIBUS and PROFINET solutions, ET 200 connection modules and other ET 200 network interfaces together with the IM 153 documentation.

Installation and Commissioning Guidance

Disconnect the station power: Active bus modules must be installed on the rail while de-energized. Module replacement during operation applies to the compatible I/O module carried by the bus module; it does not mean that the bus module itself can be removed while energized.

Use the dedicated rail: Active ET 200M bus modules require the Siemens 6ES7 195-1Gxx0-0XA0 family of rails intended for the module-change-during-operation arrangement. A mechanically similar standard S7-300 rail should not be assumed to be suitable.

Complete the bus module chain: Assemble the starting bus module, IM 153 arrangement, BM 1×80 modules and any other active bus modules in the sequence required by the project. Fit backplane bus covers to unused positions and install the appropriate bus module cover at the end of the chain.

Verify the engineering configuration: If modules will be replaced while the station is running, the function must also be correctly enabled in STEP 7 or the applicable engineering environment. Installing active bus hardware alone does not automatically enable hot swapping.

When an output module is inserted during operation, outputs commanded by the user program may become active immediately. Outputs should therefore be brought to a safe state, the machine risk assessment followed and field power controlled by qualified personnel.

Maintenance and Pre-owned Product Inspection

When inspecting a used BM 1×80, check the rail latches, side coupling locks, backplane contacts, module guides and plastic housing for cracks or deformation. Bent or oxidized contacts can cause intermittent communication with adjacent active bus modules and may produce station diagnostic faults.

The ET 200M station must be de-energized before replacing the bus module itself. Depending on its position, the module mounted on it and adjacent components may need to be removed in the prescribed sequence. Photographing the original slot order and article numbers before disassembly helps prevent incorrect reinstallation.

Editor’s note: A common selection error is treating 6ES7 195-7HC00-0XA0 as a universal base for every ET 200M module. This model accommodates one 80 mm module. Confirm the full article number and mechanical width of the intended S7-300 module, then verify the active rail and IM 153 architecture. The hot-swap description must not be interpreted as permission to replace the bus module itself while energized.

Manufacturer PDF Documents

+ Siemens 6ES7 195-7HC00-0XA0 technical data sheet (English PDF generated by Siemens)
+ Siemens SIMATIC ET 200M operating instructions (English PDF covering active bus installation, commissioning, diagnostics and maintenance)
+ Otomasyon AVM Siemens ET 200 PDF manual archive

Related Topics and System Components

When reviewing the complete station, also check the ET 200 terminal blocks, ET 200 power supply modules, ET 200 power distribution modules and additional ET 200 modules and accessories.

Application-specific information is also available for ET 200 special output modules, ET 200 functional safety modules and Siemens ET 200 PROFIsafe systems.

For broader reference material, visit the analog input and output guide, pre-owned industrial automation products and the Otomasyon AVM English automation resource centre.

Reminder: Siemens 6ES7 195-7HC00-0XA0 and other SIMATIC components may be offered by Otomasyon AVM subject to stock availability. Some units may be used, open-box or discontinued spare parts. Check the product label, mechanical condition, hardware version and system compatibility before ordering. Restocking cannot be guaranteed after obsolete inventory has been sold.

Technical notice: This page is intended to support preliminary product identification and does not replace project engineering. Installation, commissioning, maintenance and module replacement must follow the current Siemens documentation and the electrical and machinery-safety requirements of the installation. Content reviewed: 30 October 2026.