Delta DVP32XP00R

Delta DVP32XP00R – AC-Powered Expansion Unit with 16 Inputs and 16 Relay Outputs

Delta DVP32XP00R is a 16-input / 16-relay-output expansion unit in the DVP ES / EX module family. Its main supply is 100–240 V AC, while its digital inputs use 24 V DC. It increases the field I/O capacity of a compatible Delta PLC. The host CPU runs the user program and processes its X inputs and Y outputs.

Typical applications include pushbuttons, limit switches, inductive sensors and photoelectric sensors, plus suitable relay, indicator and contactor control circuits. The 32-point total means 16 inputs plus 16 outputs. The distinction between analog and digital inputs matters: this unit does not provide analog measurement channels.

Power supply and input characteristics

Main supply: 100–240 V AC at L/N. Inputs: 24 V DC Sink/Source, nominally 5 mA per input. The ES/EX DIDO sheet specifies approximately 20 ms input response. Fast encoder pulses or short signals require suitable high-speed input hardware.

The sheet lists 30 VA maximum consumption and a 400 mA auxiliary 24 V DC output for the 32XP00 group. Include input circuits and sensor loads in the auxiliary supply budget. Treat this terminal as an output; do not feed an external power supply into it or parallel supply outputs. Where external power is needed, select a suitable DIN rail power supply and reference arrangement according to the wiring diagram.

PNP / NPN input wiring

For a PNP sensor, connect S/S to 0 V; the sensor output applies +24 V to the selected X input. For an NPN sensor, connect S/S to +24 V; the sensor output pulls X toward 0 V. Check sensor power, signal and common together when selecting the Sink/Source arrangement.

For a dry-contact test, switch the appropriate +24 V or 0 V reference to X. Change common wiring with power removed. Keep the AC main supply separate from the DC input circuit; never connect L/N voltage to X or S/S terminals.

Relay outputs, commons and load selection

The R suffix identifies relay outputs. The relay contacts switch an appropriate external load circuit. The manufacturer sheet specifies 2 A per output and 5 A per common, with voltage limits of 250 V AC / 30 V DC. It also lists 90 W resistive and 75 VA inductive load limits. Apply these limits together; multiplying 2 A by the supply voltage alone does not establish the permitted load power.

Common groups: C0 → Y0–Y3; C1 → Y4–Y7; C2 → Y10–Y13; C3 → Y14–Y17. Three outputs drawing 2 A each on one common total 6 A and exceed the 5 A common limit. Protect load circuits with suitable fuses. Consider an appropriate interposing relay and socket for frequent switching or high inrush loads.

Relay response is approximately 10 ms; the sheet lists a maximum switching frequency of 1 Hz. These contacts are unsuitable for servo pulse commands or fast PWM. Use appropriate flyback suppression for DC coils and manufacturer-recommended RC/MOV suppression for AC coils.

CPU compatibility and similar model codes

DVP32XP00R appears in the expansion documentation for the original DVP-ES and DVP-EX families. Check the exact host CPU, expansion connection, installed order and total I/O limit. DVP32XP200R belongs to a different ES2/EX2 generation; a similar name is insufficient evidence of interchangeability.

DVP32XP11R also provides 16 inputs and 16 relay outputs but uses a 24 V DC supply. DVP32XP00T is AC-powered with transistor outputs; DVP32XP11T is DC-powered with transistor outputs. DVP24XP00R provides 16 inputs and 8 relay outputs. Preserve the 00/11 and R/T suffixes when comparing supply, loads and terminals.

Programming software and cable

Program the host CPU using its supported WPLSoft or ISPSoft version. Preserve the correct CPU selection and project format when working with an existing ES/EX program. With ISPSoft, configure the COMMGR driver and correct COM port. DVP32XP00R itself has no programming port or independent Modbus station address.

Delta’s ES/EX cable diagram shows the UC-PRG020-12A USB programming cable for the host CPU’s COM1 RS-232 port. UC-MS020-01A can be used with a PC RS-232 port or suitable USB-to-RS-232 converter. Install the UC-PRG USB driver and select its assigned COM port. Connect to the host CPU; the expansion connector is not a PC programming interface.

X / Y addressing and commissioning example

Local inputs are labelled X0–X7 and X10–X17; outputs are Y0–Y7 and Y10–Y17. Octal addressing does not include X8/X9 or Y8/Y9. Program addresses depend on the host CPU and preceding expansions.

Example: as the first digital expansion after a DVP32ES00R2 host, the unit occupies X20–X37 and Y20–Y37. Local X0 maps to X20 and X17 to X37; local Y0 maps to Y20 and Y17 to Y37. Preceding modules may change the starting addresses. Compare input LEDs with online X bits, then compare Y bits with physical contacts using a safe test load.

Editor’s Note

Start with the full label: DVP32XP00R. A similar-looking 11R unit has a different supply. Photograph the old module label and wiring before disconnecting anything.

Inspect with power removed. Note heat marks at L/N, darkened output terminals, loose commons and damaged expansion connections. Check grounding and possible sources of electromagnetic interference inside the cabinet.

Test all 16 inputs and all 16 relay outputs with a compatible host CPU. A clicking relay does not prove a healthy contact; check switching with an appropriate low-power test load first.

Before blaming a failed output on the module, check the Y address, common supply, fuse and field cable. Several failed outputs in one group particularly justify checking their common connection.

For a welded contact or excessive voltage drop under load, investigate the relay contacts and solder joints. A replacement relay must match coil voltage, contact configuration, pinout and load capability. Correct excessive load or coil transients before returning it to service.

For a used unit, request a record stating the host CPU and channels tested. An I/O test record is more useful than “it was working.” Keep machine outputs in a safe state that prevents unintended movement during testing.

PDF documents and related topics

Use the Delta DVP PLC PDF files page for the document collection. Our original ES/EX manufacturer instruction sheet (English) also includes DVP32XP00R. Review the expansion sheet, legacy series catalogue and host CPU cable guide together.

See What is a PLC? and PLC accessories for the basic control structure, and HMI panels for operator interfaces. Timers and counters are separate device functions; the host CPU executes this expansion unit’s control logic.

Plan panel components, cable routing and load protection together. Related hardware is listed under DVP expansion modules and DVP PLC series.

Navigation: Delta home · Delta PLC · ES / EX modules · DVP files

External references

Delta ES/EX DIDO manufacturer sheet – 5011671702-ED02, English/Chinese · Delta WPLSoft / ISPSoft explanation