Delta DVP06SN11R
Delta DVP06SN11R – 6 Relay Output DVP Slim Expansion Module
Delta DVP06SN11R is a DVP Slim expansion module that adds 0 inputs and 6 relay outputs to the right side of a compatible PLC CPU. Each output has its own C common. This makes it straightforward to switch separate field circuits through the relay contacts.
Power supply and contact ratings
The 24 V DC CPU expansion bus powers the module. The external load circuit supplies the voltage switched by the dry contacts. The selection table in Delta’s 2026 manual lists a 250 V AC upper limit. The model’s wiring diagram specifies 10–240 V AC or 5–30 V DC. This page follows the wiring diagram’s 240 V AC upper limit.
The resistive load limit is 6 A per output and 6 A at that output’s C terminal. Account for the approximate 10 ms relay response and 1 Hz switching limit in the machine’s cycle time. Isolate power before fitting the module to a DIN rail and mating the expansion connector.
C0–C5 and Y0–Y5 terminals
The pairs are C0–Y0, C1–Y1, C2–Y2, C3–Y3, C4–Y4 and C5–Y5. Each relay closes the normally open contact between its own C and Y terminals when energised. Route each load circuit through the corresponding C/Y pair. Size the field supply, conductors and fuse for the load and wiring.
For a contactor coil or solenoid valve, consider inrush and the turn-off voltage spike alongside steady-state current. Delta’s load curves on printed page 7-26 show how load type affects contact life. Use an appropriately oriented diode for a DC coil or a suitable RC suppressor or varistor for an AC coil. For frequent switching, consider a suitably rated SSR or interposing relay.
CPU compatibility, Y addressing and software
Check the exact order code and expansion limits of CPUs with right-side expansion, including DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 and DVP-SE. Y0–Y5 on the case are local terminal labels. In Delta’s instruction sheet example, the six physical outputs map to Y30–Y35. The module occupies an eight-address block, so Y36 and Y37 have no physical channels and the next output module starts at Y40.
Control the outputs from the host CPU’s PLC program. Use WPLSoft or a compatible ISPSoft release according to the CPU and project version. On the DVP14SS211R/T, connect the UC-PRG020-12A to the CPU’s COM1 RS-232 port. Install the USB serial driver and select its virtual COM port. For other CPUs, select the programming cable for the port provided.
Related models
DVP08SN11R has eight relay outputs with a single C0 common. DVP08SN11T has eight NPN transistor outputs and DVP08SN11TS has eight PNP transistor outputs. DVP08SP11R combines four digital inputs and four relay outputs. Compare the channel count, output type and common terminals when selecting a spare.
Editor’s Note
On a spare module, inspect the side expansion connector and each C/Y pair. Heat damage or loose terminals can cause faults under load.
If the Y LED lights but the load stays off, check the field voltage at that output’s C terminal and its fuse first.
A relay click only confirms movement. If needed, isolate the field circuit and check the contacts with a suitable low-voltage test load.
If the next module’s first output appears at an unexpected address, check the allocation for six relays in an eight-address block.
Clear any output forces after testing. Verify emergency stop and guard circuits against the machine’s safety design.
PDF manuals and related pages
Delta DVP PLC files · See the DVP Series Module Manual §7.4.5, printed page 7-10 for model wiring and §7.5.2.2 for contact life and loads.
Navigation · Delta Automation · DVP PLC series · Expansion modules · DVP Slim digital modules
External references
Delta DVP Module Manual, wiring diagram · Delta DVP Slim instruction sheet (EN/ZH) · Delta SS2 cable selection