6ES7 195-7HB00-0XA0

6ES7 195-7HB00-0XA0 Siemens ET 200M BM 2×40 Active Bus Module

6ES7 195-7HB00-0XA0 is the BM 2×40 active backplane bus module used to accommodate one or two 40 mm wide S7-300 modules in a Siemens SIMATIC DP ET 200M distributed I/O station. It is not an input or output module. Instead, it provides two mechanical positions and the continuous backplane connection required by the installed signal, function or communication modules.

With the correct active rail and station configuration, the BM 2×40 forms part of the ET 200M module-change-during-operation arrangement. The active backplane remains continuous when one installed module is absent, allowing the other modules to remain reachable. This can reduce maintenance downtime, but it does not permit the bus module itself to be removed while energized.

Product Identity and Main Function

Product type: ET 200M active backplane bus module
Siemens designation: BM 2×40
Article number: 6ES7 195-7HB00-0XA0
System family: SIMATIC DP ET 200M
Slot arrangement: Two 40 mm module positions
Permitted use: One or two 40 mm wide S7-300 modules
Main function: Connecting installed modules to the active ET 200M backplane
Lifecycle notice: Siemens announced product phase-out effective 1 October 2023

Field wiring is not terminated directly on the BM 2×40. Wiring is connected to the front connector of the S7-300 module installed on it. Selection must therefore consider both the bus module and the complete MLFB number of the intended ET 200 analog input module, ET 200 digital output module or ET 200 function module.

Technical and Mechanical Data

Width: Approximately 97 mm
Height: Approximately 92 mm
Depth: Approximately 30 mm
Approximate weight: 140 g
Module capacity: One or two 40 mm wide S7-300 modules
Mounting system: Dedicated rail for ET 200M active bus modules
Backplane function: S7-300 backplane continuity between installed modules
Product class: Distributed I/O mounting and connection accessory

The earlier Siemens data sheet specifies an approximate weight of 140 g, while the Industry Mall entry lists a net weight of 0.132 kg. This small difference may result from product revision or weighing method and is not an electrical compatibility criterion. The full article number and product label remain the decisive identifiers.

Selection and Compatibility Checks

BM 2×40 and BM 1×80 must not be selected as interchangeable parts. The 6ES7 195-7HB00-0XA0 provides two separate 40 mm positions. A single 80 mm module requires the 6ES7 195-7HC00-0XA0. Although their overall widths are similar, their guides and backplane connection positions are different.

Before ordering, verify the installed IM 153 interface module, the full article number and width of every S7-300 module, the starting active bus module, the rail article number, whether the station is redundant and the STEP 7 hardware configuration.

Review ET 200 PROFIBUS and PROFINET solutions, ET 200 connection modules and other ET 200 network interfaces when checking the complete station architecture.

Installation and Commissioning Checks

Disconnect station power: The active bus module must only be installed or replaced while de-energized. Module change during operation applies to compatible S7-300 I/O modules carried by the bus module; it does not allow the BM 2×40 itself to be replaced while powered.

Use the dedicated rail: Active bus modules require a Siemens 6ES7 195-1Gxx0-0XA0 rail intended for module change during operation. A visually similar standard S7-300 rail must not be assumed to be suitable.

Join the bus modules fully, fit backplane covers to unused positions and close the end of the assembly with the correct bus module cover.

Verify the hardware project: If modules will be replaced while the station remains operational, the function must also be enabled correctly in the engineering configuration. Active bus hardware alone does not automatically provide hot swapping.

Outputs commanded by the program may become active immediately when an output module is inserted, so outputs must be placed in a safe state before maintenance.

For station power and field distribution, also review ET 200 power supply modules, ET 200 power distribution modules and ET 200 terminal blocks.

Maintenance and Pre-owned Inspection

When inspecting a used BM 2×40, check the rail latches, separator between the two positions, side coupling locks, backplane contacts and housing for cracks. Bent or oxidized contacts can cause intermittent station faults, diagnostic entries for neighboring modules or unreliable module replacement.

De-energize the ET 200M before replacing the bus module itself and follow the removal sequence in the Siemens manual. Photograph the original slot numbers, module labels and front connectors before disassembly to reduce the risk of incorrect reinstallation.

Editor’s note: The decisive distinction is the mechanical slot arrangement. Use BM 2×40 for two 40 mm modules and BM 1×80 for one 80 mm module. A photograph or the generic description “ET 200M bus module” is not sufficient for ordering. “Module change during operation” must never be interpreted as permission to remove the bus module itself while energized.

Siemens PDF Documents

+ Siemens 6ES7 195-7HB00-0XA0 technical data sheet (English PDF generated by Siemens)
+ SIMATIC ET 200M operating, installation and maintenance instructions (English, 04/2022, 271 pages)
+ Otomasyon AVM Siemens ET 200 PDF manual archive

Related Topics

For other station components, review additional ET 200 modules and accessories, ET 200 special output modules, ET 200 safety modules and Siemens ET 200 PROFIsafe solutions.

Broader technical information is available in the analog input and output guide, the pre-owned industrial automation section and the Otomasyon AVM English automation resource centre.

Reminder: Siemens 6ES7 195-7HB00-0XA0 and other SIMATIC components may be offered by Otomasyon AVM subject to availability. Units may be used, open-box or phase-out spare parts. Verify the label, mechanical condition, full MLFB number and system compatibility before ordering.

Technical notice: This information supports product identification and does not replace project engineering. Follow the current Siemens manual and the installation safety rules when mounting, replacing or servicing modules. Content reviewed: 30 October 2026.