What types of output signals does the tachometer provide?

Getting the speed reading into your control system

A tachometer can provide analog current or voltage, speed pulses, relay or transistor alarms, and digital communications, depending on its configuration. Some instruments offer a local readout only. Check the complete order code for fitted outputs and permitted combinations. A feature listed for a product family may require a separate option.

Match the output to the information you need

Output Information carried Typical receiver
4–20 mA / 0–20 mACurrent representing a scaled speed value.Compatible analog current input.
For example, 0–10 V / 0–5 V / 0–1 VVoltage representing speed; available ranges vary by model.Compatible voltage input or recorder.
Pulse / frequencyDetected pulses or a pulse train generated at a defined ratio.High-speed counter or frequency input.
Relay / transistor comparison outputA condition such as low speed, high speed or speed within limits.Digital input, alarm or suitable control circuit.
Digital communicationsMeasurements, status and parameters supported by the protocol.PLC, HMI, computer or gateway.
BCD on selected modelsDigits represented by parallel digital codes.Compatible parallel inputs and the specified cable.

Scaling an analog signal into rpm

An analog output maps speed onto a current or voltage range. Consider an illustrative setting of 0–3000 rpm across 4–20 mA: 4 mA represents zero speed, 12 mA represents 1500 rpm, and 20 mA represents 3000 rpm.

n = (I − 4) / 16 × 3000
I is current in mA; n is speed in rpm. Configure the PLC analog input with matching endpoints. This example is a chosen scaling, not a universal factory setting.

Zero speed can legitimately produce 4 mA. A reading near 0 mA may indicate a broken connection, lost power or another problem. Interpret it using the instrument's specified fault behaviour; defined fault currents and automatic wire-break diagnostics are not available on every tachometer.

Current and voltage interfaces require compatible circuits. Passing 4–20 mA through a suitable 250 Ω resistance produces 1–5 V, not 0–10 V. Check resistance tolerance, input loading, total loop resistance and the output's drive capability. Follow the manual for active/passive connections, power requirements and signal common.

A pulse train is different from a switched alarm

For a pulse output, establish whether it repeats detection pulses or generates a scaled frequency. Where the pulses directly represent shaft rotation, n = 60 × f / P, with f in Hz and P in pulses per revolution. For example, 50 Hz at two pulses per revolution means 1500 rpm. An incorrect encoder pulse count or reflective-marker count changes the calculated result.

NPN/PNP identifies the electrical arrangement, not the output's purpose. An NPN or PNP output can simply switch when a speed limit is crossed. Check sinking/sourcing compatibility, voltage levels, pulse width and the receiver's maximum frequency.

As a documented example, the HIOKI FT3406 provides a selectable 0–1 V analog output or 0–3.3 V detection-pulse output through one shared port. They cannot operate simultaneously. The pulse is active low, with a 300 µs low interval. Do not assume compatibility with a 24 V PLC input: check its thresholds and whether a signal converter is required. These outputs are not provided on the FT3405.

Comparison outputs report a condition

Relay and transistor comparison outputs can report low speed, overspeed or an acceptable range for the application. A single on/off output does not convey the actual rpm value. Where supported, hysteresis and delays help prevent repeated switching near a threshold. An illustrative high-speed alarm might switch on at 1800 rpm and release at 1750 rpm; verify the available comparison logic.

During installation, check contact ratings for the actual load type, and transistor voltage, current and leakage limits. A relay contact switches an external circuit; it does not supply power itself. A transistor output also needs a compatible load and common connection. Measurement accuracy, output response time and filtering affect the resulting alarm behaviour.

Communications and option cards need separate checks

A supported communications interface can transfer speed and status to a PLC, HMI or SCADA system. RS-485 specifies an electrical interface; Modbus RTU specifies a protocol. An RS-485 connection alone does not prove Modbus support. Confirm data addresses, units, scaling and the action taken when communication stops.

The OMRON K3HB-R family offers analog current/voltage, relay, NPN/PNP comparison, BCD and serial communication options. However, linear analog output and RS-232C/RS-485 cannot be used together in one instrument; check the order-code combinations. For Red Lion PAXI instruments, the option card matters too: the manufacturer specifies PAXCDC10 for Modbus operation, while PAXUSB00 is a programming interface. A USB connection should not be assumed to provide a continuous measurement stream.

Specify the receiving equipment before ordering

Define the receiver's input type, signal range, rpm scaling, number of outputs and simultaneous-use requirements. Check the measurement range separately from the range assigned to the analog output. Assess galvanic isolation and operating conditions. At commissioning, use a known speed or an appropriate output-test function to compare the local display with the receiving system. During maintenance, a working display alone does not establish that the output remains accurate.