Delta DVP04DA-H3

Delta DVP04DA-H3 — Four-Channel Analog Output Module

Delta DVP04DA-H3 adds four analog outputs, CH1–CH4, to DVP-EH2/EH3 PLC systems. Among input and output modules, it performs the output function, converting CPU commands into voltage or current analog signals. Each channel’s output range is selected separately.

It uses 16-bit data for digital-to-analog conversion and provides −10 to +10 V voltage or 0–20 mA current output. The main PLC CPU accesses control registers using FROM/TO. This is not a standalone CPU and it occupies no digital X/Y addresses.

Power and CPU compatibility

External power is 24 V DC, allowable range 20.4–28.8 V DC, with specified maximum consumption of 4.5 W. Apply the DC supply to 24V/0V. Calculate supply capacity and the current budget with the analog loads; never apply mains voltage to output terminals.

The model manual dated 28 January 2013 specifies DVP-EH2/DVP-EH3 operation. Check the exact CPU, firmware and right-side expansion arrangement. Special modules are numbered 0–7 from the CPU outward, with a maximum of eight in the supported system.

Output modes and numerical scaling

CR#1 selects all four channel modes: CH1 uses b3–b0, CH2 b7–b4, CH3 b11–b8 and CH4 b15–b12. Mode 0: −10 to +10 V; mode 1: −5 to +5 V; mode 2: 1–5 V; mode 3: 4–20 mA; mode 4: 0–20 mA; mode 15: channel disabled. Match 0–10 V and 4–20 mA selection to both mode and wiring.

With the factory conversion curve, ±10 V mode uses −32000 to +32000; 16000 produces +5 V and the step is 312.5 µV. 0–20 mA mode uses 0–32000; 16000 produces 10 mA, with a 0.625 µA step. In 4–20 mA mode, 0 = 4 mA, 16000 = 12 mA and 32000 = 20 mA. Data uses 16-bit two’s complement.

A 0–10 V receiver can use the positive portion of ±10 V mode; limit the program command appropriately. This module does not perform analog input measurement. Distinguish analog and digital inputs from analog output commands.

V+, I+, COM and FG wiring

For each channel, use V+–COM for voltage or I+–COM for current. Select the appropriate output terminal and leave the unused one open. Do not bridge V+ and I+. Connect FG/shielding and system ground according to the manufacturer’s wiring diagram.

Maximum voltage-output current is 10 mA. Current output permits a total load of 0–500 Ω, including cable and receiver resistance. Outputs can command a variable-frequency drive or proportional valve; they do not supply motor or coil power directly. In PID control, match the command range to the receiving device’s scale.

Channels are not galvanically isolated from one another. Check reference-potential differences and ground loops. Shielding, correct grounding and separation from power wiring help reduce electromagnetic interference. The specified 1 ms response time is not the complete control cycle including CPU scanning and communication.

Programming software and cable

Use WPLSoft or an ISPSoft release supporting the actual CPU. In PLC programming, write modes and output values with TO and read status with FROM. No independent user program is downloaded to the module.

Use a DVPACAB2A30 programming cable for the PC-to-CPU connection. A USB-only PC requires a suitable USB-to-RS-232 converter, its driver and the correct COM port. This cable connects to the CPU, not to the module’s D+/D− terminals.

Standalone RS-485 operation and retained settings

D+/D− provides Modbus RS-485 communication with ASCII/RTU and 4800–115200 bps support. The module’s RS-485 access is unavailable while connected to the CPU expansion bus. For standalone serial operation, disconnect it from the CPU, provide external 24 V power and use an appropriate RS-485 interface.

CR#31 sets station address and CR#32 communication format; defaults are station 1, 9600 bps and ASCII 7E1. The manual states that latched-type settings written using TO/DTO are not retained after power loss. Reapply necessary settings during CPU initialization; distinguish this from standalone RS-485 writes for retained settings.

Control registers and four-channel 4–20 mA example

CR#0 = H6409 identifies the model. CR#1 selects modes; CR#6–#9 command CH1–CH4; CR#18–#21 contain offsets and CR#24–#27 gains. CR#30 reports errors and CR#34 firmware. Do not confuse calibration registers with output data.

For a bench example with special module number 0 and all channels at 4–20 mA, TO K0 K1 H3333 K1 selects mode 3 for every channel. TO K0 K6 D100 K4 writes D100–D103 to the four outputs. With the factory curve, each 16000 command produces 12 mA. Keep startup mode selection separate from cyclic output transfer.

FROM K0 K30 D110 K1 reads the error register. CR#30 is a bit field; supply, hardware and offset/gain faults can coexist. During PLC debugging, do not treat it as a single exclusive error number. Display the command, scale and fault state together in HMI and SCADA. Replace K0 with the actual special-module position and allocate suitable D-register storage.

Editor’s Note

When buying a used module, test every channel separately. Verify the H3 label, CR#0 identifier, terminal condition and expansion connector. One working channel does not prove that the entire module works.

Check voltage outputs with a suitable high-impedance instrument. In ±10 V mode, −32000/0/+32000 should produce −10/0/+10 V. Ensure that the connected load stays within the 10 mA limit.

A suitable 250 Ω test resistor can be used for current testing. In 4–20 mA mode, commands 0/16000/32000 should give approximately 1/3/5 V across it. For direct current measurement, connect the meter in series, never across a voltage output in current mode.

If the output measures correctly but a drive or valve responds differently, check its 0–10 V/4–20 mA selection, reference terminal and scaling. If disconnecting the load restores correct output, inspect total loading and ground potentials before blaming the output stage.

Back up the program and CR settings. Test startup, CPU STOP and communication-loss behaviour with machine loads disconnected. Verify that initialization is reapplied before returning the module to service.

PDF manuals

Start with our Delta DVP PLC files page. The DVP04DA-H3 Instruction Sheet, 5012611901-3DA1, dated 28 January 2013, has 18 pages with English, Traditional Chinese and Simplified Chinese sections. Use this edition’s detailed CR table for output and calibration addresses. The English DVP catalogue dated 23 October 2023 is an additional model-selection reference.

Related topics

DVP04DA-H2 is a four-output model with different resolution and mode settings. DVP06XA-H3 combines four analog inputs with two outputs. DVP04AD-H3 provides four analog inputs. Browse DVP-H3 modules and DVP expansion modules for the appropriate hardware family.

Delta DVP PLC series | DVP04DA-H3 model page | DVP file archive

External references

Delta DVP04DA-H3 instruction sheet — manufacturer-document archive copy | Delta DVP catalogue — English archive copy | Delta DVPACAB2A30 cable guidance