Delta RTU-485
Delta RTU-485 RS-485 Modbus Remote I/O Module
The Delta RTU-485 is a remote I/O coupler for connecting DVP Slim series input and output modules to Modbus over RS-485. It detects the modules mounted on its right side and responds to requests as a Modbus slave. Field sensors and control devices connect to the I/O cards in the remote panel. A PLC or another compatible Modbus master reads the inputs and controls the outputs.
Expansion, power supply and field wiring
Capacity is up to 128 digital inputs, 128 digital outputs and 8 special I/O modules. The installed DVP Slim cards provide the I/O points. When selecting cards, check how PLC I/O modules work, the difference between digital and analog inputs, and the analog I/O range. For example, a pressure transmitter needs a card with an input that matches its 4–20 mA or 0–10 V signal.
The module requires a 24 V DC supply (20.4–28.8 V DC). The RS-485 link uses a shielded twisted pair and a removable D+, D−, SG connector. Follow the panel design for routing, shield bonding and grounding. Electromagnetic interference from motor and drive wiring can disrupt serial communication.
DIP settings, PLC software and cable
Set the RTU-485 station address from 1 to 240 with ID0–ID7. Use DR0–DR2 to select a supported rate from 1,200 to 115,200 bit/s and PA0–PA3 and A/R to select an ASCII or RTU frame. Set the switches with power off, then reapply power. Match the master’s serial settings to the module, including Modbus ASCII or Modbus RTU.
DIP switches configure the RTU-485. Use WPLSoft or ISPSoft, according to CPU support, to create the PLC program that sends Modbus requests. Delta’s example uses COM2 RS-485 on a DVP28SV. To upload the PLC program, select a PLC programming cable that matches the CPU and its port. To test the RS-485 link from a PC, use a USB-to-RS-485 converter such as the Delta IFD6500.
Modbus addresses start at 0x0400 for digital inputs and 0x0500 for digital outputs. The first special module’s CR0–CR48 range is 0x1600–0x1630. The second starts at 0x1640 and ends at 0x1670. Moving a special module to a different position changes its register addresses. Check how the PLC or HMI driver represents raw hexadecimal addresses. Use 0x02 to read digital inputs and 0x03 to read registers. See the Modbus FAQ for protocol background.
Editor’s Note
Look at the connector before buying used. Ask for photos of the label, RS-485 terminal block, DIP switches and right-side expansion connector.
Photograph the settings before replacement. Record the address, baud rate, parity, ASCII/RTU mode and the order of the attached cards.
Start with a read test. The manual lists 0x0200 as the RTU-485 model code at register 0x0000. Then check a digital input whose field state you already know.
Read the LEDs together. If power is present and the communication LED stays dark, check the master’s request, the station address and line polarity in that order.
Plan the RUN/STOP test. Switching from RUN to STOP turns the attached digital outputs off. Switching back to RUN rescans the attached I/O. Test this with the machine in a safe state.