Delta DVP04AD-S2

Delta DVP04AD-S2 – 4-Channel Analogue Input Module

Delta DVP04AD-S2 adds four analogue inputs to a compatible Delta DVP Slim PLC system. It belongs to the DVP Slim analogue module family. Each channel can be set for voltage or current. Unlike a digital input, each analogue input reports the magnitude of the measured signal to the CPU.

Typical sources include a pressure transmitter for a pump, a level sensor for a tank or a 0–10 V sensor for position measurement. 4–20 mA sensors are also used for process measurements and long field runs. Check the range, output type and supply voltage on the pressure sensor label.

Power, resolution and input wiring

Provide an external 24 V DC supply. The supply range is 20.4–28.8 V DC and the instruction sheet lists a maximum draw of 2 W. Hardware resolution is 14 bits for voltage and 13 bits for current. Conversion takes 3 ms per channel. Input impedance is at least 1 MΩ for voltage and 250 Ω for current. The analogue circuit is isolated from the digital circuit. Analogue channels share the same circuit reference.

Wire a voltage signal to the channel’s V+ and COM. For current signals, jumper V+ to I+ on that channel and wire the current input through I+ and COM. A two-wire transmitter needs a field supply in the current loop. Size the 24 V DC power supply and fuse for the loop. Follow Delta’s diagram for grounding and shield connections. Route signal wiring away from motor cables to reduce electromagnetic interference when laying out the panel components.

CR#1 input modes and scaling example

Mode 0 is −10 to +10 V, mode 1 is −6 to +10 V, mode 2 is −12 to +20 mA and mode 3 is −20 to +20 mA. Module firmware V5.00 or later adds mode 4 for 4–20 mA, mode 5 for 0–10 V and mode 6 for 0–5 V. Mode 7 disables the channel. Read CR#34 to check the firmware version.

For a 0–10 bar transmitter with a 4–20 mA signal, default mode 3 scaling gives about 800 counts at 4 mA and 4000 at 20 mA. Pressure = (raw value − 800) × 10 ÷ 3200. Verify both endpoints before sending the engineering value to an HMI or PLC PID controller. Use the same units for the feedback and setpoint in applications such as speed control.

PLC software, cable and control registers

The first special module on the CPU’s right-side expansion bus is numbered 0. The card uses no digital X/Y addresses. On a supported CPU, use TO in the ladder program to write channel modes to CR#1 and FROM to read values. For the first special module, FROM K0 K6 D100 K4 reads the four averages into D100–D103. CR#2–5 sets averaging counts, CR#6–9 holds averages, CR#12–15 holds current readings and CR#30 holds fault bits.

Use WPLSoft or ISPSoft with a compatible Slim CPU such as DVP-SS2, DVP-SA2, DVP-SX2 or DVP-SV2. Use COMMGR for the ISPSoft connection. For example, the SS2 COM1 RS-232 connection uses UC-PRG020-12A from PC USB or UC-MS020-01A from PC RS-232. Connect the programming cable to the CPU. The module’s own RS-485 port supports standalone Modbus ASCII/RTU operation away from the CPU bus.

Related models and topics

DVP04AD-S is the earlier four-input model. Check its own modes and scaling. DVP06AD-S has six analogue inputs, DVP06XA-S2 has four analogue inputs and two analogue outputs, and DVP04DA-S2 has four analogue outputs. For local readings outside the PLC, see analogue signal controllers.

Editor’s Note

Start with the S2 suffix on the label. Compare modes and raw values before replacing an S card with an S2 card in an existing program.

If all four channels are missing, check the module’s 24 V supply first. Then check the side connector, special module number and CPU detection. The low byte of the CR#0 model code should be H’90.

If one current channel stays at zero, check its V+/I+ jumper, COM wiring and loop current.

Test a used card with a known source. In mode 3, apply 4, 12 and 20 mA and verify the reading rises across all three points. A lit LED alone cannot establish channel accuracy.

If readings fluctuate, check the shield and cable routing before changing averaging. More samples slow the response to a changing signal.

PDF manuals and technical documents

See Delta DVP PLC files for series documentation. In the Delta module manual, section 8.1.1 gives electrical specifications, 8.4.1 covers DVP04AD-S2 registers and 8.5.1 shows wiring.

Navigation · Delta automation · Delta PLC · DVP PLC series · Expansion modules · DVP04AD-S2 model page

External references

Delta DVP module manual · Delta DVP04AD-S/S2 instruction sheet