Delta AS-F2DA
Delta AS-F2DA Two-Channel Analog Output Card
Delta AS-F2DA is a two-channel analog output card for a Delta AS300 CPU’s function-card slot. It converts a PLC command into a 0–10 V DC or 4–20 mA signal. Typical applications include a drive speed reference, a proportional valve command or an analog reference to another controller.
Output terminals and load limits
VO1 and VO2 are voltage outputs. IO1 and IO2 are current outputs. COM is the analog common. In voltage mode, the receiving input must be at least 1 kΩ. In current mode, the total load must be 500 Ω or less. Delta’s hardware manual specifies 2 ms conversion time per channel. Include the PLC scan when estimating total response time.
ISPSoft settings and SR addresses
Open the AS300 project in ISPSoft. Use COMMGR and a suitable PLC programming cable to connect to the CPU. In HWCONFIG, open Function Card 1 or Function Card 2 according to the card’s physical slot. Select the receiving device’s signal type under F2DA Analog Output Mode.
Slot 1 uses SR172 for CH1 and SR173 for CH2. Slot 2 uses SR174 for CH1 and SR175 for CH2. Use MOV to write the scaled setpoint to the channel’s SR. In 0–10 V mode, 0–4000 corresponds to 0–10 V.
For 4–20 mA, Delta’s hardware manual specifies 0–4000 and 12-bit resolution. Section 2.2.16 of the programming manual specifies 0–2000 and 11-bit resolution. Check the existing project scaling. Before commissioning the receiving device, verify 4, 12 and 20 mA at the low, midpoint and full-scale settings on the bench.
Choosing a function card or expansion module
Among the AS function cards, the AS-F2AD provides two analog inputs. The AS04DA-A provides four outputs. The AS06XA-A combines four inputs with two outputs. These are right-side AS expansion modules. Compare AS analog measurement modules by channel count and signal range.
Editor’s Note
When buying used, check the AS-F2DA model code, connector and five-position terminal block.
Isolate power before removing the card and record which CPU slot it uses.
If the card changes slots, check the program’s SR172–SR175 addresses against the new slot.
Bench-test both channels in the intended operating mode. Include the load resistance in current mode.
Before connecting a drive, compare the PLC output range with the drive analog input setting and speed scale.