Delta DVP04DA-H

Delta DVP04DA-H analog output module

Delta DVP04DA-H is a four-channel, 12-bit analog output module from the original -H generation for the DVP-EH family. It converts digital commands from the PLC program into voltage or current signals. Within an analog I/O system, it performs output duties; it is not a CPU or sensor input module.

Applications include speed references for variable frequency drives, analog commands for suitable servo drives, and setpoints for proportional control equipment. Match the receiver's analog input range and wiring to the selected output mode.

Output modes and digital scaling

Each channel is selected independently: Mode 0: 0–10 V; Mode 1: 2–10 V; Mode 2: 4–20 mA; Mode 3: 0–20 mA. The factory mode is 0. The nominal command range is K0–K4000; the analog signal scale depends on the selected mode.

With standard conversion characteristics, commands of 0 / 2000 / 4000 produce 0 / 5 / 10 V in Mode 0 and 2 / 6 / 10 V in Mode 1. For analog current, the same commands produce 4 / 12 / 20 mA in Mode 2 and 0 / 10 / 20 mA in Mode 3. Establish the physical meaning of a zero command in 0–10 V and 4–20 mA applications. Modified OFFSET/GAIN settings can change the standard curve.

The manufacturer specifies basic resolution of 2.5 mV for voltage and 5 µA on the 0–20 mA scale. Total current-output load must be 0–500 Ω, including receiver and cable resistance. Response time is specified as 3 ms × number of channels; approximately 12 ms for four channels is not the complete PLC scan time.

-H, -H2 and -H3 generations

DVP04DA-H, DVP04DA-H2 and DVP04DA-H3 are different generations. Do not treat this module as a direct equivalent of an H2/H3 option selected for EH3. Check the CPU expansion table, complete model and hardware revision together. The DVP04DA-H CR#0 model code is H0401.

For CPU access, special modules are numbered 0–7 by their distance from the main unit. Digital I/O modules do not count toward this special-module number. When relocating a DVP expansion module, check the module number in FROM/TO instructions too. The analog module occupies no standard digital X/Y points.

Power supply and field wiring

The supply is 24 V DC, with a permitted range of 20.4–28.8 V DC. Calculate DIN rail power supply capacity together with the other loads. Use V+–COM for voltage output and I+–COM for current output; wiring and the CR#1 setting must select the same output type.

Keep shielded signal cables separate from power wiring and follow the manufacturer's FG and grounding arrangement. The digital and analog sections are isolated; analog channels are not isolated from each other. Receivers operating at different potentials may require suitable analog signal conditioning and isolation.

Programming software and cable

The module does not run a separate PLC project. It is controlled through FROM/TO instructions in the connected CPU program using WPLSoft or a version of ISPSoft supporting that CPU. In the ladder program, handle mode setup, output commands and fault checking separately. For ISPSoft connections, COMMGR manages the appropriate communication channel.

A common programming cable for the DVP-EH CPU's COM1 RS-232 port is DVPACAB2A30: approximately 3 m, with a 9-pin female D-sub PC connector and an 8-pin mini-DIN PLC connector. Without a PC serial port, add a USB-to-RS-232 converter with its driver installed and select the assigned COM number. See Delta PLC programming cables. Observe the differences between RS-232, RS-422 and RS-485; the module's RS-485 connection serves a different purpose from the CPU programming port.

CR registers and programming example

CR#1 selects channel modes, CR#6–CR#9 contain CH1–CH4 output data, and CR#30 contains error status. In CR#1, CH1 uses b0–b2, CH2 b3–b5, CH3 b6–b8 and CH4 b9–b11. For example, H0010 selects 4–20 mA for CH2 and 0–10 V for the other channels. Writing it affects the mode fields of all four channels.

Example for special-module number 0 only: under a first-scan condition, TO K0 K1 H0010 K1 sets the modes. Cyclic TO K0 K6 D100 K4 writes D100–D103 to the four outputs. FROM K0 K30 D200 K1 reads error status into D200. Limit D100–D103 to 0–4000 and scale engineering values from an HMI panel into this range first.

CR#18–CR#21 are OFFSET and CR#24–CR#27 are GAIN adjustments. Do not confuse them with normal output-command registers. CR#30 is bit-coded, so several error bits can be active simultaneously.

RS-485 and process applications

Standalone serial operation supports Modbus RS-485 using ASCII or RTU. RS-485 cannot be used simultaneously with the CPU expansion connection. For standalone PC access, use a USB-to-RS-485 converter with its driver installed and suitable twisted-pair wiring. CR#31 sets the station address and CR#32 the serial settings. The manual specifies a default speed of 9600 bps, with 7E1 for ASCII and 8E1 for RTU.

For PID control with a PLC, scale the PID output to this module and acquire feedback through appropriate input hardware. Define the pressure sensor's range and pressure measurement units correctly. Temperature sensors likewise require a separate input module; DVP04DA-H does not read sensors directly.

Editor's Note

Record the -H suffix, CPU model and module order first. Do not directly apply a project or wiring diagram prepared for H2/H3 to this older module.

If an output is missing, measure the 24 V supply at the module terminals under load. A POWER indication alone does not confirm a correct analog supply or an output command. Read CR#30 as well.

Test all four channels separately at commands of 0, 2000 and 4000. A zero command producing 4 mA in 4–20 mA mode is normal. Match the channel mode and receiver input before adjusting calibration.

Test current channels with an appropriate loop load. Measure current in series and voltage in parallel; do not place a meter set to current directly across a voltage output.

Back up OFFSET/GAIN and mode settings before changing them. A factory reset through CR#33 can affect field calibration. Do not keep changing calibration registers to generate normal output commands.

If outputs fluctuate when contactors operate, check supply dips, shielding and commons. Verify valve or drive behaviour on power loss and CPU STOP; independent machine protection must not rely solely on the analog command.

PDF manuals and related topics

Use our Delta DVP PLC files page for installation, CR tables and programming examples. Read the 2004 DVP04DA-H instruction sheet together with chapter 2 of the 2013 special-modules manual. The archived manufacturer documents are in English.

DVP -H modules · DVP04AD-H analog input · DVP expansion modules · DVP PLC series · Delta PLC · Second-hand Delta equipment

External references

Delta DVP04DA-H manufacturer instruction sheet, 2004 · DVP-PLC Special Modules, 2013, chapter 2