Delta DVP01PU-H

Delta DVP01PU-H – Single-Axis Position Control Module

Delta DVP01PU-H is a DVP-EH position control module with one axis and differential pulse output up to 200 kPPS. It provides motion commands to a stepper motor or servo drive, with speed, target position and ramps set by the PLC program. Each module controls one axis. Adding several modules to a system does not turn one card into a multi-axis controller.

Pulse output, power and expansion

The high-speed pulse outputs use FP+/FP- and RP+/RP- pairs with 5 V differential line drivers. Select Pulse/Direction, CW/CCW or A/B phase to match the servo drive input format and signal level. These are command signals; the servo motor or stepper motor receives power from its suitable drive.

Supply the module with 24 V DC, -15%/+20%. It connects to a compatible main unit’s right-side extension bus and occupies no digital X/Y points. Special module numbers run from 0–7 according to their distance from the main unit. Other special modules share the eight-module limit; verify the supply budget and CPU support.

Home, limits, MPG and auxiliary terminals

START starts operation, STOP stops it, LSP/LSN are directional limits and DOG serves as a home-near or interrupt input according to the mode. S/S is the common for these field inputs. Match the home position and limit switch functions to the output type and active level of each inductive sensor or photoelectric sensor.

ΦA+/ΦA- and ΦB+/ΦB- are manual pulse generator (MPG) A/B inputs; PG0+/PG0- accepts a zero signal. An incremental encoder having A/B signals does not make this a complete servo encoder feedback connection. Assess open- and closed-loop control together with the drive’s own feedback and independent verification of machine position.

CLR+/CLR- clears the servo drive’s error counter. It is an NPN open-collector output for 5–24 V DC loads below 20 mA. Match it to the receiving drive’s CLR circuit before wiring.

Programming software and cable

Prepare the host CPU program in WPLSoft or ISPSoft. The ladder diagram uses FROM/TO, or DFROM/DTO for 32-bit data. DVP01PU-H contains 54 sixteen-bit control registers, CR#0–CR#53. A 32-bit value occupies two consecutive registers.

Connect the PC to the main PLC. For a DVP-EH COM1 RS-232, 8-pin mini-DIN port, use a suitable DVP cable such as DVPACAB230. A PC without a serial port needs a USB-to-RS-232 adapter and its driver. In ISPSoft, configure the COMMGR serial driver with the correct COM port and PLC settings. The module’s motion output terminals are not programming ports.

Key CR registers and reading example

CR#0 = H0110 identifies the model. CR#1–#2 specify command pulses per motor revolution; CR#3–#4 specify travel per revolution; CR#5 holds basic parameters. CR#21/#22 set acceleration/deceleration; CR#23–#24 are target position I and CR#25–#26 operation speed I. CR#31 controls operation, CR#32 selects the mode, CR#43 reports execution status and CR#44 reports errors.

For the first special module, DFROM K0 K33 D200 K1 reads the pulse-based position in CR#33–#34 into D200–D201. FROM K0 K44 D210 K1 reads the error code. Change K0 to the actual module number. These are reading examples; configure the operating mode, units, limits and reference state before initiating motion.

Electronic gearing, travel and profiles

Calculate electronic gearing, command pulses per revolution and mechanical travel together. With 10,000 command pulses/revolution and 5 mm/revolution travel, a 20 mm move requires 40,000 pulses. This example assumes direct 1:1 mechanical transmission. Include any planetary gearbox or other transmission ratio in the calculation.

The module supports absolute/relative positioning, JOG, homing and selectable motion modes, with trapezoidal or S-curve acceleration. Set drive auto-tuning and position-loop gain for the mechanical load. Reaching a target in the module’s pulse counter does not by itself prove that the mechanical axis reached the correct position.

RS-485, wiring and generation differences

The RS-485 interface supports Modbus ASCII/RTU. On the H model, CR#41 sets the station address and CR#42 communication parameters. Raw RS-485 parameter addresses differ between the 2005 sheet and 2013 application manual. Match the document to the module revision instead of treating a CR number as a raw Modbus address.

Use shielded twisted pairs for differential pulse signals. Electromagnetic interference and incorrect grounding can cause direction or counting errors. DVP01PU-H2 and DVP01PU-S are separate models; the S and H upper CR maps differ. Review the program, terminals and firmware before replacement.

Safety and technical files

A standard STOP or limit input does not replace the machine’s emergency stop system. Design the required safety relay and drive stopping functions according to the risk assessment. Use low speed for initial tests and verify home direction, limit action and stopping distance.

Use Delta DVP PLC files for wiring sheets, CR descriptions and motion examples. Preserve the complete model, firmware and document edition with the program backup.

Editor's Note

A POWER indicator does not validate the motion section. Check external 24 V, the LV indication, limit inputs and CR#44 together. A direction inhibited by the control logic can appear to be a defective output.

On a used unit, test both directions, homing and MPG input separately. FP/RP indicators alone are insufficient; verify the differential pulses with a suitable oscilloscope or receiver and confirm the drive’s input type.

For incorrect travel, check command pulses per revolution, drive electronic gearing and mechanical travel first. Changing loop gain does not correct incorrect scaling.

If the motor does not move, check drive enable, alarms and limit permissions before blaming the pulse module. Do not increase current or speed to overcome a jammed mechanism or brake fault.

Back up the program and CR settings before replacement or initialization. Make initial moves at low speed in a controlled area. Remove all supplies before disconnecting cables, inspecting the board or replacing the module.

Related topics and navigation

Delta DVP-H modules · DVP01PU-H2 · DVP expansion modules · DVP PLC series · DVP PLC files

External manufacturer documents

Delta DVP01PU-H Instruction Sheet, 2005, EN · Delta DVP Special Modules Application Manual, 2013, Chapter 6, EN · Delta WPLSoft / ISPSoft FAQ