Delta DVP Slim communication modules
Delta DVP Slim communication modules
Delta DVP Slim communication modules connect compatible DVP PLCs to Ethernet, DeviceNet, CANopen, PROFIBUS DP and serial networks. They let you share PLC data with an operator panel, exchange data with drives and remote I/O stations, or pass measurements and status information to a building automation system.
Start with the other device’s protocol, its master or slave role, and the exact PLC model. Delta classifies the DVPDT01-S and DVPPF01-S as DVP-S extension modules and the -SL models below as left-side high-speed communication modules. Before ordering, check the host expansion bus, minimum firmware, and supported module count in the relevant manual.
Compare models · Software and cabling · Choose by application · PDF manuals
Eight models at a glance
| Model | Network / interface | Role |
|---|---|---|
| DVPDT01-S | DeviceNet | Slave adapter. Connects to an existing scanner with four bytes in each direction. |
| DVPPF01-S | PROFIBUS DP | Legacy DP slave. Fixed cyclic data of four bytes in each direction. |
| DVPEN01-SL | Ethernet / Modbus TCP | Client and server functions. One Ethernet port and one RS-232 port. |
| DVPDNET-SL | DeviceNet | Scanner/master function. The manual also covers slave mode. |
| DVPCOPM-SL | CANopen | CANopen master applications, PDO/SDO and PLC data mapping. |
| DVPPF02-SL | PROFIBUS DP | Left-side DP slave. Cyclic I/O configuration through a GSD file. |
| DVPSCM12-SL | RS-485 / RS-422 | Two serial ports. Modbus RTU/ASCII and user-defined UD Link. |
| DVPSCM52-SL | RS-485 / RS-422 | SCM12 functions plus BACnet MS/TP slave support. |
Which software and cable do you need?
PLC programming. Open the existing project in WPLSoft or ISPSoft, according to CPU support. Set up the ISPSoft connection in COMMGR where required. Choose the PC-to-PLC programming cable to match the CPU’s communication port. Use an RJ45 network cable for a supported Ethernet connection or a serial programming cable with the correct Delta pinout for that CPU.
Ethernet and serial modules. Use DCISoft for DVPEN01-SL IP and data exchange settings. Use SCMSoft within DCISoft to set the ports, protocols and data exchange on DVPSCM12-SL and DVPSCM52-SL. See Delta PLC programming cables for the CPU connection. The DVP-SA2, for example, can use a UC-PRG020-12A cable through COM1 RS-232. Select the field cable from the network wiring diagram. The device manual specifies wiring and pinouts for the RS-232, RS-422 and RS-485 interfaces.
Fieldbus setup. Use DeviceNet Builder for the DVPDNET-SL scan list and I/O mapping or CANopen Builder for DVPCOPM-SL nodes and PDO layout. Import the DVPPF01-S or DVPPF02-SL GSD file into the PROFIBUS master’s engineering tool. Use cables and connectors specified for the particular DeviceNet, CANopen or PROFIBUS bus. Check the model code and revision when selecting a file from the Delta EDS archive.
Choose a module by application
Share data with an HMI or SCADA system. For a Modbus TCP host, establish the DVPEN01-SL client/server role, its IP settings and the PLC addresses to read. The EtherNet/IP and Modbus TCP comparison helps identify which protocol an Ethernet device uses. Delta’s DVPEN02-SL has two Ethernet ports. If the installation uses the DVPEN01-SL’s RS-232 port, account for it in the upgrade. Check DVPEN02-SL EtherNet/IP support against the CPU and firmware table.
Add a drive or remote I/O. For CANopen drives connected through DVPCOPM-SL, record each node ID, baud rate and PDO map. Use DVPDNET-SL scanner mode to manage a DeviceNet network from the DVP. For a legacy DVP node connecting to an existing scanner, check the DVPDT01-S adapter. To collect I/O at a separate station, see Delta DVP remote I/O modules, including RTU-EN01, RTU-DNET and RTU-PD01.
Maintain a machine on PROFIBUS DP. Both PROFIBUS models operate as DP slaves. Delta specifies a fixed cyclic data length of four bytes in each direction for DVPPF01-S. Plan DVPPF02-SL GSD selection and PLC data mapping using its manual. Record the station address and cyclic input/output lengths from the master project before replacing hardware.
Metering, serial devices and building automation. For an energy meter, identify the Modbus over RS-485 address, Modbus RTU or Modbus ASCII settings, and register table. DVPSCM12-SL and DVPSCM52-SL use COM1/COM2 settings and UD Link where needed for serial data exchange. For a BACnet MS/TP connection, match the DVPSCM52-SL MS/TP slave role and its supported AV/BV points to the master device.
Editor’s Note
Ask for clear label photos. On used equipment, check the CPU and module labels, side connector, latches and removable field terminals.
Save the working setup before removal. Keep the IP list, EDS/GSD files, I/O map and address switch positions with the CPU project.
Commission one node first. Read one value from a known address and compare the LEDs with the manual. Test write operations separately under safe test conditions.
Trace intermittent faults back to the wiring. Check end termination, polarity, line speed, shielding and grounding. If failures coincide with a drive starting, inspect the cable routing inside the panel.
Check the data map if values are wrong. Compare byte and word order, signed values, scaling and address offsets against a known measurement.
Bench-test the spare. Use the same CPU to verify module detection and data exchange over the network. Isolate power before fitting the module and identify the correct terminal from its manual.
Related topics
Network planning. Industrial communication · PROFINET · CAN communication FAQ · Modbus FAQ
Physical connections and monitoring. RS-232 · RS-422 · SCADA
Delta PLCs, expansion and software. DVP PLC series · DVP expansion modules · DVP-SA2 · DVP-SX2 · DVP-SV2 · DVP-SE · Delta PLC software
OtomasyonAVM PDF manuals
Delta DVP PLC PDF files · DVPEN01-SL Rev.04 installation and IP settings · DVPCOPM-SL CANopen and PDO mapping · DVPDNET-SL scanner, historical edition
External references
Delta DVP Series Module Manual, 2026 edition, Chapter 13 (PDF) · DVP Special Modules Application Manual, Chapter 10 (PDF) · DVPSCM12/52-SL serial and BACnet manual (Delta download page) · Delta DVPEN01-SL and DVPEN02-SL comparison