C22.2 No. 248 Standard

Choosing the right fuse takes more than matching the ampere rating
Hello friends. The CSA C22.2 No. 248 series addresses the construction, operating characteristics, markings and test conditions of low voltage fuses. It is not a transformer or energy efficiency standard. The purpose of an electrical fuse is to provide protection by opening a circuit under unsuitable current conditions; the 248 series establishes how different fuse classes are evaluated.
Editor's note: A fuse marked 16 A is not expected to open immediately at 16.1 A. Opening time depends on the magnitude of the overcurrent and the time-current characteristic. Two fuses with the same ampere rating may not be interchangeable if their delay, interrupting rating or application class differs.
One standard or a family of standards?
C22.2 No. 248 identifies a series. 248.1 provides the general requirements, and the relevant product part is read together with it. The verified general requirements edition is CSA C22.2 No. 248.1:22. It was developed through North American harmonisation with UL 248-1 and Mexico's NMX-J-009/248/1-ANCE. This relationship does not mean that every product is automatically approved for all three countries.
The general scope of 248.1:22 covers fuses rated up to 1000 V AC and/or DC, with interrupting ratings up to 300 kA; the stated limit for Mexico is 200 kA. These are not ratings available from every fuse. Particular parts can also modify the general scope, so the applicable product limits must be established from the relevant part and manufacturer documentation.
Which parts address which fuses?
Examples of product parts in the 248 family include 248.4 for Class CC, 248.5 for Class G, 248.8 for Class J, 248.10 for Class L, 248.12 for Class R and 248.15 for Class T. Renewable and non-renewable Class H fuses have separate parts, and Class K is addressed separately. These letters should not be interpreted merely as dimensions or current ranges.
248.13 addresses semiconductor fuses, 248.14 supplemental fuses, and 248.19 photovoltaic fuses. When deciding which fuse type to use, establish which application category is involved. Supplementary protection on an electronic board and protection of a power distribution circuit are different duties.
The series should not be limited to older lists of parts. CSA C22.2 No. 248.21:25 covers fuses for the protection of batteries and battery systems, with its own scope extending to 2000 V DC. This particular scope illustrates why the general voltage limit in 248.1 cannot be applied unchanged to the entire family. The standard's title alone also does not establish an installation's voltage classification.
Supplementary protection and branch circuit protection
Supplemental fuses covered by 248.14 are not intended for branch circuit protection or equivalent applications. The relevant scope addresses supplemental fuses rated 60 A or less. CSA or UL information on a product does not establish suitability for every protective duty. When comparing different fuse types, check their intended protective function as well.
For example, a supplemental fuse used at a control board input is not a suitable substitute for a machine's branch circuit protection simply because the ampere ratings match. Electrical fuse selection starts with the circuit's function and the appropriate product class. The equipment manufacturer's maximum fuse rating or specified class must also be respected.
Read the current rating together with the time-current curve
A fuse's ampere rating describes its current carrying rating under specified conditions. It does not determine opening time on its own. Motor starting or initial energisation of a power supply may produce a brief high current. Compare that pulse with the manufacturer's time-current and pulse withstand data. Fitting a larger fuse to conceal a sustained overload is not a sound solution.
For example, knowing that a load runs at 8 A and draws 40 A during energisation is insufficient for selecting a fuse: the duration and repetition rate of that 40 A pulse also matter. When investigating why a fuse opens, distinguish normal inrush from overload and short circuit conditions. For high power equipment, conductor protection and the equipment's particular protection requirements must be assessed together.
Voltage rating and interrupting rating describe different limits
The voltage rating matters when the fuse opens the circuit safely; it does not specify a voltage at which the element begins to melt. Circuit voltage must not exceed the fuse's applicable AC or DC rating. An AC rating does not establish DC suitability, and the DC interrupting rating must also be verified separately.
The interrupting rating concerns the highest prospective short circuit current that the fuse can safely interrupt under specified conditions. For a fuse marked 20 A / 500 V AC / 50 kA, 20 A is the current rating and 50 kA is the interrupting rating. If the available fault current is 18 kA, that capacity comparison appears satisfactory; voltage, class, characteristic and holder suitability still require separate checks.
What do I²t and selective coordination tell us?
I²t is the time integral of current squared, expressed in A²s. It helps compare the thermal effect of the current pulse passed before interruption; it is not directly an energy value in joules. Pre-arcing I²t and total clearing I²t differ: the total includes the contribution during arcing. Matching only the ampere rating is therefore insufficient for semiconductor protection.
Selective coordination aims to have the protective device nearest the fault open while upstream devices remain in service. Review time-current curves and the manufacturer's coordination data for the short circuit region. Selecting an upstream fuse with twice the downstream ampere rating does not guarantee coordination for every fuse type and every fault current.
The holder and panel are part of the selection
While the fuse itself is evaluated under the 248 series, holders are commonly addressed by the 4248 series and, where its scope applies, C22.2 No. 39. Identical physical dimensions do not establish identical electrical suitability. Verify the holder's accepted fuse class, voltage, current and short circuit conditions. A high fuse interrupting rating does not automatically increase the short circuit rating of the complete panel.
For fuse box installation and maintenance, enclosure temperature, ventilation, contact surfaces and tightening torques matter. A loose contact can overheat while the fuse remains intact. There is no single current derating percentage applicable to all fuse classes; use the temperature and mounting data for the actual product family.
Testing, markings and replacement
The 248 family establishes construction, operating conditions, markings and test conditions for the applicable class. Current carrying performance, opening behaviour and safe fault interruption are assessed in relation to product ratings. A single test current or opening time cannot be assigned to every class. References to CSA standards should identify the applicable part and edition.
When a fuse needs replacement, compare its model, class, current rating, AC/DC voltage, interrupting rating, characteristic and holder compatibility. For safe fuse replacement, isolate every energy source and verify the absence of voltage. Equivalence between IEC 60269 and UL fuse standards also cannot be established from matching ampere ratings alone; compare the actual product documentation.
Related topics
What is a fuse?; Fuse standards; CSA standards; Fuse products.
Sources
CSA C22.2 No. 248.1:22: general requirements and scope
CANENA: correspondence between CSA, UL and ANCE standards
UL Standards & Engagement: scope of 248-14 supplemental fuses
CSA C22.2 No. 248.21:25: fuses for batteries and battery systems
Mersen: replacement assessment using fuse class, voltage and interrupting rating
Littelfuse: Fuseology; time-current curves, I²t and coordination principles