Delta DVP -H3 modules

Delta DVP -H3 modules

Delta DVP -H3 modules are right-side expansion modules for analog measurement and control in DVP-EH3 systems. The DVP04AD-H3 has four input channels, the DVP04DA-H3 has four analog outputs, and the DVP06XA-H3 combines four inputs with two outputs. For a new PLC panel, count the signals to read and the devices that need a reference. Then check the CPU model and signal ranges.

Compare the three H3 modules

ModelChannel arrangementMain signal rangeModule ID
DVP04AD-H34 analog inputsInput ±10 V or ±20 mAH6407
DVP04DA-H34 analog outputsOutput ±10 V or 0–20 mAH6409
DVP06XA-H34 analog inputs + 2 analog outputsInput ±10 V or ±20 mA. Output ±10 V or 0–20 mA.H6608

The table shows the main voltage and current ranges. For a 4–20 mA loop, use the module’s instruction sheet to select the channel mode and wiring diagram. Voltage and current connections may use different terminals. For example, the DVP06XA-H3 uses mode 3 for 4–20 mA on the selected channel.

Choose a module for the application

Use the DVP04AD-H3 for measurement. Its analog inputs can read up to four pressure transmitters, flowmeters or level transmitters. With a two-wire transmitter, check the loop supply, polarity and current input wiring together. For an on/off pressure switch contact, see analog versus digital inputs.

Use the DVP04DA-H3 when you need four analog control outputs. For example, it can send independent speed references to four variable-frequency drives. Match each drive’s reference source, input type and range. For current output, check that the connected device and total loop load fall within the module’s allowable limits.

The DVP06XA-H3 combines measurement and control. CH1–CH4 are inputs and CH5–CH6 are outputs. For example, use an input to read pressure and an output to set pump speed. In a constant-pressure pump system, configure the transmitter scale and the drive speed limits separately. If you use PLC-based PID control, verify the control action and output limits before commissioning the loop.

Identify and address the module on an EH3

On the DVP-EH3, registers D1320–D1327 store the IDs of right-side special expansion modules in connection order. If the right-side special module closest to the CPU is a DVP06XA-H3, D1320 reads H6608 in hexadecimal. Compare the project’s module number with the physical order when investigating unexpected readings after a replacement.

In the ladder program, FROM reads module control registers and TO writes to writable control registers. On the DVP06XA-H3, CR#1 selects input modes and CR#2 selects output modes. Channel modes, measured values and output commands occupy separate registers. When transferring settings, check the module number, CR address and data length against the specific module’s register table.

In a DVP-EH2 or older DVP-EH cabinet, check the full CPU order code against the specific module sheet. Delta’s DVP04AD-H3 and DVP04DA-H3 sheets document FROM/TO access with EH2 and EH3. Its programming manual also lists the supported -H2 special modules for EH3. Compare the terminals, CR addresses and raw measurement range before replacing a module.

WPLSoft, ISPSoft and connection cables

Connect to the EH3 CPU with WPLSoft or ISPSoft. For ISPSoft, configure the communications driver in COMMGR. Select the correct CPU target in the PLC programming software and back up the existing project.

For EH3 COM1 RS-232, Delta’s cable guide shows UC-PRG020-12A for a PC with USB and UC-MS020-01A for a PC with a serial RS-232 port. Install the USB cable driver and select the COM port assigned by Windows. See DVP programming cables for other CPU connections. Check the module sheet for its RS-485 communication conditions. For example, the DVP04DA-H3’s RS-485 interface is disabled while it is attached to the CPU.

What to check during the first measurement

For a linear 4–20 mA / 0–10 bar pressure sensor, 4, 12 and 20 mA represent 0, 5 and 10 bar respectively. Check the input current first, then the module’s raw value and the engineering value displayed on the HMI. If a sensor reading stays at its upper limit, check the channel mode, common terminal and loop supply. If the electrical values are correct, check the PLC scaling endpoints.

If readings jump when the drive runs, check for electromagnetic interference. Check signal cable routing and grounding against the manufacturer’s diagram. Once measurements are stable, consider filtering or averaging based on the required noise immunity and response time.

Editor’s Note

When buying a used module, ask for photos of the front and side labels, terminals, side connector and DIN rail latch.

Back up the project before removing the old card. Record module order, the CR addresses in use and the channel modes so you have a baseline for the replacement.

Check the CPU supply and the module’s 24 V DC supply separately. Isolate the power before inspecting terminal wiring.

Test AD and XA inputs with a known signal source. Measure DA and XA outputs on a suitable test load before connecting a drive or valve.

If the display value differs from what you expect, start with the live raw reading. Then check PLC scaling and the HMI unit.

After replacement, confirm the module ID in D1320–D1327. Bring the inputs and outputs into service one at a time.

PDF files and related Delta pages

Delta DVP PLC PDF files · Delta PLC and HMI manuals · DVP-EH2 hardware sheet (PDF)

Delta DVP expansion modules · Delta DVP EH modules · Delta DVP -H modules · DVP Slim analog modules · DVP Slim specialty modules

DVP80EH00T3 · DVP32EH00M3 · Delta DVP PLC series · Delta PLC · Used Delta products

External references

DVP04AD-H3 instruction sheet (PDF) · DVP04DA-H3 instruction sheet (PDF) · DVP06XA-H3 instruction sheet (PDF) · DVP-EH3 hardware sheet (PDF) · Delta DVP programming manual (PDF) · Delta PLC/HMI Cable Selection Guide (PDF)


Refine Search