Delta DVP48EH00T

Delta DVP48EH00T – DVP-EH PLC with 24 inputs and 24 transistor outputs

The Delta DVP48EH00T is a first-generation Delta DVP-EH PLC CPU with a 100–240 V AC supply, 24 digital inputs at 24 V DC (X0–X27) and 24 NPN open-collector transistor outputs (Y0–Y27). Input and output addresses use octal numbering. Delta lists 16K program steps for first-generation EH. The controller suits conveyors, assembly machines and packaging equipment with multiple sensors and DC control outputs.

Inputs, output loads and pulse limits

Check the AC supply and the 24 V DC field inputs separately. Match the S/S common to the PNP or NPN sensor and follow Delta’s diagram for the required sink/source arrangement. An inductive sensor can detect a part, a photoelectric sensor can detect passing products and a limit switch can report end-of-travel. Match the NO/NC contact action to the input condition in the program.

The transistor outputs sink DC load current. Delta’s first-generation EH sheet lists 0.3 A per point at 40 °C for standard transistor outputs. Account for coil inrush and suppression. Choose a suitable interposing relay where needed and check fusing and panel grounding.

Delta’s application manual lists the 48-point first-generation EH transistor outputs in the standard 10 kHz output class. For a stepper motor or servo drive, check the supported pulse channel and instruction in the manual. For encoder feedback, check the input voltage, A/B phases and the selected counter mode’s frequency limit.

Programming software and cable

Use Delta WPLSoft or a version of Delta ISPSoft that supports the first-generation EH target. When programming the PLC, select EH. Keep the original ladder diagram project and CPU firmware details. For ISPSoft, start the serial channel in COMMGR and select that channel in ISPSoft.

Connect the PC to COM1 RS-232 using a DVPACAB2A30 cable. The PLC end is 8-pin mini-DIN and the PC end is 9-pin D-sub. On a USB-equipped PC, install the driver for a suitable USB-to-RS-232 adapter and select the assigned COM number. See Delta PLC programming cables.

RS-485 and related Delta models

COM2 is the RS-485 field port. On a Modbus RS-485 link, match the station address, baud rate, serial framing and device roles. Check the existing project for Modbus RTU or ASCII. See the RS-232, RS-422 and RS-485 comparison and industrial communication guide for interface selection.

The DVP48EH00R has the same 24 inputs and 24 outputs, with relays. The DVP48EH00T2 and DVP48EH00T3 belong to the EH2 and EH3 generations respectively. Before changing generations, compare pulse points, instructions, terminal layouts and the exact part numbers of Delta DVP-EH expansion modules.

Editor’s Note

Ask for a close-up of the nameplate when buying used. Check that the photo shows the complete DVP48EH00T code and terminals. Look for heat marks or loose screws around the output commons.

Back up the PLC before battery work. If BAT.LOW is active, save the program and required retained data first. Keep the original project and port settings as well.

Check the output under load. With machine loads disconnected, use a suitable DC test load to check the Y terminals and their commons. See the electrical measurement and test guide.

Measure the waveform in pulse applications. Safely prevent machine movement and verify pulse and direction signals at the drive input at operating frequency.

Test both serial ports separately. Read the program through COM1 and check data exchange with a field device through COM2.