Delta DVP32EH00T2

Delta DVP32EH00T2 – EH2 PLC with 16 inputs and 16 NPN outputs

The Delta DVP32EH00T2 is a Delta DVP-EH2 PLC CPU with a 100–240 V AC supply, 16 digital inputs at 24 V DC (X0–X17) and 16 NPN open-collector transistor outputs (Y0–Y17). Input and output addresses use octal numbering. Delta lists 16K program steps and 10K words of data registers for EH2.

Inputs and two-axis pulse output

Check the AC supply to the CPU and the 24 V DC field input circuit separately. Match the S/S common to the PNP or NPN sensor circuit and follow Delta’s diagram for the required sink/source arrangement. An inductive sensor can detect a part, a photoelectric sensor can detect passing products and a limit switch can report end-of-travel. Match NO/NC contact action to the program condition.

Y0 and Y2 are the high-speed pulse points. Delta lists two axes at up to 200 kHz per axis and one group of linear or circular interpolation. For a stepper motor or servo drive, check the input circuit, pulse/direction format and electronic gearing. Encoder feedback uses the input circuit. Delta’s sheet lists 200 kHz input bandwidth for X0, X1, X4 and X5. Check the limit for the selected counter mode.

The transistor outputs sink DC load current. Delta lists 0.5 A per point and 4 A per common for resistive loads. Account for coil inrush and suppression. Use a suitable interposing relay where required. Check output-circuit fusing and panel grounding.

Programming software and cable

Program the CPU with Delta WPLSoft or Delta ISPSoft. When programming the PLC, select the EH2 CPU target. Keep the existing ladder diagram project and CPU firmware details. For ISPSoft, start the serial channel in COMMGR and select that channel in ISPSoft.

Connect the PC to the 8-pin mini-DIN COM1 RS-232 port with a DVPACAB215 (1.5 m) or DVPACAB230 (3 m). On a USB-equipped PC, install the driver for a suitable USB-to-RS-232 adapter and select the assigned COM number. See Delta PLC programming cables.

Communication and related Delta models

COM2 is the RS-485 field port. On a Modbus RS-485 link, match station addresses, baud rate, serial framing and device roles. Check whether the project uses Modbus RTU or ASCII. The RS-232, RS-422 and RS-485 comparison and industrial communication guide cover interface selection.

The DVP32EH00R2 has the same 16 inputs and 16 outputs, with relays. The DVP32EH00M2 provides two differential pulse channels. The DVP40EH00T2 has 24 inputs and 16 transistor outputs. Check Delta DVP-EH expansion on the right side of the standard T2 and the left-side module support of the T2-L before installation.

Editor’s Note

Ask for a photo of the full nameplate. Identify T2, M2 and T2-L by the complete code. Inspect the terminals, output commons and serial socket.

Back up the machine before removing the CPU. Save the program, retained data, serial settings and the drive’s pulse and gearing parameters. If BAT.LOW is active, verify the backup before battery work.

Test Y0 and Y2 separately. Prevent machine movement safely. Verify pulse and direction signals at the drive input at low speed and then at the operating frequency.

Check the output under a suitable test load. Verify switching, load supply and the common terminal. See the electrical measurement and test guide.

Check both serial ports. Read the program through COM1 and verify data exchange with a field device through COM2.

Internal references and PDF files

Delta DVP PLC PDF files · OtomasyonAVM DVP-EH2 wiring guide (English PDF) · Delta DVP-EH2 · Delta DVP PLC series

External references

Delta DVP-EH2 instruction sheet (2014) · Delta DVP catalogue · Delta DVP Application Manual · Delta ISPSoft User Manual