Delta DVP16EC00R3
Delta DVP16EC00R3 | PLC with 8 inputs and 8 relay outputs
The Delta DVP16EC00R3 is a 100–240 V AC main unit in the DVP-EC3 series. It has 8 built-in digital inputs rated at 24 V DC and 8 relay outputs. The PLC reads sensor and pushbutton signals. The CPU runs the sequence and switches field loads through its relay outputs.
Digital inputs and high-speed counting
The built-in PLC inputs and outputs use addresses X0–X7 and Y0–Y7. When connecting an inductive sensor, identify its PNP or NPN output. Check the S/S terminal in Delta’s sink/source wiring diagram.
Delta’s electrical table lists maximum input frequencies of 20 kHz for X0 and X1, and 10 kHz for X2–X7. For high-speed counting, check the applicable limit for the selected count mode and input filter. When connecting an incremental encoder, check its signal level. An encoder with differential line-driver outputs needs a suitable electrical interface.
Relay outputs and panel wiring
C0 is common to Y0–Y3, and C1 is common to Y4–Y7. The relay contacts switch externally powered loads. Delta specifies 2 A per output and 5 A total per common for resistive loads. Check the required fuse protection and use a suitable suppression diode where appropriate for a DC coil.
Check the DIN rail layout and protective grounding during installation. When the application needs high-speed pulse outputs, consider the DVP16EC00T3. Delta lists up to 10 kHz on Y0 and Y1 for T3 hardware V8.00 and later. If the project requires analog inputs or local expansion, consider an expandable CPU such as the DVP16ES200R.
Programming software and cables
Use WPLSoft to read and back up the existing ladder program. Earlier EC3 units are in the 4K class. Delta’s programming manual identifies the 8K variant with firmware V8.60 and later as EC3-8K. In ISPSoft, select the matching CPU target and configure the serial connection in COMMGR. Verify firmware and instruction support before writing the program to the PLC.
For COM1 (RS-232), use UC-PRG020-12A with a USB-equipped PC or UC-MS020-01A with a native serial port. Install the USB cable driver and select the COM port assigned by Windows. For Modbus over this model’s COM2 (RS-485), match the station address, baud rate and serial frame settings. Delta PLC cable options
Related Delta models
The DVP16EC00T3 has the same I/O count with transistor outputs. The DVP14EC00R3 has 8 inputs and 6 relay outputs. The DVP20EC00R3 has 12 inputs and 8 relay outputs, and the DVP32EC00R3 has 16 inputs and 16 relay outputs. Compare the terminal layout, serial ports in use and project when changing models.
Editor’s note
When buying used, ask for a nameplate photo and the CPU version read online.
Back up the program and Modbus settings before removal. Record the serial ports in use.
If a whole group of outputs fails, check the C0 or C1 common supply for that group first.
If a relay clicks but the load stays off, test the contact under a suitable load.
If encoder counts are erratic, check the input pair, signal level and input filter together.