Delta DVP02TKN-S

Delta DVP02TKN-S 2-Channel PID Temperature Control Module

The Delta DVP02TKN-S is a temperature controller with two universal measurement inputs and four NPN transistor outputs. It monitors two heating points, such as sealing jaws, moulds or oven zones, and runs PID control on the module. Measured values and setpoints can be shared with a PLC or HMI over RS-485.

Sensor inputs and NPN outputs

CH1 and CH2 are configured separately. Inputs include Pt100, JPt100 and Pt1000 RTDs, J and type K thermocouples, and 0–5 V, 0–10 V, 0–20 mA and 4–20 mA signals. For example, the Pt100 mode covers −200 to +600 °C and the type K mode covers −200 to +1300 °C. See the Pt100 and thermocouple comparison for sensor selection, and check the analog input type if you use a transmitter.

Supply is 24 V DC (20.4–28.8 V DC). OUT1–OUT4 are open-collector NPN sinking outputs. C0 is common to OUT1 and OUT2, and C1 is common to OUT3 and OUT4. The resistive load ratings are 12–30 V DC, 0.3 A per output and 0.6 A per common. Use an appropriately rated solid-state relay with a compatible DC control input or a suitable contactor circuit with an interposing relay for the heater power circuit.

Configuration software and cable

Use TKSoft (TK Wizard) to configure the module over RS-485. Set up the PC connection in COMMGR. A USB–RS-485 converter such as the Delta IFD6500 connects a PC via USB. On the Modbus RS-485 link, use the module’s station address as the target. Match the baud rate, frame settings and ASCII or RTU mode at both ends.

Use WPLSoft or ISPSoft, according to CPU support, to program the PLC. For the COM1 RS-232 port of a DVP-SS2 CPU, examples of PLC programming cables are the UC-PRG020-12A (USB) or UC-MS020-01A (RS-232). Use the RS-485 connection above to configure the DVP02TKN-S.

For PLC/HMI reads, CR#2 holds the CH1 measured value and CR#3 holds the CH2 value. CR#4 and CR#5 hold the corresponding setpoints. In °C temperature mode, 253 represents 25.3 °C. Check the HMI driver's address format and decimal settings when building the display.

To understand the PID feedback, first observe how the sensor reading and output direction respond in the field. The PID temperature control guide covers loop behaviour, and PLC-based PID control explains how a loop runs on a CPU.

Editor’s Note

Check the label. For a used unit, ask for a photo of the DVP02TKN-S label and C0/C1 terminals. The TKR relay version uses different output wiring.

Test the inputs one at a time. Read both channels separately at a known temperature. For a thermocouple, check polarity and the type of extension wire.

Track down interference. Route sensor cables away from motor and heater wiring. If the readings jump, start with electromagnetic interference and grounding checks.

Test the output first. With the heater power circuit disabled, verify the output assignment and confirm that the NPN output switches the connected interface device.

Back up the settings. Before replacement, record the sensor types, setpoints, PID settings, output assignments and serial communication settings.