Delta AS218PX-A
Delta AS218PX-A PLC CPU with PNP outputs
The Delta AS218PX-A is a compact Delta AS200 PLC CPU with a 24 V DC supply and 64K program steps. It has 8 digital inputs, 6 PNP transistor outputs, 2 analog inputs and 2 analog outputs. In a pump panel, it can read a pressure transmitter through an analog input, send an analog speed reference to the drive and monitor level switches on digital inputs.
Analog input and output ranges
The built-in analog signal channels have 12-bit resolution. Both inputs measure −10 to +10 V in voltage mode or −20 to +20 mA in current mode. Both outputs provide −10 to +10 V in voltage mode or 0 to 20 mA in current mode.
For a 4–20 mA transmitter, use current mode and scale 4 mA and 20 mA to the lower and upper engineering values. Check Delta’s wiring diagram for the two-wire transmitter supply loop and the terminal jumper required in current mode. For extra channels, see the AS analog modules.
PNP outputs and pulse control
The PNP outputs source positive voltage to the load when active. The output circuit accepts a 5–30 V DC load supply. Delta specifies 0.5 A per output and 1.5 A per common for resistive loads. The CPU supports up to three pulse axes at 200 kHz in the relevant pulse mode and four high-speed counter channels for applications such as encoder feedback. For additional digital I/O, check compatible AS expansion modules. Delta specifies up to 32 expansion modules and 1,024 I/O points in a supported configuration.
The related AS218TX-A has NPN outputs and the AS218RX-A has relay outputs. The AS228P-A also has PNP outputs and provides 16 digital inputs and 12 digital outputs. Check the output type and built-in analog channel requirements when choosing a replacement.
Programming and communications
Select the AS218PX-A CPU in Delta ISPSoft and set up the PC connection in COMMGR. When connecting with a Mini USB data cable, check the Delta USB driver. For Ethernet access, check the IP settings on the PC and PLC.
The two RS-485 ports can be used for serial Modbus. The Ethernet port supports Modbus TCP and EtherNet/IP. The CPU also has a CANopen connection and a microSD slot.
Editor’s Note
On a used unit, check the PX nameplate marking and confirm that the removable AIO terminal block is present.
On the bench, use a 24 V DC supply to check the POWER and ERROR indicators, then verify the ISPSoft connection.
Apply 4 mA and 20 mA to an analog input and check the readings at both ends of the range.
Measure an analog output and check a PNP output separately with a suitable test load.
Before replacement, back up the PLC project, analog channel settings and network parameters.