Delta DVP32EH00R2
Delta DVP32EH00R2 PLC | 16 Inputs, 16 Relay Outputs
The Delta DVP32EH00R2 is a 100–240 V AC PLC CPU in the DVP-EH2 series. It has 16 digital inputs at 24 V DC and 16 relay outputs. On a conveyor, filling station or packaging machine, it can read inductive sensors and photoelectric sensors and control valves, interposing relays or contactors through suitable load circuits.
Digital I/O and relay wiring
The built-in PLC inputs and outputs use octal addresses. Inputs run from X0–X17 and outputs from Y0–Y17. Check the S/S common and sink/source wiring for the PNP or NPN sensors in use. Delta’s EH2 catalogue lists 16,000 program steps and 10,000 data-register words.
Delta’s instruction sheet rates the relay contacts at 2 A per point and 5 A per common for resistive loads. Check current and contact-life limits separately for inductive loads such as coils. Use the model’s terminal diagram to check the load supply, common groups and fuse. For pressure or level measurement, select an analog input module that matches the signal.
Encoder counting and pulse output
Delta’s EH2 sheet lists X0/X1 and X4/X5 as 200 kHz input pairs and X10/X11 and X14/X15 as 20 kHz pairs. When connecting an incremental encoder, check the frequency limit and signal levels for the selected A/B counting mode.
The R2’s 200 kHz rating applies to its high-speed counter inputs. Its Y terminals use relay contacts for load switching. For high-speed pulse output, the DVP32EH00T2 has the same I/O count and provides up to 200 kHz at Y0 and Y2. Check the drive’s input type and frequency limit before selecting the CPU.
Programming software and cable
Use WPLSoft to read the existing Ladder program from the PLC to the PC and save a backup. If you use ISPSoft, check that your installed release offers the EH2 target and start the serial connection in COMMGR. For the programming connection, select the assigned Windows COM port and match the PLC’s serial settings.
Connect the PC to COM1 RS-232 with the DVPACAB2A30 cable. If the PC has no DB9 port, use a compatible USB-to-RS-232 adapter and driver at the PC end. See Delta PLC cables for other connection options.
COM2 RS-485 handles industrial communications. For Modbus RTU, match the station address, baud rate, parity and stop bits at both ends. Before a CPU swap, record the existing serial settings and the part number of any installed option card.
Related Delta models
DVP32EH00M2 is an EH2 model with differential pulse outputs. DVP64EH00R2 provides 32 inputs and 32 relay outputs. DVP32EH00R3 provides 16 inputs and 16 relay outputs in the EH3 family. Before moving to EH3, compare program instructions, special registers, terminal layouts and existing expansion cards.
Editor’s Note
When buying used, ask for clear photos of the side label and terminals. Read the final suffix to identify the output type and generation.
Back up the program and required data through COM1. If BAT.LOW is on, follow Delta’s battery procedure.
You may hear the relay click when a Y indicator lights. With machine motion disabled, check that the contact switches a suitable test load.
If a load stays on after the output turns off, check separately for a welded contact and an external feed.
If counting becomes erratic when a variable-frequency drive starts, check the encoder cable route, electromagnetic interference and cabinet grounding.
Related topics, internal references and PDF files
Delta DVP PLC files · OtomasyonAVM Delta EH2 wiring and operation sheet (EN PDF) · Delta DVP-EH2 · Delta DVP-EH3
External references
Delta EH2 instruction sheet (2014, multilingual PDF) · Delta DVP-PLC programming manual (EN PDF) · Delta DVP catalogue, EH2 model table (EN PDF)